3

  

Rev. E, 05/08 

5.2.1

Mounting the Strike Plate 

The strike plate should be mounted prior to the magnet in out-swinging door applications. 

Figure 3

 below illustrates a typical strike mounting configuration.  

Figure 3 

Select a mounting location for the Magnalock and strike assembly as mentioned in 

Section 5.1

.

The following general guideline should be used for consideration during the installation review:  

x

Read and follow the template instructions which include drilling and mounting instructions.

x

Installing a strike plate horizontally, the top edge of the strike will be approximately 1/8" 
[3.2mm] below the door frame stop. If the strike and magnet are to be mounted 
vertically, increase this clearance between the strike and frame to 3/16" [4.8mm]. 

x

An approximated 1” [25.4mm] clearance should be considered between the Magnalock 
and the edge corner of the door frame. This will allow proper access for the mounting 
locations for drilling and tool access. 

x

Use the template provided for positioning and marking the mounting locations of the 
Magnalock and strike. Check the external and internal areas of the marked door and 
frame for any obstacles such as wire chases or internal structural features. Make 
necessary adjustments to avoid these obstacles. 

x

Offset strikes are available for lowering a strike alignment 1/4” [6.0mm] allowing 
clearance when door construction contains obstructions in the mounting locations. 

5.2.2

Mounting the Magnet 

Installations with blade stops require an Aluminum Spacer Bracket (ASB) for clearance without 
having to cut the stop as shown in

 Figure 4

. Information on mounting brackets is located in 

Section 6

 of this manual.  

To properly install the Magnalock, the following conditions should be verified: 

x

The entire Magnalock mounting area for the magnet must be a flat surface. 

x

The frame area selected must be structurally strong enough for support. 

x

The magnet face must be mounted parallel to the door face when closed. 

x

The installed strike must still allow the door to close properly by clearance and alignment. 

x

The Magnalock face and strike plate must be aligned so that they are centered. 

ALIGNMENT IS IMPORTANT FOR “B” & “D” MAGNALOCKS (Section 5.2.4) 

ALIGNMENT IS CRITICAL FOR THE MAGNALOCK HOLDING FORCE (Section 2) 

x

Mark and drill all holes for the mounting screws as instructed on the template. 

x

Make wire connections, apply power and test for proper operation. 

x

Mount the Magnalock using the hardware and thread locking compound provided.  

x

Tighten the screws until secure.

DO NOT OVER-TIGHTEN SCREWS

NEVER DRILL MAGNALOCK MOUNTING HOLES 

– DAMAGE MAY OCCUR – 

Strike Plate 

2-3 Washers 

2X Roll Pins 

Strike Mounting 

Screw

Strike Bushing 

2X Roll Pin Bushings 

Door Frame & Stop 

Sex Bolt 

Содержание M32

Страница 1: ...Door Position Sensor is activated by a special magnetic strike armature assembly The isolated SPDT reed switch with an internal resettable protection device is designed for interface to access control and or alarm system for door status Section 5 2 4 2 SPECIFICATIONS MODEL M32 M62 M82B Holding Force 600 Lbs 272 kg 1200 Lbs 544 kg 1800 Lbs 816 kg Dimensions Length 8 203mm 8 203mm 12 305mm Height 1 ...

Страница 2: ...ng the survey x Accessibility should be considered for prevention of any potential safety hazard Additional brackets may be needed for proper installation Specialized brackets are available through Securitron and their many product distributors Section 6 5 2 Out Swinging Door The installation shown below in Figure 2 illustrates the door swinging away from the Magnalock This is a common configurati...

Страница 3: ...cles x Offset strikes are available for lowering a strike alignment 1 4 6 0mm allowing clearance when door construction contains obstructions in the mounting locations 5 2 2 Mounting the Magnet Installations with blade stops require an Aluminum Spacer Bracket ASB for clearance without having to cut the stop as shown in Figure 4 Information on mounting brackets is located in Section 6 of this manua...

Страница 4: ... 5 for the installation of the blind nuts x Drill 3 8 9 5mm diameter mounting holes into the marked locations of the frame x Insert the assembled Blind Nut and Installation Tool into a mounting hole x Use 1 2 13mm box end wrench for holding the Install Nut x Use a 3 16 5 0mm Hex Wrench with the Socket Cap Screw to collapse the Blind Nut x Remove the collapsing tool when finished x Check that the b...

Страница 5: ...enter Model X Y M32B D 9 32 1 8 M62B D 5 16 1 8 M82B D 9 16 1 8 Table A X Y 0 0 Figure 6 5 2 5 In swinging Door Installation Figure 7 below illustrates a typical in swinging door mounting configuration This installation requires the use of a face mount style Magnalock i e M32F M62F or M82FB and a Z bracket Z 32 Z 62 or Z 82 or an adjustable ZA bracket ZA 32 62 or ZA 82 for offsetting the mounting ...

Страница 6: ...ered between the doors x The mounting diagram measurement and marking placement are critical x The mounting diagram is NOT a scaled template x Refer to the Magnalock out swinging door mounting procedures in Section 5 2 x Refer to the strike mounting procedures in Section 5 2 1 x Refer to the blind nut instructions in Section 5 2 3 5 2 7 Mounting Magnalocks for Gates The G Series Magnalock is suita...

Страница 7: ...ted with reverse polarity it will not operate The M32 M62 and M82B Magnalocks are auto sensing dual voltage locks The Magnalock circuit design will automatically select the proper operational conditions for the applied voltage See Section 2 for more information 5 3 3 Poor Release Characteristics The Magnalock is designed with quick release circuitry Wiring errors may cause a Magnalocks to release ...

Страница 8: ... 08 5 3 5 Electrical Wiring The following diagrams Figures 12 13 14 and 15 represent the proper electrical wiring connections required for Magnalock Standard BondSTAT B DPS D and BD versions Figure 12 Figure 13 Figure 14 Figure 15 ...

Страница 9: ...t is the user s responsibility to correctly hookup the Magnalock according to the instructions It is recommended to use a switch or relay to perform break of power Securitron power supplies have terminals for the interconnection of such emergency release switches THE END USER INSTALLER ARE LIABLE FOR FIRE BUILDING CODES COMPLIANCE 6 SPECIALIZED MOUNTING BRACKETS x ASB Aluminum Shim Bracket The ASB...

Страница 10: ...ilable in four 4 architectural finishes x Double Dress Covers The covers are designed to fit over a double door dual lock installation Available in two 2 architectural finishes 8 2 Installation Tool Kit Securitron offers an installation tool kit which includes special drill bits a heavy duty drill guide a blind nut collapsing tool extra fasteners and hardware Metric is also available 8 3 Tamper Pr...

Страница 11: ...nalock Table A Section 5 2 4 Solution Check the Magnalock and strike for obstructions and that contact surfaces are properly cleaned Section 8 Problem DPS Does Not Report Door Status Points of Reference Check strike mounting for proper alignment Table A Section 5 2 4 Check for proper door closure Section 8 1 Check for proper voltage current on switch Section 2 Solution Check resettable protection ...

Страница 12: ...uge x Follow Example A 12VDC system and Example B 24VDC system below x Use Tables 1 and Table 2 to choose the correct wire gauge for the application 1 2 1 Example A 12VDC system Devices Used Amps 12VDC Progressive Totals M62 Magnalock 0 250 0 250 DK 26 Access 0 160 0 410 XMS Motion 0 050 0 460 EEB2 Timer 0 025 0 485 Total Current Rounded Up Table 1 0 600A Using Table 1 12VDC Find Current Draw 600 ...

Страница 13: ...14 Gauge 14 Gauge 12 Gauge 10 Gauge 800A 22 Gauge 22 Gauge 20 Gauge 18 Gauge 18 Gauge 16 Gauge 14 Gauge 14 Gauge 12 Gauge 600A 24 Gauge 22 Gauge 22 Gauge 20 Gauge 18 Gauge 18 Gauge 16 Gauge 14 Gauge 14 Gauge 400A 24 Gauge 22 Gauge 22 Gauge 22 Gauge 20 Gauge 18 Gauge 18 Gauge 16 Gauge 14 Gauge 300A 24 Gauge 24 Gauge 22 Gauge 22 Gauge 22 Gauge 20 Gauge 20 Gauge 18 Gauge 16 Gauge C U R R E N T 200A 2...

Страница 14: ...ion may be the identical item or a newer unit which serves as a functional replacement In the event that the product type has become obsolete in SECURITRON s product line this MAGNACARE warranty will not apply This MAGNACARE warranty also does not apply to custom built to order or non catalog items items made by others such as batteries returns for payment distributor stock reductions returns seek...

Страница 15: ...PN 500 10420 Page 15 Rev E 05 08 ...

Страница 16: ...s the Integrity of the Lock Mounting Hardware Brackets and Tools Aerospace Collapsing Blind Nuts 1000 lbs tensile strength per blind nut Grade One Machine Screws 1 4 20 Allows use of Thread Locker adhesive Complete Line of Mounting Hardware for Doors Frames Herculite glass aluminum metal clad and wood Optional Installation Kit A real Tools of the Trade kit that reduces installation error and speed...

Отзывы: