ALASKA / SIBERIA / BERING SERIES · Cooler EF
AIR/WATER
–
WATER/WATER
© FLUIDRA 2019 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT.
Pag: 20
ENGLISH
The internal list of parameters is as follows:
Concept
Code
Parameter name
Range
Factory
setting
Unit
Observations
Temperature
F11
Temperature setting point
F14
–
F13
28
C
F12
Temperature difference
1
–
10
1
C
F13
Max setting temperature
30
–
100
40
C
F14
Min setting temperature
1
–
29
10
C
F15
Auto mode temperature
difference
0
–
20
1
C
F17
ID
1
–
255
9
-
F19
Password (Installer)
0
–
999
-
-
0: Without password (Consult your
salesman)
F20
Password (Manufacturer)
0
–
999
-
-
0: Without password (Consult your
salesman)
Compressor
Defrost
F21
Compressor delay time
1
–
10
8
min
F22
Compressor Phase protection
Number of circuits*
0
–
1
0
ONE PHASE
0: no protection
1
:
have protection
1
THRE
PHASE
F24
Water fiow switch delay time
1-2
1
1
:
1 Compressor
2
:
2 Compressors
F25
Low limit temperature
0-100
1
min
F26
The lower limit temperature of
Low speed operation
-20 - 10
0
Not enabled select -20
F27
The upper limit temperature of
Low speed operation
-10~30
-10
C
1. Temperature differential ±1°C.
2. Always working at low speed (-
10ºC).
F28
OPERATING MODES ENABLED
35~100
44
C
Temperature differential ±1°C
F29
Defrost start temperature
0 / 1 / 2 / 3
2
0: Automatic mode (C/H)
1: Heat mode (Heat)
2: Cool mode(Cool)
3: Choose the mode (M)
Desescarche
Remote
control
F31
Defrost end temperature
-10
–
0
-3
C
F32
Defrost start time
5
–
35
15
C
F33
Max defrost time
1
–
120
1
min
F34
Pipe1(2) fault
,
Defrost start
temperature
3
–
20
10
min
F35
Alarm Delay Time after Defrost
-10 - 20
7
C
Ambient Temp.
Defrost according to F33/34.
F36
4-way valve mode
0
–
120
3
min
F37
Remote Cooling MODE
0 - 1
1
1: heating 4-way valve has
electricity
0: heating 4-way valve has not
electricity
Control
Remoto
Voltage
consumption
F38
Remote Heating MODE
0
–
1
0
0: Always cooling, and the set point
is not taken into account
1
The set point is taken intoaccount
F39
Maximum consumption
protection
0
–
1
0
0: Always cooling, and the set point
is not taken into account
1
The set point is taken into
account
Voltaje y
Consumo
F40
Temperature setting point
2-40
Depends on
the model
of the
machine
10
0
:
not enable
TABLE 4
TABLE 5
TABLE 6
F42
Alarm delay time due to excessive
consumption
0
–
30
3
S