6
dP
Decimal point
On – Off
ON
7
HSEt
Differential
0.0 + 30.0
1
8
tone
Activation time output
OUT for probe broken
OFF + 99.59
min.sec
OFF
9
toFE
Deactivation time output
OUT for probe broken
OFF + 99.59
min.sec
OFF
10
Func
Output operation mode:
HEAt = Heat
CooL = Cool
HEAt – CooL Cool
11
od
Delay at power on
OFF + 99.59
min.sec
OFF
12
PASS
Access password to
parameters functions
OFF + 9999
OFF
13
SP
Set Point
SPLL + SPHL 0.0
IV.
ERROR SIGNALS
Parameters
Description
Action
E1 – E1
The probe may be
interrupted or in short
circuit or may measure
a value outside the
range allowed
Check the correct
connection of the probe
with the instrument and
check the probe works
properly
EEPr
Internal memory error
Check and if necessary
re-programme the
parameters function.
9.
GENERAL PRECAUTIONS
The installation, start-up and maintenance should be performed by qualified personnel only.
This equipment should not be exposed to inflammable substances or explosives.
For any maintenance work done on the inside of the machine, proper care and precautions should
be taken to disconnect the main equipment from the power supply.
In maintenance operations the use of protective equipment such as goggles and gloves is required.
During operation of the equipment, it is normal that the condensation produced by the evaporation
unit will produce a certain quantity of water which will have to be evacuated. The machines have
an outlet tube for this reason on the corner of the back cover which should always be free of any
obstruction and connected to drain.