Test 1 – Verifying 

correct startup 

The DEM680E should be calibrated with 

a non-zero nuisance delay setting. 

With the door closed

, the LED should be GREEN, 

indicating that it is active (see 

Diagram 36

). 

•  If the LED is RED or AMBER, stop and consult 

the 

Troubleshooting Guide

 to correct.

Test 2 – Verifying 

door security

With the door closed

, PUSH against the face of 

the door WITHOUT releasing the primary locking 

mechanism (e.g., an exit device or cylindrical/mortise 

door lock). The nuisance alarm should not sound if 

the door is adjusted properly (see 

Diagram 37

).

• If the nuisance alarm sounds

, there is too much door 

movement. The primary locking mechanism must be 

adjusted to reduce excessive door travel. Excessive 

movement will cause the DEM680E to go into alarm 

and unlock when the door is pulled from the unsecure 

side. Make necessary corrections and repeat Test 2.  

Test 3 – Verify nuisance 

alarm function 

UNLOCK the primary locking mechanism (push bar or turn 

handle) and attempt to push the door open. The nuisance 

alarm should sound (see 

Diagram 38

). Close the door before 

the nuisance interval expires to prevent the alarm state.

• If the nuisance alarm does not sound

, the strike 

assembly screw may have been overtightened. 

Overtightening prevents the door from traveling past 

the nuisance threshold. Refer to “No Alarm” in the 

Troubleshooting Guide

 and 

Diagram 14

 which shows 

proper adjustment of the strike assembly screw. 

Test 4 – Verify countdown 

alarm & free egress 

UNLOCK the primary locking mechanism and attempt to 

open the door. The nuisance alarm should sound along 

with a flashing strobe. Maintain pressure on the door 

until the alarm becomes steady; the DEM680E is now in 

alarm state. The door should open in 15 or 30 seconds, 

depending on the exit and nuisance delay settings. At 

the end of the alarm interval, the LED should turn red, 

and the door should freely open. (see 

Diagram 39

).

*After testing, close the door and perform a reset. After 

reset, the strobe should turn off and the LED should change 

from red to green. VERIFICATION IS COMPLETE.

MAGNALOCK OPERATIONAL TESTS

Diagram 36  Indicator light displays

Diagram 37  

Diagram 39 

Diagram 38

Содержание SECURITRON DEM680E Series

Страница 1: ...ns Dimensions Height 2 50 64 mm Depth 2 56 65 mm Length 11 50 292 mm Certifications UL 10C Fire Rated 1 Hour CAN ULC S104 Fire Door Conformant UL 294 UL Tested Ratings Endurance 100 000 cycles ANSI BH...

Страница 2: ...shown in Diagram 3a and the 3 screws that secure the mounting bracket to the top of the lock chassis as shown in Diagram 3b 2 SET the cover and screws aside to re attach later 3 SLIDE the bracket to...

Страница 3: ...with template pins against the closed door using a Phillips screwdriver and two 2 1 4 20 x 1 Phillips pan head screws see Diagram 10 InstallingtheMagnalock onaWOOD DOORframe 1 DRILL two 2 3 16 diamet...

Страница 4: ...tside of the door see Diagram 13 8 ATTACH the strike plate housing using six 6 6 32 x 3 8 Phillips flat head screws for METAL OR six 6 6 x 1 2 Phillips flat head screws for WOOD door 9 CRITICAL STEP P...

Страница 5: ...bracket at each end and remove the Magnalock from the bracket see Diagram 17 4 ENSURE that the mounting bracket aligns with the marks and TIGHTEN the mounting screws see Diagram 18 5 USING THE BRACKET...

Страница 6: ...nalock functions using Table 2 and the desired delay egress functions using Table 3 MAGNALOCK ELECTRICAL INSTALLATION Diagram 24 Location of J1 and J4 terminals Diagram 25 Terminal pin out diagram Dia...

Страница 7: ...ks 30 seconds after an irrevocable alarm cycle Disabled SW 8 ON Enabled Unlocked at Startup SW 9 OFF Disabled When enabled system starts in the unlocked state Disabled SW 9 ON Enabled No Irrevocable A...

Страница 8: ...agram 31 LED location Diagram 32 System settings Diagram 33 Settings labels Behavior ofDelayed EgressMagnalockswith regionalsettings California Uponpowerup lockgoes into analarmstate andrequiresamanua...

Страница 9: ...V battery for installations in facilities that do not yet have commercially available power NOTE3 AccesscontrolsystemsmayregisterDPSand or BONDerrorconditionsduringthecalibrationsequence TECHTIP Fori...

Страница 10: ...le and attempt to pushthedooropen Thenuisance alarmshould sound see Diagram 38 Closethedoorbefore thenuisanceinterval expires to preventthealarmstate If the nuisance alarm does not sound the strike as...

Страница 11: ...ngle bond sensor failure Magnet disconnected or magnet cable wire broken Verify that the strike label has been removed Recalibrate Check for obstructions between strike and magnet Clean face of strike...

Страница 12: ...E Each DEM680E comes with an NFPA exit delay door label as required by fire code 1 FOLLOW the included application instructions to apply the lettering to a door Restoring factory defaultsettings 1 DIS...

Отзывы: