background image

The power supply unit (power
supply carrier) is secured with
outside screws and screws at
two points inside. These have to
be loosened for deinstallation.

(Fig. 3 & 4)

When uninstalling, itʼs best first
to remove the plug-in cards at
slot 1 and slot 8 using the plug-in
card removal tool.

To press out the power supply unit
carriers, the plug-in card removal
tool is alternately placed on the nuts
on the side and pressed. This relea-
ses the plug contacts of the power
supply carrier from the base.
(see Fig. 5).

(See also Chapter 5.5. Installing
plug-in cards.)

If in a V16 base a single power unit (VSN 1) is to be sub-

sequently exchanged for a redundant one (VSN 2) or vice

versa, the change must also be set in the software of the

base device. This is done using the KC 3 manual device.

After exchanging the power unit, close the housing, apply

mains voltage, and connect the KC 3.
The following display appears:

After pressing the "Menu" key the setup display

appears.

Select

line 3

with the

or

arrow key.

Use the

or

arrow key to set the installation status

to VSN 1 (Power A) or VSN 2 (Power A+B).

An incorrect setting of the VSN … installation status

leads to faulty signaling (front LEDs) and incorrect

function displays of the HE programming software.

3.4

LNB remote supply (for VMS 616)

When using the inter-

nal SAT VMS 616 dis-

tributor field, the LNB

remote power supply

can be switched on for

up to four of the six

SAT inputs (each max.

250 mA, short-circuit

proof). On the mainbo-

ard there are four jum-

pers between card slot

four and five with

6

3 Preparing the base unit

3 Preparing the base unit

ASTRO V16

Version X.XX

1= deutsch

(next<>)

V16 Setup

VMS 616

Yes

Power

A+B

Password

Off

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Содержание V16

Страница 1: ...SAT HEADEND 1 6 Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8 Power A Power B ...

Страница 2: ...pter Interlocking device Redundant power supply Slots SAT distribution board 2 temperature regulated fans The V16 is CE certified and complies with all relevant EN standards Changes and printing errors reserved Version 02 2009 LED indicator lamps ...

Страница 3: ...ment 11 9 Technical specifications 12 Accessories 12 Contents 1 Safety information 3 1 Pictographs and safety information Warns about situations in which there is danger of lethal injury due to hazardous electrical voltage and non com pliance with these instructions Warns about various hazards to health environment and materials This is a general information symbol Recycling All of our packaging m...

Страница 4: ... Because of fire hazard due to lightening it is recommended that all mechanical parts e g V16 equipotential busbars distributors etc are mounted on non combustible under lays Combustible materials include wooden beams woo den boards plastics etc 2 Hazard and safety information 2 Hazard and safety information 2 2 Opening the housing Before opening the housing Be careful when doing maintenance work ...

Страница 5: ...h the middle screw 3 2 Installation and deinstallation of SAT VMS 616 distribution board If a SAT VMS 616 distribution board is to be subsequently installed to a V16 base or an already installed VMS 616 is to be removed the change must be set in the software of the base device This can be done either by using the ASTRO HE programming software or the KC 3 manual device For this after installing or ...

Страница 6: ...ne using the KC 3 manual device After exchanging the power unit close the housing apply mains voltage and connect the KC 3 The following display appears After pressing the Menu key the setup display appears Select line 3 with the or arrow key Use the or arrow key to set the installation status to VSN 1 Power A or VSN 2 Power A B An incorrect setting of the VSN installation status leads to faulty s...

Страница 7: ...nputs 11 14 can be switched via software to the last 12 outputs card 3 tuner A to card 8 tuner B geschaltet werden 7 which the remote power supply can be activated for each of the inputs Activated remote power supplies are indicated by adjacent LEDs Fig 6 SAT inputs for which LNB remote power supply can be activated inputs 11 13 15 and 16 3 5 3 5 Remote supply voltage on HF output If an ASTRO netw...

Страница 8: ... set is connected to the PC directly or via the bus system 4 3 Temperature The current temperature mainboard surface is display ed in line 4 5 Installing plug in cards Lift out and remove the interlocking device by lightly pressing to the right Fig 8 Itʼs a good idea to place the bar on top of the V16 while the card is being installed The connection labels speed up correctly assigning for example ...

Страница 9: ...ds 9 Plug in the card Connect the tuner A connection cable to an available output of the SAT VSF 8 distribution board that carries the required polarization Twin cards Proceed correspondingly with the connection cable from tuner B 5 3 Cards for terrestrial conversion Because the SAT VMS 616 distribution board is suitable exclusively for SAT intermediate frequencies 950 2150 MHz the inputs from ter...

Страница 10: ...or LEDs that monitor functions The topmost 8 LEDs provide information about the installed plug in cards top LED slot 1 far left to eighth LED slot 8 far right LED off no plug in card installed Red LED plug in card installed but not func tioning correctly e g no SAT signal Green LED plug in card installed and in operation The bottom two LEDs indicate the state of the power supply unit s For an inst...

Страница 11: ...justment The optimal output level measured at the output of the base device is as follows 100 dBµV for PAL channels 90 dBµV for QAM channels 96 dBµV for radio FM channels To enable the setting the level regulators of the indivi dual plug in cards are set accordingly Fig 14 The level adjustment can be done via HE programming software depending on the plugin card Note Under no circumstances should a...

Страница 12: ...ent temp C 0 50 Housing H x W x D mm without mounting bracket 340 x 426 x 277 19 7 HE Basis with front side mounting bracket 340 x 491 x 277 with rear mounting bracket 340 x 491 x 290 3 HE for air flow unit Weight of V16 1 base unit kg 9 6 Type VSN 1 single power supply VSN 2 dual power supply Order no 350 210 350 220 Rated voltage V 230 6 10 50 60 Hz 230 6 10 50 60 Hz Power input VA W 196 190 208...

Страница 13: ...78 Transmission loss dB 12 Decoupling input input dB 25 Remote voltage supply 12 V mA 250 4 outputs Current consumption 5V mA 650 Type VSF 8 VSF 42 Order no 380 280 380 281 Input freq range MHz 950 2150 Optimum input level dBµV 68 74 Ripple dB 1 Skew position dB 2 1 Return loss input output dB 10 Decoupling outputs dB typ 40 Transmission loss of loop through dB 0 1 outputs 1 8 8 1 Inputs outputs Ω...

Страница 14: ...monitoring timer protects against excessive telephone charges automatic hang up if there is no communicati on within five minutes G Operating software can be updated via serial interface i e software updates without installation work X BC 2 additional features G Remote control via GSM modem G Error messaging via SMS alarm messaging to max 3 phone numbers G 4 time partitions can be set for each tim...

Страница 15: ...reconfiguring the operating parameters for the redundancy module is not required The following processes are performed automatically G deactivating HF the failed module G copying all operating parameters of the failed module to the redundancy module G activating HF the redundancy module With the HE programming software up to twenty X 5 X 8 V16 headend devices can be saved in a configuration file F...

Страница 16: ...RO Strobel Kommunikationssysteme GmbH Olefant 1 3 D 51427 Bergisch Gladbach Bensberg Tel 49 0 22 04 405 0 Fax 49 0 22 04 405 10 e mail kontakt astro kom de http www astro kom de Germany 82 261403 GB 01 09 ...

Отзывы: