ASPIRCOMFORT PRO dH
5
ELECTRICAL CONNECTIONS
5.1 GENERAL
- Before starting any operation to perform the electrical connection make sure that the unit is not electrically
powered
- Perform the necessary electrical connections referring exclusively to the wiring diagram attached to this
manual.
- Install a suitable cut-off and breaker device exclusively serving the unit.
- It is essential for the unit to be earthed.
- Check that the electrical components chosen for installation (main switch, breakers, cable size and terminals)
are suitable for the electrical power of the installed unit and that they take into account the start-up currents of
the compressor in addition to the maximum achievable load. The relative data is stated on the attached wiring
diagram and on the unit’s rating plate
- It is forbidden to enter the unit with electrical cables except where specified in this file.
- Use duly-sized electrical cables and conductors that comply with the regulations in force in the various
countries.
- Strictly avoid feeding through the electrical cables so that they are directly touching pipes or parts inside the
unit
- After the first moments of operation, check the tightness of the power supply terminal screws
Table for power supply line sizing
Codes
AP20060
AP20062
Power supply
V/Ph/Hz
230/1/50
Max absorbed current
A
3.5
5.9