Delayed Egress
status LEDs
The two LEDs shown display the
following Delayed Egress states.
RED
GREEN
STATE
OFF
OFF
Unlocked
OFF
ON
Bypass
ON
OFF
Egress Alarm
ON
ON
Locked
Documenting the
configuration settings
1
Indicate the settings on the adhesive-backed labels
included with the Magnalock (see
Diagram 32
).
2
Complete the labels and affix them to the inside
of the Magnalock cover (see
Diagram 33
).
Diagram 31 LED location
Diagram 32 System settings
Diagram 33 Settings labels
Behavior of Delayed
Egress Magnalocks with
regional settings
California
Upon power up, lock goes into an alarm state
and requires a manual reset. Nuisance delay
is settable to 0, 1, 2 or 3 seconds and the exit
delay is fixed at 15 or 30 seconds. Bypass delay
is settable to 0, 15, 30 or 45 seconds. A manual
reset is required after a delayed egress event.
Chicago
Upon power up, lock goes into an alarm state and
requires a manual reset. Nuisance delay is fixed at
1 second, the exit delay is fixed at 15 seconds, and
the bypass delay is fixed at 0 seconds. A manual
reset is required after a delayed egress event.