BDP SERIES
Performance loss
Expansive valve blocked
Clean or replace expansive
valve
Environmental temperature
too cold.
Control thermostat contacts
locked in closed position.
Repair or replace the cold
control thermostat.
Excessive superheat.
Too high pressure drop in the
evaporator
Check that the external
equalizer is not obstructed.
J) CHANGE SUMMER OR WINTER MODE OR VICEVERSA
TROUBLE DETECTED
PROBABLE CAUSES
SOLUTIONS
Inverse valve does not act
Solenoid valves don’t act
Check valve and relay
2.2.5. - REGULATION ELEMENTS
High Pressure switch controls condenser performance. A poor performance resulting from
condensation pressures too high, it is usually caused by:
- Dirty condenser.
- Reduced air flow.
Low Pressure switch monitors the pressure at which the refrigerant evaporates in the
evaporator tubes. A low evaporation pressure is usually caused by:
- Lack of refrigerant.
- Thermostatic expansion valve faulty.
- Filter Drier obstructed.
-Compressor discharge system inoperative (Power reduction).
Cold water thermostat regulates the temperature of cold water to the evaporator inlet. The
most common causes of water temperature in this area are:
- Reduced water flow.
- Thermostat regulating at very low temperatures.
The oil pressure switch detects the difference between back pressure pump compressor oil
(semi-hermetic compressors), and the prevailing pressure in the compressor crankcase. This difference
is the net pressure of the oil or the oil pressure chamber. Weak oil effective pressure is usually the
result of:
- Lack of oil.
- Faulty oil pump.
- Reheating defective crankcase, causing condensation of the coolant in the crankcase bottom.
- Thermostatic expansion valve incorrectly set.
Содержание BDP Series
Страница 1: ...HEAT PUMP BDP ...
Страница 23: ...BDP SERIES ANNEX A TECHNICAL FEATURES COOLING CIRCUIT 1 TECHNICAL FEATURES ...
Страница 24: ...2 COOLING CIRCUIT ONE CIRCUIT MODELS ...
Страница 25: ...3 COOLING CIRCUIT DOUBLE CIRCUIT MODELS ...
Страница 26: ...SERIES BDP ANNEX B OPTIONAL HYDRAULIC CIRCUIT 1 HOT COOL WATER COIL ...
Страница 27: ...SERIES BDP For different temperature increases consult technical features sticker 2 CONDENSER ...
Страница 28: ...SERIES BDP ANNEX C MAIN DIMENSIONS ...
Страница 29: ...SERIES BDP ANNEX D ELECTRIC DIAGRAM CONTROL ...
Страница 30: ...SERIES BDP ANNEX E ELECTRIC DIAGRAM POWER ...
Страница 31: ...SERIES BDP ANNEX F TERMINAL DIAGRAM ...
Страница 32: ...SERIES BDP ANNEX G PLUGS ...