Operation Data Settings
The unit’s operation data can be set on the whire controller. Please set according the below table:
Digit
Meaning
Range
Default
Adjust (yes/no)
00
Return water temp.
Setting(cooling mode)
8-28
27
℃
yes
01
Return water temp.
Setting(heating mode)
15-40
27
℃
yes
02
Turn round of dehumidifying
under heating mode(frost)
30-90 min
45 min
yes
*03
Defrosting start temperature
0-30
7
℃
yes
04
Terms of exit defrost under
heating model
0-30
13
℃
yes
05
Time of exit defrost under heating
model
1-12MIN
8MIN
yes
*06
System quantity
1-2
1/2
Do not Modify
*07
Automatic restarting
0-1
0
yes
0 (NO) / 1 (YES)
08
Model(cooling only/heat
pump/auxiliary electrical
heating/hot water)
0/1/2/3
0
yes
*09
Water pump model
0/1
0
yes
Note: Above data setting 00 is relevant to cooling mode only. All other data (ie 01-08) is relevant to heating mode.
Remarks:
Parameter 03:
The wire controller displays (0 - 30ºC), but the actual range is (-30 - 0ºC).
The default 7ºC is -7ºC actually.
Parameter 06:
1: the unit has 1 system;
2: the unit has 2 systems;
Parameter 07:
0: the unit can restart automatically;
1: the unit can not restart automatically;