background image

 

 

 
  

The AEC 132-0137 (6043)  Amp-Probe may also be used independently of the 6044.  Plug the insulated jacks into a standard digital Multimeter and 
set the meter for DC millivolts (mV); the Amp-Probe reads 1mV = 1 Amp.  If the Amp-probe needs to be used for AC current just set the Multimeter 
to ACV (AC volts). 
 
 
 
  

 6044 TROUBLESHOOTING HINTS:

 

 

 

Was the unit connected with the correct polarity? 

 

The unit needs at least 7.5V from the battery to operate correctly if the voltage drops below this level the display may go blank or have an 
erratic display. 

 

Is the battery in the Amp-probe good? 

 

Is the unit displaying “HOT” it will not run the battery test when the unit is hot, let cool? 

 

The differential leads(external leads) and the amp-probe are zeroed at power up if a voltage or current is present at this time then those 
values are considered zero, and can cause errors in further readings by those devices/items.  The zero value can be checked by installing 
the amp-probe and pressing the zero button and connecting the differential leads and then shorting them together then placing the unit in 
the  display mode.  This is done by pressing Select Test [2] until the starter LED is lit, then pressing Start Test [4] button (starter Led will be 
flashing) and then pressing the up arrow.  At this time the values in the amp and voltage display should be reading very close to zero.  If 
not, leave the amp probe and differential leads as they are and disconnect the unit from the battery and reconnect (resetting power to the 
unit) this should zero the devices.  

  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  

 
 
                                                                         

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

ASSOCIATED EQUIPMENT CORPORATION 

5043 Farlin Avenue  

Saint Louis, Missouri 63115  

(314) 385-5178 

www.associatedequip.com

 

 

 
 
 
W2312  

REV. 02/19/09 027-0837(c) 

Содержание BEST 6044

Страница 1: ... actuated and serves as a reminder to not disconnect leads while load is on AMPS meter reads both and amps for easy diagnosis of leakage current problems Unit monitors the voltage ripple letting you know when alternator output diodes have failed The electronic circuits are protected against reverse voltages caused by connecting leads incorrectly The electronic circuit board has a protective coatin...

Страница 2: ...rking with a lead acid battery A lead acid battery can produce a short circuit current high enough to instantly weld a ring or the like to metal and cause severe burn 5 Spilled acid Neutralize with a solution of baking soda 1 pound per gallon of cold water or household ammonia 1 pint per gallon of cold water VEHICLE SAFETY 1 Keep your body clothing and test leads away from all moving parts of the ...

Страница 3: ...esent open circuit battery voltage If the minimum voltage was below 9 6V then it will also flash Bd The minimum acceptable voltage for a battery at the different temperatures is as follows BATTERY TEMPERATURE COMPENSATION 15 SECOND LOAD TEST C 21 16 10 4 1 7 12 18 F 70 60 50 40 30 20 10 0 MIN VLT 9 6 9 5 9 4 9 3 9 1 8 9 8 7 8 5 If the CCA of the battery is not known check vehicle manufacturer s re...

Страница 4: ...it should be less than 0 2V BATTERY TEMPERATURE COMPENSATION 15 SECOND LOAD TEST C 21 10 2 4 9 15 F 70 50 35 25 15 5 MIN VOLT 4 8 4 7 4 6 4 5 4 4 4 3 Please note that the test described above is not the easiest way to run a test on two batteries in series but it is the most accurate If you were to test the batteries and take only one voltage reading from the positive terminal of Battery 1 to the n...

Страница 5: ...re the lead from the battery terminates 2 3 Start the vehicle press the up arrow this will display the maximum differential external voltage reading during the starter test 4 Repeat the same procedure checking the voltage drop across the solenoid negative lead to starter side of solenoid 2 to 3 5 Repeat again checking the voltage drop between the solenoid and the starter Positive lead at solenoid ...

Страница 6: ...wing steps 1 Make sure the differential voltage leads and the amp probe are not connected The 6044 zero s these two items on power up so any voltage reading on them now will be considered zero 2 Connect the unit to the battery see figure 10 3 Connect install Differential Voltage leads and Amp Probe into there respective jacks Amp probe should not be around any cables at this time this would cause ...

Страница 7: ...wer up if a voltage or current is present at this time then those values are considered zero and can cause errors in further readings by those devices items The zero value can be checked by installing the amp probe and pressing the zero button and connecting the differential leads and then shorting them together then placing the unit in the display mode This is done by pressing Select Test 2 until...

Отзывы: