If possible, you should choose a location where 

the chimney will pass through the house without 

cutting floor or roof joists (see fireplace dimen-

sions 

Page 9

).

Usually, no additional floor support is needed 

for the fireplace.  The adequacy of the floor 

can be checked by first estimating the weight 

of the fireplace system.  Weights are given 

on 

Page 23

.   Note the floor construction and 

consult your local building code to determine 

if additional support is needed. 

The Montecito fireplace may be installed 

directly on the floor or on a raised base (for 

proper guidelines, refer to “Hearth Extension 

Requirements”) and a minimum of 6’8” (2 m) 

measured from the base of the appliance to the 

ceiling is required.

When selecting the location, the chimney outlet 

position and the direction of the wind are impor-

tant factor affecting the chimney performance. 

To allow a maximum draft and to reduce wind 

turbulence, the chimney must:

•  Penetrate the highest part of the roof.

•  Be installed as far as possible of roof offsets, 

trees or any other obstructions that may 

cause wind turbulence and back drafts in 

the chimney.

•  The least amount of offsets (elbows) pos

-

sible.

 NOTE: 

A maximum of 2 offsets is 

allowed.

GLASS CARE

Glass Replacement

The glass used for the Montecito™ fireplace is 

a high temperature ceramic glass (1,400° F / 

760° C).  If the glass breaks, it must be replaced 

with an identical ceramic glass. Tempered 

glass or ordinary glass will not withstand the 

high temperatures of the Montecito fireplace.  

Replacement glass should be purchased from a 

IHP dealer (see “Replacement Parts”, 

Page 23

)

.  

DO NOT OPERATE THE UNIT WITH CRACKED 

OR BROKEN GLASS. 

Glass Cleaning

The Montecito fireplace is designed to keep 

the glass clean under normal operating condi-

tions. If the Montecito fireplace is operated 

continuously with the combustion air controls 

closed, the glass will tend to get dirty unless 

the fuel, firebox and glass are maintained at 

hot temperatures (see “Refueling For Best 

Performance”).  To clean the glass, there are a 

number of specially designed cleaners.  Your 

authorized IHP dealer can recommend a suit

-

able cleaner which is available in your area.  

Regular household glass cleaners will not clean 

creosote.  Do not use abrasives such as steel 

pads, steel wool or oven cleaner as they will 

scratch the glass.

DO NOT USE CHEMICAL GLASS CLEANERS 

ON PAINTED SURFACES AS IT MAY CAUSE 

THE PAINT TO PEEL.
CAUTION : DO NOT ALLOW WINDOW CLEANER 

TO GET IN CONTACT WITH DOOR GASKET OR 

PAINT ON FACADE OR DOOR.  ONCE CLOSED, 

CONTACT OF GLASS CLEANER WITH THE 

FIREPLACE FACADE CAN PROVOKE PAINT 

PEELING OFF.

Gasket

Length Dimensions

Part No.

Steel Door

Around 

Glass

69

(1753)

1 x 3/16

(25 x 4.8)

PR-SR1685D

On Door 

Frame

73

(1854)

5/8 dia.

(15.9)

PR-SR1823G 

Cast Door

Around 

Glass

69

(1753)

1 x 5/16

(25 x 4.8)

PR-SR1823H

On Door 

Frame

73

(1854)

5/8 dia.

(15.9)

PR-SR1823G 

Table 1                      

        Inches (millimeters)

FIREPLACE INSTALLATION

Locating The Montecito Fireplace

The best location to install your fireplace is 

determined by considering the location of 

windows, doors, and the traffic flow in the room 

where the fireplace is located, allowing space 

in front of the unit for the hearth extension and 

the mantel, and taking into consideration the 

location of the hot air ducts (optional), outside 

air kit and chimney.  

Gasket Replacement

Remove the door from the unit (see 

Page 6

)

 

and lay it on a clean unabrasive surface. To 

replace the gasket, first remove all of the old 

gasket and gasket cement.  Make sure that the 

surface is totally clean before applying new 

cement (a high temperature silicone caulking 

rated at 500° F [260° C], is suitable) or adhesion 

problems may result.  Apply gasket cement to 

the gasket channel and install the new gasket.  

This replacement part is available from your IHP 

dealer in the following dimensions:

Marginal Location

Wind Direction

Location

Not

Recommended

Outside Air Intake

Facing the Wind

Location

Not 

Recommended

Location Recommended

Figure 6

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

17

Содержание MONTECITO MONTE

Страница 1: ...t of glass doors Install this fireplace in a square and plumb condition using shims as necessary at sides and or bottom Install the fireplace only as described in these instructions This installation...

