background image

Astria.US.com

126875-01_G

6

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or uncon-

fined space.

Space:

 Includes the room in which you will install fireplace plus any 

adjoining rooms with doorless passageways or ventilation grills 

between the rooms.
1.  Determine the volume of the space (length x width x height).
  Length x Width x Height =__________cu. ft. (volume of space)
  Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling 

height) = 2,560 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to determine the maximum Btu/

Hr the space can support.

   _______ (volume of space) x 20 = (Maximum Btu/Hr the space 

can support)

  Example: 2,560 cu. ft. (volume of space) x 20 = 51,200 (maximum 

Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in the space.
  Vent-free fireplace  ________Btu/Hr
  Gas water heater*  ________Btu/Hr
  Gas furnace 

________Btu/Hr

  Vented gas heater  ________Btu/Hr
  Gas fireplace logs  ________Btu/Hr
  Other gas appl ____Btu/Hr
 Total 

=_______Btu/Hr

  * Do not include direct-vent gas appliances. Direct-vent draws 

combustion air from the outdoors and vents to the outdoors.

 

Example:

 

  Gas water heater        40,000 Btu/Hr
  Vent-free fireplace  +  33,000 Btu/Hr
  Total 

=  73,000 Btu/Hr

4.  Compare the maximum Btu/Hr the space can support with the actual 

amount of Btu/Hr used.

   ______ Btu/Hr (maximum the space can support) 
   ______ Btu/Hr (actual amount of Btu/Hr used)
 

Example:

     51,200 Btu/Hr (maximum the space can support) 

                      73,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the example is a confined space because the actual Btu/

Hr used is more than the maximum Btu/Hr the space can support. 

You must provide additional fresh air. Your options are as follows:

A.

  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. See Ventilation Air 

From Inside Building.

B.

 Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.

  Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room 

unconfined. 

If the actual Btu/Hr used is less than the maximum Btu/Hr the 

space can support, the space is an unconfined space. You will need 

no additional fresh air ventilation.

 WARNING: If the area in which the heater may be 

operated does not meet the required volume for indoor 

combustion air, combustion and ventilation air shall 

be provided by one of the methods described in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 

International Fuel Gas Code, or applicable local codes.

VENTILATION AIR
Ventilation Air From Inside Building 

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two per-

manent openings: one within 12" of the ceiling and one within 12" of the 

floor on the wall connecting the two spaces (see options 1 and 2, Figure 

2). You can also remove door into adjoining room (see option 3, Figure 

2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for 

Combustion and Ventilation for required size of ventilation grills or ducts.

AIR FOR COMBUSTION AND VENTILATION 

Continued

 

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and one 

within 12" of the floor. Connect these items directly to the outdoors or 

spaces open to the outdoors. These spaces include attics and crawl 

spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for 

Combustion and Ventilation for required size of ventilation grills or ducts. 

IMPORTANT:

 Do not provide openings for inlet or outlet air into attic 

if attic has a thermostat-controlled power vent. Heated air entering 

the attic will activate the power vent.

Figure 3 - Ventilation Air from Outdoors

Figure 2 - Ventilation Air from Inside Building

Outlet 
Air 

Ventilated 
Attic  

Outlet 
Air 

Inlet 
Air 

Inlet Air 

Ventilated  

Crawl Space 

To 

Crawl

Space

To Attic

Or 

Remove 

Door into 

Adjoining 

Room, 

Option 

Ventilation Grills  

Into Adjoining Room, 

Option 2 

Ventilation 

Grills  

Into Adjoining  

Room, 

Option 1 

12" 

12" 

Содержание F1219

Страница 1: ...r adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on page 5 of this manual WARNING If the information in these instructions is not followed...

Страница 2: ...ore trying to assemble operate or service this heater Improper use of this heater can cause serious injury or death from burns fire explo sion electricalshockandcarbonmonoxidepoisoning DANGER Carbon m...

Страница 3: ...replace is designed to be smokeless If logs ever appear to smoke turn off fireplace and call a qualified service person Note During initial operation slight smoking could occur due to log curing and f...

Страница 4: ...ASSACHUSETTS REQUIRE MENTS These appliances are approved for installation in the US state of Mas sachusetts if the following additional requirements are met Un vented Room Heaters shall be installed i...

Страница 5: ...gs exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or less with openings gasketed or sealed and b weather stripping has be...

Страница 6: ...ortoadjoining room or add ventilation grills between rooms See Ventilation Air From Inside Building B Vent room directly to the outdoors See Ventilation Air From Outdoors C Install a lower Btu Hr fire...

Страница 7: ...moisture See Air for Combustion and Ventilation page 5 CHECK GAS TYPE Use the correct gas type natural or propane LP for your fire place If your gas supply is not correct do not install fireplace Cal...

Страница 8: ...ning 1 12 A 24 2 9 B 21 3 6 C 18 4 4 D 16 5 2 E 14 A B C D E 1 2 3 4 5 Wall Supplied firebox hood must be used at all times Note All vertical measurements are from top of fireplace hood opening to bot...

Страница 9: ...75 01_G 9 17 1 2 29 5 8 29 5 8 16 3 8 7 1 8 1 7 8 8 1 4 44 1 8 1 1 55 1 8 52 47 16 1 2 11 3 4 8 1 4 5 8 INSTALLATION Continued Figure 8 ParisLights43 Series Dimensions Gas Line Access Gas Line Access...

Страница 10: ...e LP supply This fireplace requires anexternalregulator notsupplied Installtheexternal regulatorbetweenthefireplaceandpropane LPsupply WARNING Never connect natural gas fireplace to private non utilit...

Страница 11: ...trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into fireplace gas controls If sediment trap is not installed or is instal...

Страница 12: ...o gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Figure 13 2 Pressurize supply piping system by either openin...

Страница 13: ...uide screw the rear panel to the fireplace as shown in Figure 16 INSTALLING HOOD 1 Loosen screws at top of face opening and slide hood through screws as shown in Figure 17 2 Tighten screws securing ho...

Страница 14: ...place unscrew 4 corner brackets from the firebox top See Figure 21 2 Remove 2 side walls and then the rear wall Discard rear wall 3 Replace 2 side walls and reinstall the corner brackets Installing Ac...

Страница 15: ...l stay ON when the main burner shuts OFF Figure 26 Gas Module Right Side Figure 27 Gas Module Left Side Remote Control Feature The module has a built in remote control receiver that allows the user to...

Страница 16: ...lied with the unit into the battery compart ment It is recommended that ALKALINE batteries always be used for this product Be sure the batteries are installed with the and ends facing the correct dire...

Страница 17: ...default or degrees C Press the UP and DOWN Buttons simultaneously to change between degrees F and C SET TEMP While in THERMOSTAT mode press the UP or DOWN Button to change the SET TEMP 45 90 deg F 7 3...

Страница 18: ...e A icon and Flame A setting number will flash in the FLAME Zone LIGHT ADJUSTMENT Transmits a light setting command to the control module to adjust the light output level Available settings are 0 off...

Страница 19: ...liance requires 120V electricity for normal operation Control module should be plugged into electrical outlet located underneath firebox bottom Back up battery supply is available for power outages 1...

Страница 20: ...end using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compressed air in a can If using compressed air in a can please follow the directions...

Страница 21: ...e running Some burner flame holes may become blocked by debris or rust with no flame present If so turn off fireplace and let cool Remove blockage Blocked burner flame holes will create soot BURNER FL...

Страница 22: ...V MAX 15 AMPS 110V POWER IPI I S MAX 15 AMPS To Rocker Switch To J Box To J Box Pilot Main HI LO DC Motor Drive Light Module Black Black Brown Red Orange Orange To Ground Igniter Sensor PILOT BATTERY...

Страница 23: ...t local propane LP gas company 3 Clean ODS pilot see Cleaning and Main tenance page 20 or replace ODS pilot assembly 4 Replace gas regulator 1 Contact local natural or propane LP gas company 2 Clean b...

Страница 24: ...ng while cooling 1 Burner orifice is clogged or damaged 2 Damaged burner REMEDY 1 Check burner for dirt and debris If found clean burner see Cleaning and Mainte nance page 20 1 Refer to Air for Combus...

Страница 25: ...y 3 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement above 2 Control valve or gas control...

Страница 26: ...Astria US com 126875 01_G 26 PARTS MODELS PARISLIGHTS43ZEN PARISLIGHTS43ZEP 11 7 4 3 8 8 8 8 14 15 16 17 18 19 20 24 21 5 22 23 6 2 1 13 10 9 12...

Страница 27: ...e 32 1 J6989 Orifice 49 1 7 J6819 Brass Elbow 1 8 J6757 Light Bulb G9 120V 20W 4 9 J5207 Flat Washer 7 10 J4775 Bulkhead Fitting 1 11 J6834 Brass Elbow 2 12 J4714 Flextube Dormont 1 13 J6694 Burner Ga...

Страница 28: ...Astria US com 126875 01_G 28 PARTS MODELS PARISLIGHTS43ZEN PARISLIGHTS43ZEP 1 4 6 2 8 9 7 5 3 5 11 12 13 14 10 7 8...

Страница 29: ...e of non approved parts can result in poor performance and safety hazards KEY NO CATALOG NO DESCRIPTION ParisLights43ZEN F1219 ParisLights43ZEP F1220 QTY 1 J6630 Top Spacer 4 2 J6566 Top Nailing Flang...

Страница 30: ...P 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Visit us at Astria US com SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not pro...

Страница 31: ...ccident riot fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjec...

Страница 32: ...name P126875 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Co...

Отзывы: