background image

Astria.us.com

126810-01B

8

AIR FOR COMBUSTION AND VENTILATION

Continued

Figure 3 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

INSTALLATION

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining 
unconfined space. When ventilating to an 
adjoining unconfi ned space, you must provide 
two permanent openings: one within 12" of the 
ceiling and one within 12" of the fl oor on the wall 
connecting the two spaces

 (see options 1 and 

2,  Figure 2).

 You can also remove door into 

adjoining room 

(see option 3, Figure 2). 

Follow 

the 

National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation

 

for required size of ventilation grills or ducts.

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation 
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling 
and one within 12" of the fl oor. Connect these 
items directly to the outdoors or spaces open 
to the outdoors. These spaces include attics 
and crawl spaces. Follow the 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 54, Air for 
Combustion and Ventilation

 for required size 

of ventilation grills or ducts. 

IMPORTANT:

 Do not provide openings 

for inlet or outlet air into attic if attic has a 
thermostat-controlled power vent. Heated air 
entering the attic will activate the power vent.

Figure 2 - Ventilation Air from Inside Building

NOTICE: This appliance is in-
tended for supplemental heat-
ing. Use this heater along with 
your primary heating system. Do 
not install this heater as your pri-
mary heat source. If you have a 
central heating system, you may 
run system’s circulating blower 
while using heater. This will help 
circulate the heat throughout the 
house. In the event of a power 
outage, you can use this heater 
as your primary heat source.

NOTICE: State or local codes may 
only allow operation of this appli-
ance in a vented confi guration. 
Check your state or local codes.

 WARNING: A qualifi ed ser-

vice person must install heater. 
Follow all local codes.

 WARNING: Make sure the 

selector switch is in the OFF 
position before installing heater.

 WARNING: Seal any fresh 

air vents or ash clean-out doors 
located on fl oor or wall of fi re-
place. If not, drafting may cause 
pilot outage or sooting. Use a 
heat-resistant sealant. Do not 
seal chimney fl ue damper.

f i r e - p a r t s . c o m

Содержание Sheridan18NM

Страница 1: ...it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on Page 6 of this manual Installation and Operation Instruc...

Страница 2: ...ANSI Z21 11 2 Exception DO NOT install this appliance in a factory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs WARNING This i...

Страница 3: ...proper operation of this fireplace WARNING Do not allow fans to blow directly into the heater Avoid any drafts that alter burner flame patterns Ceiling fans can create drafts that alter burner flame...

Страница 4: ...utside air ven tilation to run properly This heater has an oxygen depletion sensing ODS pilot light safety system The ODS shuts down the heater if not enough fresh air is available See Air for Combust...

Страница 5: ...et assembly from carton NOTE Do not pick up assembly by logs This could damage heater Always handle assembly by grate CAUTION Donotremovethe data plates from the grate as sembly The data plates contai...

Страница 6: ...ill ensure proper venting of vented fuel burning appliances PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Com bustion and Ventilatio...

Страница 7: ...__ volume of space x 20 Maximum Btu Hr the space can support Example 2560 cu ft volume of space x 20 51 200 maximum Btu Hr the space can sup port 3 Add the Btu Hr of all fuel burning appliances in the...

Страница 8: ...he outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ve...

Страница 9: ...hing or other flammable objects are less than 42 from the front top or sides of the heater in high traffic areas in windy or drafty areas CAUTION This appliance cre ates warm air currents These cur re...

Страница 10: ...hood accessory 24 Model Only See Figure 5 for minimum clearances Figure 5 Heat Resistant Material Slate Marble Tile etc Above Fireplace Noncombustible Material Distance A Requirements for Safe Instal...

Страница 11: ...fireplace opening and mantel shelf If you do not meet the clearances listed below you will need a hood Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top...

Страница 12: ...mbustible flooring see Figure 9 14 Min Combustible Material Noncombustible Material Hearth 5 Min Combustible Material NOTICE Surface temperatures ofadjacentwallsandmantelsbe comehotduringoperation Wal...

Страница 13: ...per open Installation instructions are included with clamp accessory See chart below for minimum permanent flue opening you must provide Attach damper clamp so the minimum permanent flue open ing will...

Страница 14: ...ne LP gas equipment shutoff valve test gauge connection sediment trap tee joint pipe wrench approved flexible gas line with gas connec tor if allowed by local codes provided For propane LP units the i...

Страница 15: ...old gas control with wrench when connecting it to gas piping and or fittings WARNING Testallgaspiping and connections internal and external to unit for leaks after installing or servicing Correct all...

Страница 16: ...gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter to equip ment shutoff valve for natural gas or propane LP supply to equipment shutoff v...

Страница 17: ...tructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life WARNING Damper handle will be hot if heater has been running NOTICE Duringinitialoperation of...

Страница 18: ...ntrol knob counterclockwise to the ON posi tion 10 Wait one minute and switch selector switch to the ON position to light burners 11 Set flame adjustment knob to any level between HI and LO 12 To leav...

Страница 19: ...cell for LCD both included Remote receiver requires 4 AA 1 5V alkaline batteries included Operating Frequency 303 875 MHz 1 After lighting let pilot flame burn for about one minute Turn control knob...

Страница 20: ...flame pattern and burner flame patterns often PILOT FLAME PATTERN Figure 20 shows a correct pilot flame pattern Figure 21 shows an incorrect pilot flame pat tern The incorrect pilot flame is not touch...

Страница 21: ...three months during operation and have heater inspected yearly by a qualified service person We also recommend that you keep the burner tube clean and free of dust and dirt We rec ommend using compres...

Страница 22: ...inched by any metal or tubing Keep igniter cable dry 3 Replace battery 4 Replace igniter cable 5 Replace electronic igniter 6 Replace pilot assembly When igniter button is pressed there is spark at OD...

Страница 23: ...eaning and Mainte nance Page 21 or re place ODS pilot assembly 6 Hand tighten until snug then tighten 1 4 turn more 7 Replace pilot assembly 8 Replace control valve Burner does not light after ODS pil...

Страница 24: ...ked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see Pages 9 through 12 4 Clean burner see Clean ing and Maintenance Page 21 or replace burner orifice White po...

Страница 25: ...supply propane LP only 3 Gas leak See Warning statement at top of page 1 Open window to ventilate room Stop using odor causing products while heater is running 2 Refill supply tank pro pane LP only 3...

Страница 26: ...o low If so contact your local propane LP or natural gas supplier TECHNICAL SERVICE You may have further questions about instal lation operation or troubleshooting Please contact your IHP dealer for a...

Страница 27: ...4NM F0093 Sheridan24PM 7 20 3 6 9 4 6 1 25 8 5 23 24 10 11 25 21 12 13 16 10 6 14 2 15 18 17 22 19 Installed in BTB Models Only 17 Remote Control and Receiver WARNING Failure to po sition the parts in...

Страница 28: ...2 Valve LP 1 12 J5239 Valve Bracket 1 13 J4596 Electronic Igniter 1 14 J3840 Control Knob Extension 1 15 J3841 Control Knob Extension 1 16 J3656 Fan Switch 1 17 J4871 Remote Control and Receiver 1 18...

Страница 29: ...GA6050 For all models Helps deflect heat away from mantel or wall above fireplace Fits openings 28 to 48 wide DECORATIVE ASH BED CONTROL COVER KIT SIX PACK Cat No F1759 Model CDABKA 6 DECORATIVE ASH B...

Страница 30: ...ote is programmable for your convenience and has a large bright LCD Touch Screen for easy use MODE SET PROG ON OFF REMOTE AND RECEIVER WITH WHITE WALL PLATE Cat No F2236 Model RCKIT 4001 For all Remot...

Страница 31: ...o the Product will produce excessive temperatures and could result in a re hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided wit...

Страница 32: ...butor for fireplace code information Printed in U S A 2014 Innovative Hearth Products P N 126810 01 Rev B 05 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Astria us com Record the following imp...

Отзывы: