Measurement scale settings
Entry of 100% values in respect of sensors a to d. This might be for example the rated loads of hoist unit
a and b. The values can only be entered as whole numbers. Any of the sensors can be disabled at will.
Note:
Where changes are made to the individual sensors, the LS 804 will automatically switch
over to the Adjustments Mode after the “
OK
” button has been pressed.
Analogue out settings
The analogue outputs can be configured either as voltage or current outputs. The reference value for
signal is the 100% value entered above when selecting signal a to d or, when selecting Sum, the 100%
value of the relevant sum.
CAN settings (X1)
When setting the cyclical value output – “Values out” to ON – outputting of the following values takes
place on the CAN interface together with the configured interval – “Values out interval”.
Output-interval settings are possible from 50…5000 ms.
Two CAN telegrams with different CAN IDs are sent with the float values of sensors a and b or sensors c
and d.
ID send (base):
DLC
B0
B1
B2
B3
B4
B5
B6
B7
8
a_float a_float a_float a_float b_float b_float b_float b_float
ID send (base+1):
DLC
B0
B1
B2
B3
B4
B5
B6
B7
8
c_float c_float c_float c_float d_float d_float d_float d_float
RS485/RS232 settings (X2)
When setting the cyclical value output – “Values out” to ON – outputting takes place of the following
formatted ASCII telegram on the serial interface cyclically with the configured interval – “Values out
interval”.
"a:%s b:%s c:%s d:%s Sab:%s Scd:%s Sabcd:%s\r\n"
In the configured scaling these values are transmitted with decimal places and unit of measurement.
Output-interval settings are possible from 1…240 s (4 Min.).
Security settings
Factory default
Security settings (Login admin)
, when set
Username/Login (not changeable)
admin
Password
admin
Master password
1803
An existing password is deleted by erasing the contents of fields
Password
and
Password
confirmation
and then entering the
Master password
.