Rev. E, 05/08
Appendix B
Wire Gauge Factoring
1.1
Remote Power Supply
x
The Magnalock requires adequate voltage and current for proper operation.
x
Resistance is created by the length and gauge (size) of the wire being used.
x
An accurate estimated distance from the power supply to the opening is crucial.
x
For superior operation the correct size gauge wire must be used.
x
The devices used operate the best with the least amount of resistance on the source.
x
Using the correct gauge wires protects against large voltage and current (load) losses.
x
The gauge is determined by the wire distance, voltage and current of all devices.
1.2
Determining Wire Gauge
x
Follow
Example A
(12VDC system)
and
Example B
(24VDC system)
below.
x
Use
Tables 1
and
Table 2
to choose the correct wire gauge for the application.
1.2.1 Example A:
(12VDC system)
Devices Used
Amps (12VDC)
Progressive Totals
M62 Magnalock
0.250
0.250
DK-26 Access
0.160
0.410
XMS Motion
0.050
0.460
EEB2 Timer
0.025
0.485
Total Current Rounded Up (Table 1)
0.600A
Using
Table 1
(12VDC)
Find:
- Current Draw
.600 Amps
- Wire Distance
200 Feet (One-Way)
Solution:
18 Gauge
is indicated for proper installation
1.2.2 Example B:
(24VDC system)
Using
Table 2
(24VDC)
Find:
- Current Draw
.400 Amps
- Wire Distance 1000 Feet (One-Way)
Solution:
14 Gauge
is indicated for proper installation
Devices Used
24VDC Amps
Progressive Totals
M82 Magnalock
0.200
0.200
TSB Touch Bar
0.025
0.225
DK-11 Access
0.070
0.295
XDT-24 Delay
0.050
0.345
MK Bypass/Reset
0.020
0.365
Total Current Rounded Up (Table 2)
0.400A