115
107750-01 - 9/17
XII. Operation
F. Changing Adjustable Parameters (continued)
Table 12.10: Parameters Changed Using the Boiler Type Parameter Selections:
Control Service
Part
107877-02
Altitude
0-2,000 ft.
2,001-6,000 ft.
Model
ASPN-320-02-N
ASPN-399-02-N ASPN-320-26-N
ASPN-399-26-N
Maximum Heat Rate
(RPM)
6,800
6,700
8,400
8,550
Minimum Heat Rate
(RPM)
1,450
1,400
2,450
2,625
Default Light off
Rate (RPM)
3,000
3,000
3,000
3,000
Model
ASPN-320-02-P
ASPN-399-02-P
ASPN-320-26-P
ASPN-399-26-P
Maximum Heat Rate
(RPM)
6,500
6,800
7,800
8,500
Minimum Heat Rate
(RPM)
1,300
1,250
2,350
2,500
Default Light off
Rate (RPM)
3,000
3,000
4,000
4,000
Altitude
6,001-7,800 ft.
7,801-10,100 ft.
Model
ASPN-320-67-N ASPN-399-67-N
ASPN-320-70-N
ASPN-399-70-N
Maximum Heat Rate
(RPM)
8,900
8,575
8,400
8,400
Minimum Heat Rate
(RPM)
2,500
2,650
2,550
2,600
Default Light off
Rate (RPM)
4,000
4,000
4,000
4,000
Model
ASPN-320-67-N
ASPN-399-67-N ASPN-320-70-P
ASPN-399-70-P
Maximum Heat Rate
(RPM)
8,200
7,500
7,500
6,250
Minimum Heat Rate
(RPM)
2,450
2,400
2,450
1,925
Default Light off
Rate (RPM)
4,000
4,000
4,000
4,000
Содержание ASPN-320
Страница 11: ...11 107750 01 9 17 IV Locating the Boiler continued Figure 4 1 Minimum Clearances To Combustible Construction ...
Страница 13: ...13 107750 01 9 17 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 88: ...88 107750 01 9 17 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Страница 89: ...89 107750 01 9 17 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Страница 90: ...90 107750 01 9 17 X Wiring continued CONDENSATE FLOAT SWITCH ...
Страница 91: ...91 107750 01 9 17 X Wiring continued Figure 10 6 Internal Wiring Connections Diagram ...
Страница 100: ...100 107750 01 9 17 Operating Instructions XI Start Up and Checkout continued ...
Страница 145: ...145 107750 01 9 17 XV Service Parts continued ...
Страница 147: ...147 107750 01 9 17 XV Service Parts continued All Models ...
Страница 149: ...149 107750 01 9 17 XV Service Parts continued All Models ...
Страница 151: ...151 107750 01 9 17 XV Service Parts continued All models ...
Страница 157: ...157 107750 01 9 17 ...
Страница 158: ...158 107750 01 9 17 ...
Страница 159: ...159 107750 01 9 17 ...
Страница 160: ...160 107750 01 9 17 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...