KEYPAD INITIATION 

Keypad initiation must be done at the initial turn-on of the keypad. 
1.  Connect power to the keypad. 
2.  Put the keypad in 

Program Mode

 by entering “

0 0 0 0 

”. The keypad will 

beep twice and the yellow LED will be on and not blinking. 

3. Enter “

8 9 0 1 #

”. 

4.  The keypad will beep twice and the keypad initiation is complete. 
5. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

It is strongly recommended that the 

Installer Code 

be changed from the default  

0 0 0 0

”. If the 

Installer Code 

is not known, please refer to the section on 

Direct 

Access to Programming

1.  Put the keypad in 

Program Mode

 by entering “

0 0 0 0 

” or the current 

installer code. The keypad will beep twice and the yellow LED will be on and 
not blinking. 

2. Enter “

0 (4 to 8 digit new installer code) #

”. For example, to change the 

Installer Code 

to 1 2 3 4 you would enter “

0 1 2 3 4 #

”.  

3.  The keypad will beep twice indicating that the new 

Installer Code 

has been 

accepted. 

4. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

It is necessary to put the keypad in 

Programming Mode 

in order to access all 

keypad configuration settings. 
1.  Put the keypad in 

Program Mode

 by entering the 

Installer Code 

followed by 

the “

”. The keypad will beep twice and the yellow LED will be on and not 

blinking. 

2. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

User Codes

 are 4 to 8 digits long and must not be the same as the 

Installer Code

User Code 

can be assigned to operate either Output 1 or Output 2. The 

keypad can store up to 100 

User Codes 

for Output 1 and up to 10 

User Codes

 

for Output 2. 
Each 

User Code 

has a 

Code Number

. Output 1 

Code Numbers 

are two digits 

ranging from “

00

” to “

99

”. Output 2 

Code Numbers 

are one digit ranging from “

0

” 

to “

9

”. 

1.  Put the keypad in 

Program Mode

 by entering the 

Installer Code 

followed by 

the “

”. The keypad will beep twice and the yellow LED will be on and not 

blinking. 

2. Enter “(

Output)

  

(Code Number) (User Code) #

”.  

For example, if you wish to assign a 

User Code 

of “6 7 8 9” to 

Code Number

 

“00” to operate Output 1 you would enter “

1 0 0 6 7 8 9 #

”. 

If you wish to assign a 

User Code 

of “3 4 3 3” to 

Code Number 

“1” to operate 

Output 2 you would enter “

2 1 3 4 3 3 #

”. 

3. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

ENTERING A NEW INSTALLER CODE 

PROGRAMMING MODE 

PROGRAMMING USER CODES 

Содержание Alarm Controls KP-300

Страница 1: ...00 645 5538 www alarmcontrols com Model KP 400 is a self contained vandal resistant digital keypad This dual relay output keypad is suitable for residential industrial and commercial installations It...

Страница 2: ...ed tool 2 Pass the wire harness through the opening in the back box 3 Mount the back box to the door frame or wall 4 Make all required wiring connections to the terminal blocks 5 Place the keypad face...

Страница 3: ...put that switches to ground after the duress code has been entered Output rating Ic max 100mA sink Vc max 24VDC Door Position Sensor Input DOOR SENS A normally closed contact connected to this termina...

Страница 4: ...Programming Mode in order to access all keypad configuration settings 1 Put the keypad in Program Mode by entering the Installer Code followed by the The keypad will beep twice and the yellow LED wil...

Страница 5: ...tering the Installer Code followed by the The keypad will beep twice and the yellow LED will be on and not blinking 2 Enter 7 2 5 3 Enter to exit Program Mode The yellow LED will begin blinking To dis...

Страница 6: ...s 1 and 2 can be programmed for either momentary or latching operation Momentary operation time can be set for between 1 and 999 seconds The factory default momentary operation time is 2 seconds 1 Put...

Страница 7: ...ep twice and the yellow LED will be on and not blinking 2 Enter 8 2 1 3 Enter to exit Program Mode The yellow LED will begin blinking To return the keypad to Manual Entry Mode 1 Put the keypad in Prog...

Страница 8: ...new installer code For example if you wish to change the Installer Code to 1 2 3 4 you would enter 0 1 2 3 4 7 The keypad will beep twice indicating that the new Installer Code has been accepted 8 Ent...

Страница 9: ...DC POWER SUPPLY AC POWER CAN ONLY BE USED WITH AC POWERED ELECTRIC STRIKES MAGNETIC LOCK OR ELECTRIC STRIKE MODEL TS 2 REQUEST TO EXIT STATION OPTIONAL USE N O CONTACTS Output 2 is used to control acc...

Страница 10: ...2 REQUEST TO EXIT STATION OPTIONAL USE N O CONTACTS N C DOOR CONTACT Two keypads are required for an inter lock system If either door is open the other door will remain locked TAMPER SWITCH The Tampe...

Страница 11: ...5 Relative Humidity Non condensing Environmental Rating Conforms to IP66 Dimensions 3 125 W x 4 5 L x 1 75 to 2 5 D CODES It is recommended that the Installer Code and User Codes be noted here for ref...

Страница 12: ...KP 400 Rev E 3 14...

Отзывы: