background image

 

 

 

PN# 500-22125

 

 

Page 7 

Rev. D, 08/11 

Troubleshooting (Solar Controller) 

Problem 

Battery is not charging… 

Solution  

a.

 

Check the green LED indicator.  The green “CHARGING” LED should be on if it is 
daytime. 

b.

 

Check that the proper battery type (sealed or flooded) has been selected. 

c.

 

Check that all wire connections in the system are correct and tight.  Check the 
polarity (+ and –) of the connections. 

d.

 

Measure the PV array open-circuit voltage and confirm it is within normal limits.  
If the voltage is low or zero, check the connections at the PV array itself.  

Disconnect the PV from the controller when working on the PV array. 

e.

 

Check that the load is not drawing more energy than the PV array can provide. 

f.

 

Check if there are excessive voltage drops between the controller and the 
battery.  This will cause undercharging of the battery. 

g.

 

Check the condition of the battery.  Determine if the battery voltage declines at 

night with no load.  If unable to maintain its voltage, the battery may be failing. 

h.

 

Measure the PV voltage and the battery voltage at the controller terminals.  If 

the voltage at the terminals is the same (within a few tenths of volts) the PV 
array is charging the battery.  If PV voltage is close to the open circuit voltage 

of the panels and the battery voltage is low, the controller is not charging the 
batteries and may be damaged. 

 

Problem 

Battery Voltage is too high…  

Solution  

a.

 

First check the operating conditions to confirm that the voltage is higher than 
specifications.  Consider the temperature compensation of the controller’s PWM 
set-point.  For example, 15 at 0°C the controller will regulate at about 15.1 

volts (for 12 volt flooded batteries). 

b.

 

Check that the proper battery type (sealed or flooded) has been selected. 

c.

 

Check that all wire connections in the system are correct and tight. 

d.

 

Disconnect the PV array and momentarily disconnect the lead from the 

“BATTERY” positive terminal.  Reconnect the battery terminal and leave the PV 
array disconnected.  The green charging LED should not be lit.  Measure the 

voltage at the “SOLAR” terminals (with the array still disconnected).  If the 
green  charging  light  is  on  or  battery  voltage  is  measured  at  the  “SOLAR” 
terminals, the controller may be damaged. 

 

Problem 

Load not operating properly… 

Solution  

a.

 

Check that the load is turned on.  Check that no system fuses are defective.  
Check that no system circuit breakers are tripped.  Remember that there are no 

fuses or circuit breakers inside the controller. 

b.

 

Check connections to the load, and other controller and battery connections.  

Make sure voltage drops in the system wires are not too high. 

c.

 

Check for proper LED indications on the controller.  If the red “LOAD 
DISCONNECT” LED is on, the load has been disconnected due to low battery 

voltage.  This is generally a normal state when the load exceeds the PV array 
output due to weather and other sunlight conditions. 

d.

 

Measure the voltage at the controller “BATTERY” terminals.  If this voltage is 
above the LVD, the load should have power.  Then measure the voltage at the 

controller “LOAD” terminals, and if there is no voltage present, the controller 
may be defective. 

 

IF PROBLEMS PERSIST CALL SECURITRON TOLL FREE 

(800) MAG-LOCK 

(800) 624-5625

 

Содержание SECURITRON BPSS-10

Страница 1: ...0 BPSS 20 Power Supply Specifications Use Environment Outdoor NEMA 3R Cabinet Weight without batteries 14 Lbs 6 4 kg Cabinet Dimensions Length 12 8 325mm Height 12 2 310mm Depth 4 7 119mm Voltage 11 5 14 1 Volts DC Maximum Output Current Continuous Up to 125mA Maximum Output Current While Operating Lock Up to 425mA Operating Temperature Range with batteries 4 to 113 F 20 to 45 C Number of daily lo...

Страница 2: ...eing used 4 2 2 Controller Safety SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the controller WARNING Be very careful when working with batteries Lead acid batteries can generate explosive gases and short circuits can draw thousands of amps from the battery Read and follow all instructions provided with the batte...

Страница 3: ...sconnect LVD feature along with a red LED indicator Whenever the battery charge state falls below the LVD set point the load will be disconnected and the red LED will light This indicates that the controller has disconnected the load to protect the battery from further discharge and possible damage After some period of recharging the battery such that it recovers to approximately 40 to 50 percent ...

Страница 4: ... 3 1 Insert the square nuts into the cutouts at each side of the panel and slide in slot to initial position 2 Assemble swivel brackets with the included hardware to the nuts 3 Tighten screws securely when brackets are adjusted to the desired position Figure 3 PV ARRAY PANEL 6X 10 32 X 7 16 LONG PPH SCREW 2X 10 SPLIT LOCK WASHER 6X 10 PLAIN FLAT WASHER REFERENCE POLE NOT INCLUDED 2X 10 32 SQUARE N...

Страница 5: ...nel should be aligned 7 8 degrees east of magnetic South on a compass 5 2 2 TILT ANGLE The panel can be adjusted to the desired tilt angle using the swivel bracket at each side of the panel Simply loosen the pivot and the adjustment screw at each bracket The brackets are marked at 15 increments from 0 horizontal to 90 vertical Align the indicator on the bracket to the desired angle and then tighte...

Страница 6: ...to a fence post or pole up to 3 76mm O D This kit is available through Securitron or their authorized distributors 7 MAINTENANCE 7 1 Cleaning Methods Use canned compressed air to blow out dirt and dust from inside the cabinet Cleaning once a year is recommended Clean every six months in very dusty environments Cleaning more often may be required in outdoor applications ...

Страница 7: ...he temperature compensation of the controller s PWM set point For example 15 at 0 C the controller will regulate at about 15 1 volts for 12 volt flooded batteries b Check that the proper battery type sealed or flooded has been selected c Check that all wire connections in the system are correct and tight d Disconnect the PV array and momentarily disconnect the lead from the BATTERY positive termin...

Отзывы: