11 

of 12

Troubleshooting Guide

TROUBLE INDICATOR

POSSIBLE CAUSES

POSSIBLE SOLUTIONS

Solid RED

•  Two bond sensor failures*
•  Supply voltage < 8.5 VDC
•  Two bond sensor failures* 

•  Ensure bond sensor connectors are properly seated 
•  Check power supply voltage
•  Ensure bond connectors are properly seated

Solid RED with 

Audible Alarm

•  Open door
•  DPS failure*
•  Attempting to calibrate with two bond sensor failures*
•  Strike tray installed upside down
•  DPS magnet missing from strike tray

•  Close door
•  Ensure DPS connector is properly seated
•  Ensure bond connectors are properly seated
•  Ensure that the strike tray is mounted 

with alignment tabs facing up

•  Check strike tray for damage, replace if needed

Solid AMBER

•  Door sag 
•  Obstructed strike/magnet face
•  Supply voltage < 10.8 VDC
•  Single bond sensor failure*
•  Magnet disconnected or magnet cable wire broken
•  Verify that the strike label has been removed

•  Recalibrate
•  Check for obstructions between strike and magnet
•  Clean face of strike and magnet. Recalibrate
•  Check power supply voltage
•  Ensure bond connectors are properly seated
•  Make sure magnet connector is properly 

seated or repair magnet cable wire

Flashing RED

•  Factory reset

•  Ensure SW10 is in the OFF position

LED off

•  LED disabled by SW1
•  Supply voltage < 5 VDC

•  Turn SW1 to the ON position
•  Check power supply

Intermittent alarm

•  Over-tightened strike screw

•  Unscrew strike screw 1/2 turn at a time 

until alarm sound is constant when door 

is pushed (Recalibrate lock after each 

adjustment and repeat 

Install Verification

)

No alarm

*  Failure means that the circut cannot detect a signal from the sensor. Check that the sensor connectors are properly 

seated and inspect sensor wires for damage. Call Technical Support if replacement is needed.

Содержание SECURITRON DEM680E Series

Страница 1: ...ns Dimensions Height 2 50 64 mm Depth 2 56 65 mm Length 11 50 292 mm Certifications UL 10C Fire Rated 1 Hour CAN ULC S104 Fire Door Conformant UL 294 UL Tested Ratings Endurance 100 000 cycles ANSI BH...

Страница 2: ...shown in Diagram 3a and the 3 screws that secure the mounting bracket to the top of the lock chassis as shown in Diagram 3b 2 SET the cover and screws aside to re attach later 3 SLIDE the bracket to...

Страница 3: ...with template pins against the closed door using a Phillips screwdriver and two 2 1 4 20 x 1 Phillips pan head screws see Diagram 10 InstallingtheMagnalock onaWOOD DOORframe 1 DRILL two 2 3 16 diamet...

Страница 4: ...tside of the door see Diagram 13 8 ATTACH the strike plate housing using six 6 6 32 x 3 8 Phillips flat head screws for METAL OR six 6 6 x 1 2 Phillips flat head screws for WOOD door 9 CRITICAL STEP P...

Страница 5: ...bracket at each end and remove the Magnalock from the bracket see Diagram 17 4 ENSURE that the mounting bracket aligns with the marks and TIGHTEN the mounting screws see Diagram 18 5 USING THE BRACKET...

Страница 6: ...nalock functions using Table 2 and the desired delay egress functions using Table 3 MAGNALOCK ELECTRICAL INSTALLATION Diagram 24 Location of J1 and J4 terminals Diagram 25 Terminal pin out diagram Dia...

Страница 7: ...ks 30 seconds after an irrevocable alarm cycle Disabled SW 8 ON Enabled Unlocked at Startup SW 9 OFF Disabled When enabled system starts in the unlocked state Disabled SW 9 ON Enabled No Irrevocable A...

Страница 8: ...agram 31 LED location Diagram 32 System settings Diagram 33 Settings labels Behavior ofDelayed EgressMagnalockswith regionalsettings California Uponpowerup lockgoes into analarmstate andrequiresamanua...

Страница 9: ...V battery for installations in facilities that do not yet have commercially available power NOTE3 AccesscontrolsystemsmayregisterDPSand or BONDerrorconditionsduringthecalibrationsequence TECHTIP Fori...

Страница 10: ...le and attempt to pushthedooropen Thenuisance alarmshould sound see Diagram 38 Closethedoorbefore thenuisanceinterval expires to preventthealarmstate If the nuisance alarm does not sound the strike as...

Страница 11: ...ngle bond sensor failure Magnet disconnected or magnet cable wire broken Verify that the strike label has been removed Recalibrate Check for obstructions between strike and magnet Clean face of strike...

Страница 12: ...E Each DEM680E comes with an NFPA exit delay door label as required by fire code 1 FOLLOW the included application instructions to apply the lettering to a door Restoring factory defaultsettings 1 DIS...

Отзывы: