SE LP10 ML20600 Mortise Lock
27
Note:
Once electrical wiring has been successfully completed
according to proper application, perform the following:
a. Turn power ON.
b. Verify LED located on reader is ON (Red or Green)
depending on reader configuration
c. Present valid credential and verify LED and
sounder activity.
d. Verify valid card read at EAC Panel.
e. Verify system operation functions; i.e., when valid credential
is presented to reader the door unlocks.
Electrical Operation Check
8) Operational Check (Continued)
If the lock fails to operate when DC voltage is applied:
A. Remove power.
B. Confirm the polarity of the supply (i.e., ‘
+
’ is positive).
If the lock is functioning opposite to the desired fail-safe or fail-secure operation:
A. Remove power and check the “Fail” condition by attempting to rotate the outside lever
(e.g. if fail-secure, the outside lever should be rigid with power removed).
B. If the function is incorrect, remove the lock and repeat
section 6, step 3
(DIP Switch configuration).
NOTE: Ensure LED operates as configured*:
• LED remains green when panel asserts GREEN_LED signal
*For configurations with GREEN LED override enabled; see Application Diagram #2 in Section 6.