Страница 2: ...ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air WARNING Neither the manufacturer nor the seller warrants smoke free operat...

Страница 3: ...e kit Required Order Separately See Page 20 UZY5 blower included in the fireplace VRUW Blower Speed Control included Outside air kit Included w Fireplace OPTIONAL EQUIPMENT Additional Equipment option...

Страница 4: ...g 10 to 20 minutes after reloading depending on the heat and on the moisture content of the wood Onceyouhavereachedthedesiredtemperature the air boost can be closed and the primary air set to a medium...

Страница 5: ...ces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote resi...

Страница 6: ...door seal Close the door on the paper in at least eight points It is normal to feel only a slight amount of friction The door gasket does not need to be tight in all areas since a small amount of leak...

Страница 7: ...er the entire width of the fireplace The combustible floor in front of the fireplace mustbecoveredwithanon combustiblemate rial tile marble stone etc See Figures 7B Cold climate INSTALLATIONS Climates...

Страница 8: ...strations and photo graphs are not to scale consult installation instructions Product designs materials dimensions specifications colors and prices are subject to change or discontinuance without noti...

Страница 9: ...tside Walls Of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 Level 7 2 1 m Min 6 8 2 m Min 8 2 4 m Level 42 1067mm 2 X 3 Min 51mm x 76mm Rock Board or Other Noncombustible F...

Страница 10: ...ure 12 Fireplace Blower The fireplace comes equipped with a heat acti vated blower It is located in the bottom of the fireplace towards the back It uses 120V and must be connected to the main electric...

Страница 11: ...a 5 diameter flexible pipe for the complete run up to thirty 30 feet and a 6 diameter pipe for a run of up to forty 40 feet The duct system must be installed respecting the following 1 Removetheplates...

Страница 12: ...hen offsets are used the pipe may not penetrate a ceiling or floor unless it is running vertical no 30 offsets Outside Intake Screw Opening Facing Down Wall Aluminum Tape Plastic Cover Insulation Flex...

Страница 13: ...oofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof using roofing nails 6 Place the spacers and the storm collar over the flashing and tight...

Страница 14: ...ne up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below install a firestop...

Страница 15: ...22 mm 6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 243...

Страница 16: ...bustible wall with the chimney at a 30 or 45 angle an angled firestop or wall radiation shield must be installed Only one is required NOTE 45 angle for Canada only RSMI45 In cold climate locations cli...

Страница 17: ...glass are maintained at hot temperatures see Refueling For Best Performance To clean the glass there are a number of specially designed cleaners Your authorized IHP dealer can recommend a suit able c...

Страница 18: ...CHIMNEY Offset Support Roof Support ASHT HT6103 6 dia 28feet 8 54m 29feet 8 84 m S 2100 HT6000 6 dia 18feet 5 49m 20feet 6 1 m AC 6 dia 40feet 12 19m 50feet 15 20 m Table 6 CHIMNEY CHASE AND MULTIPLE...

Страница 19: ...nry chimney 2 In the middle of the oval drill a hole in the masonry chimney at 30 3 Increase the size of the hole until a 30 Tubinox liner elbow can be easily slipped through 4 Slide the liner down fr...

Страница 20: ...7B26ZE45 H8949 Telescopic length 8 dia 15 to 26 7B26ZLA H8950 Adjustable length 8 dia 2 5 7B26ZL2A H8951 Length two 2 feet 8KL2 H8954 Length one 1 feet 8KL1 H8953 Wall radiation shield 8 I D 7B26ZR H...

Страница 21: ...ron Log Retainer Supports Grate 2 PR SR2324 Cast Iron Log Retainer Bar PR SR2323 Gasket Kit Glass 69 1 x 5 16 steel and cast doors PR SR1823H Gasket Kit Steel Door Frame 73 5 8 dia PR SR1685D Gasket K...

Страница 22: ...Steel Chimney 6 I D and 8 O D Double Wall Stainl Steel Listed to CAN UCL S604 and UL 103HT Description Part Cat No Lengths and Misc Chimney Components 8 length 6 Dia 6L8 6L8 12 length 6 Dia 6L12 6L12...

Страница 23: ...escription Cat Part No 6 Length 6 Dia 6LL6 6LL6 12 Length 6 Dia 6LL12 6LL12 24 Length 6 Dia 6LL24 6LL24 36 Length 6 Dia 6LL36 6LL36 48 Length 6 Dia 6LL48 6LL48 Adjustable Length 7 to 11 6 Dia 6L7A 6L7...

Страница 24: ...24 NOTES...

Страница 25: ...inder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning dry s...

Страница 26: ...dealer for any questions or concerns Replacement parts See Page 21 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through you...

Отзывы: