BDP SERIES
Please check that goods are according to your order and to the delivery note.
Handling facilities must be according to the size and weight of the machine
2.2.2.
–
DEVICE EMPLACEMENT
Check the placement of the unit, their level and the measures provided for maintenance are
respected.
BEFORE CONNECTING TO ELECTRICAL SUPPLY
HYDRAULIC CIRCUIT
Check no leaks in water pipes, joins, valves, etc.
Check thermometers set-up.
Check for pressure connections or a pressure gauge with isolating valve on the water inlet and
outlet to measure water loss from the evaporator and check that it is in accordance with that shown in
our documentation or our proposition.
Verify the performance of the water pump (rotation direction).
Check that the installation has been carefully cleaned, and the filters are clean.
Check that there is a flow switch in the system water.
Check that the probes of thermostats or safety devices in their positions.
ELECTRIC EQUIPMENT
Check that the voltage at the line beginning corresponds to the power contained in the
construction features sticker, wiring diagrams and other documents of the unit.
Standard Power Required: 380 v. / 3 Ph / 50 Hz + N + T.
Our warranty does not cover damage to our materials for maltreatment, wrong electrical
connections, wrong operation, bad or unsuitable use, etc.
Control wiring: cable section, disconnectors and fuse cuts, according to the installation.
Inspect all electrical installations. They must be clean and properly adjusted. Systematically
adjust and make sure electrical cords are sufficiently tightened.
Make sure that the electrical wiring is in accordance with the wiring diagram supplied with the
unit.
Check security switch (Hp switch, antifreeze thermostat ...) are rearmed. If necessary, reset
boxes in the devices.
OTHERS
FAN
Manually check that the electric motor and the fan turbine rotate freely.
FINNED COIL
Check the general condition of the finned coil.
Check that the fins are not damaged and that no foreign object disturbs the fluid and air flow over
them. If necessary, clean and straighten the fins with the help of a suitable material (fin comb).
Содержание BDP Series
Страница 1: ...HEAT PUMP BDP ...
Страница 23: ...BDP SERIES ANNEX A TECHNICAL FEATURES COOLING CIRCUIT 1 TECHNICAL FEATURES ...
Страница 24: ...2 COOLING CIRCUIT ONE CIRCUIT MODELS ...
Страница 25: ...3 COOLING CIRCUIT DOUBLE CIRCUIT MODELS ...
Страница 26: ...SERIES BDP ANNEX B OPTIONAL HYDRAULIC CIRCUIT 1 HOT COOL WATER COIL ...
Страница 27: ...SERIES BDP For different temperature increases consult technical features sticker 2 CONDENSER ...
Страница 28: ...SERIES BDP ANNEX C MAIN DIMENSIONS ...
Страница 29: ...SERIES BDP ANNEX D ELECTRIC DIAGRAM CONTROL ...
Страница 30: ...SERIES BDP ANNEX E ELECTRIC DIAGRAM POWER ...
Страница 31: ...SERIES BDP ANNEX F TERMINAL DIAGRAM ...
Страница 32: ...SERIES BDP ANNEX G PLUGS ...