V-HEAT SERIES · AIR/WATER SYSTEM
© ASTRALPOOL 2018. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Page 10 of 72
ENGLISH
3.2 Installation Conditions
Do not install the unit near a flammable gas source, since a gas leak may occur and cause an explosion.
According to the place where the unit must be
installed (humid place, etc.), install electrical
protection by a 30 mA differential circuit breaker.
Otherwise, an electrical discharge may take place.
Condensers must have been completely drained.
Otherwise, the water could leak out of the unit and
dampen and damage its components.
WARNING
Do not leave a damaged installation.
The unit could cause an accident.
Do not mount or place anything upon the unit. The
fall of the object or the unit could cause an accident.
Verify the network compatibility with the data specified in the unit before starting to install the heat pump.
In order to obtain an optimal operation of the heat pump, certain norms must be respected:
A.
Use of free chlorine: 0.5 – 2 ppm
B.
Bromine: 6.6 mg/l max.
C.
pH: 7.2 to 7.6
D.
Salt : 4-6 gr/l
When washing the filter of the filtering pump for swimming pools, the heat pump must be disconnected.
SPECIFIC INSTRUCTIONS:
It is obligatory for users contact a specialized company that has experience installing and
repairing heat pumps. Users should not install or repair the heat pump themselves nor should another person do it.
The operating environment of the unit usually varies between 8 ºC and 50 ºC.