background image

of 12

DEM680E Series Delayed Egress 

Magnalock

®

 

with EcoMag

 Technology

Installation & Operating Instructions

Product Components

A  Magnalock & Mounting Bracket
B  Strike Housing
C  Strike Plate Assembly
Wall Mounted Key Switch

E  Settings Labels
F  Sex Bolt & Tapered Washer
G  Template Pins 
NFPA Door Label

Installation Hardware Pack Contents

I   #14 X 3" Type A Phillips 

Pan Head Screw (4)

J  Threadlocker Packet
K  WOOD DOORS: #6 X 

1/2" Phillips Flat Head 

Type A Steel Screw (6)

L  METAL DOORS: 6-32 X 

3/8" Phillips Flat Head 

Type F Steel Screw (6)

#12 X 1-1/2" Type A Phillips 

Pan Head Screw (4)

Rivet Nut Install Tool
1/4-20 X 1" Phillips Pan 

Head Screw (2)

P   1/4-20 Rivet Nut (2)
3/16" Hex Key

Diagram 1 

Product Components

A

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

B

Specifications 

Dimensions

• 

Height:  2.50" [64 mm]

• 

Depth:  2.56" [65 mm]

• 

Length:  11.50" [292 mm]

Certifications

• 

UL 10C Fire Rated, 1 Hour

• 

CAN/ULC-S104 Fire Door Conformant

• 

UL 294

• 

UL Tested Ratings: Endurance: 

100,000 cycles

• 

ANSI/BHMA A156.23, Grade 

2; E18501 Compliant

• 

California State Fire Marshal Listed

• 

NFPA 101

Electrical

• 

Magnalock Minimum Current Draw 

(±10%) 

  95 mA at 12 VDC 

  65 mA at 24 VDC

• 

Magnalock Maximum Current Draw 

(±10%) 

  575 mA at 12 VDC 

  315 mA at 24 VDC

Static Holding Force

• 

1,200 lbs [544kg]

Operating Temperature

• 

32˚ to 120˚F [0˚ to 49˚C]

• 

Indoor use only

NOTE:  Hardware is provided for various installations.  

There will be leftover parts depending on the type of installation.

IMPORTANT:  UL 294 compliance requires that the locking device be powered by a UL 

294 (ALVY) or UL 603 (APHV) listed power supply and shall be installed in accordance 

with the following UL and National Standards: NFPA 70 – National Electrical Code.

IMPORTANT 

This Magnalock requires calibration upon installation.

Содержание SECURITRON DEM680E Series

Страница 1: ...ns Dimensions Height 2 50 64 mm Depth 2 56 65 mm Length 11 50 292 mm Certifications UL 10C Fire Rated 1 Hour CAN ULC S104 Fire Door Conformant UL 294 UL Tested Ratings Endurance 100 000 cycles ANSI BH...

Страница 2: ...shown in Diagram 3a and the 3 screws that secure the mounting bracket to the top of the lock chassis as shown in Diagram 3b 2 SET the cover and screws aside to re attach later 3 SLIDE the bracket to...

Страница 3: ...with template pins against the closed door using a Phillips screwdriver and two 2 1 4 20 x 1 Phillips pan head screws see Diagram 10 InstallingtheMagnalock onaWOOD DOORframe 1 DRILL two 2 3 16 diamet...

Страница 4: ...tside of the door see Diagram 13 8 ATTACH the strike plate housing using six 6 6 32 x 3 8 Phillips flat head screws for METAL OR six 6 6 x 1 2 Phillips flat head screws for WOOD door 9 CRITICAL STEP P...

Страница 5: ...bracket at each end and remove the Magnalock from the bracket see Diagram 17 4 ENSURE that the mounting bracket aligns with the marks and TIGHTEN the mounting screws see Diagram 18 5 USING THE BRACKET...

Страница 6: ...nalock functions using Table 2 and the desired delay egress functions using Table 3 MAGNALOCK ELECTRICAL INSTALLATION Diagram 24 Location of J1 and J4 terminals Diagram 25 Terminal pin out diagram Dia...

Страница 7: ...ks 30 seconds after an irrevocable alarm cycle Disabled SW 8 ON Enabled Unlocked at Startup SW 9 OFF Disabled When enabled system starts in the unlocked state Disabled SW 9 ON Enabled No Irrevocable A...

Страница 8: ...agram 31 LED location Diagram 32 System settings Diagram 33 Settings labels Behavior ofDelayed EgressMagnalockswith regionalsettings California Uponpowerup lockgoes into analarmstate andrequiresamanua...

Страница 9: ...V battery for installations in facilities that do not yet have commercially available power NOTE3 AccesscontrolsystemsmayregisterDPSand or BONDerrorconditionsduringthecalibrationsequence TECHTIP Fori...

Страница 10: ...le and attempt to pushthedooropen Thenuisance alarmshould sound see Diagram 38 Closethedoorbefore thenuisanceinterval expires to preventthealarmstate If the nuisance alarm does not sound the strike as...

Страница 11: ...ngle bond sensor failure Magnet disconnected or magnet cable wire broken Verify that the strike label has been removed Recalibrate Check for obstructions between strike and magnet Clean face of strike...

Страница 12: ...E Each DEM680E comes with an NFPA exit delay door label as required by fire code 1 FOLLOW the included application instructions to apply the lettering to a door Restoring factory defaultsettings 1 DIS...

Отзывы: