ALASKA / SIBERIA / BERING SERIES · Cooler EF
AIR/WATER
–
WATER/WATER
© FLUIDRA 2019 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT.
Pag: 27
ENGLISH
6.4.7
FAN OPERATING CONDITIONS
When F27=-10, the fan will run at normal speed. In the PROHEAT II model, the fan will rotate at
this fixed speed.
When F27≠
-10
,
If the ambient temperature ≤F27(20ºC), the fan will run at maximum speed.
If F27 (20ºC) < Ambient temperature < F28 (45ºC), the fan will run at minimum speed.
If ambient temperature ≥F28 (45ºC), the fan will run at
maximum speed.
The PROHEAT II machines run at normal speed F27=-10ºC.
6.4.8
REMOTE SWITCH
When the remote switch is closed:
If the unit is running. The unit works normally
If the unit is stopped. The unit stops.
When the remote switch is open:
If the unit is running. The unit stops and the screen display "OFF".
If the unit is stopped. The unit stops.
6.5
PROTECTION SYSTEMS
6.5.1
COMPRESSOR DELAY PROTECTION
The compressor delay time is adjustable (F21) and set to 5 minutes by default. The regulator
uses this time setting to prevent continuous ON/OFF cycles. When the compressor has been
running and then stops, the next time it is started up, the regulator will check that the period of
time has passed before starting it up again; if not, it will wait for 5 minutes until the compressor
starts again. If the machine has just been started up, there will be a 5-minute wait before the
compressor starts.
6.5.2
PHASE CONTROL
When the 3 phases of the machine are connected incorrectly or a fault is detected in any of the
phases, the machine will stop and the error code "A91" will be displayed.
6.5.3
OVER CURRENT PROTECTION (If 23=0, disable)
Consumption is checked three seconds after the compressor starts up; if the current > F23 for 5
seconds, the machine will stop and error "A93" will be displayed.