6
of 12
Pulling the wiring
NOTE: End-user and installer must comply
with fire and building codes.
1
PULL wires/cables through the wire feed-
through hole(s) drilled in the frame.
2
INSTALL the provided wall-
mounted switch if necessary.
Connecting the
final wiring
1
CONNECT the wires using
Diagrams 24
through 28
as guides and as applicable.
NOTE:
The positive terminal (+) and reference
voltage (VREF) are internally bussed to provide
a reference voltage for external control.
2
LOCATE the jumpers as shown in
Diagram 29
.
3
SET the jumpers for the desired
function using
Table 1
.
4
LOCATE the DIP-switches as
indicated in
Diagram 30
.
5
Select the desired Magnalock functions
using
Table 2
and the desired delay-
egress functions using
Table 3
.
MAGNALOCK ELECTRICAL INSTALLATION
Diagram 24 Location of J1 and J4 terminals
Diagram 25 Terminal pin-out diagram
Diagram 26 Typical system wiring
Diagram 27 Typical system wiring
with external initiate device
Diagram 28 Typical system
wiring with external controls
Terminal Block
Header J4
Terminal Block
Header J1
Door Status
Bond Status
Input
Voltage
External
Controls
External
Alarm
H3
Power
Supply
Wall Mounted
Key Switch
DEM680E
Terminal Block
Header J1
Dry Alarm
Contacts
Power
Supply
External
Initiate
Device
(optional)
Wall Mounted
Key Switch
DEM680E
Terminal Block
Header J1
Dry Alarm
Contacts
Power
Supply
DEM680E
Terminal Block
Header J1
“(+) and ”VREF” Terminals are internally bussed to provide
reference (+) voltage external control use.
Dry Alarm
Contacts