ADR141A /
ADR241A
Doc ID : ADR241A_IM_01
Ref ID : ADR241A/IM/SS
Rev No.
: 02
Page No. : 77 of 150
This setting is used to set the time-delay for Definite Time (C6) setting if selected for first stage ground
over current.
14.
IP>> Delay
0.05s
000 – 10.0s in steps of 0.01s
This setting is used to set the time-delay for second stage over current.
15.
IE>> Delay
0.05s
000 – 10.0s in steps of 0.01s
This setting is used to set the time-delay for second stage ground over current.
16.
BF Delay
50ms
000 – 800 msec.
This setting for the time-delay for the CBF trip.
17.
CT Secondary
1 A
1 A/5 A
This setting is used to set the CT Secondary
18.
CT Primary
10 A
10 – 5000A in step of 1A
This setting is used to set the CT Primary.
19.
Test Block
No
01 – 02 (1= Yes, 2= No)
This setting is used to enable (turn on) or disable (turn off) the CB Trip operation through relay HMI.
20.
Trip Circuit
No
01 – 02 (1= Yes, 2= No)
This setting is used to enable (turn on) or disable (turn off) Trip circuit supervision. This is used to
monitor trip coil which is used to trip the circuit breaker.
21.
Ann. Type
1
1 – 4
This setting is used select the annunciation type.
22.
Ann. Contact
1
01 –02 (1=SR, 2=HR)
This setting specifies to ann. contact can be set to Manual/Hand reset (HR) or Self reset (SR)
23.
Trip Contact
1
01 –02 (1=SR, 2=HR)
This setting specifies to Trip1 and Trip2 contact can be set to Manual/Hand reset (HR) or Self reset (SR)
24.
BF Contact
1
01 –02 (1=SR, 2=HR)
This setting specifies to BF contact can be set to Manual/Hand reset (HR) or Self reset (SR)
25.
Com Port
USB
USB/RS485
This setting specifies to select communication port for 103 communications.
26.
Set Parity
None
None/ Even/ Odd
This setting is used to set parity. It is important that both relay and master station are set with the same
parity setting.
27.
Baud Rate
57600
2400/ 4800/ 9600/ 14400/ 19200/ 28800/
38400/ 57600
This setting is used to set Baud rate It is important that both relay and master station are set with the
same Baud rate setting.
Содержание ADR141A
Страница 10: ...Page intentionally Left Blank...
Страница 16: ...Page intentionally Left Blank...
Страница 28: ...Page intentionally Left Blank...
Страница 43: ...Page intentionally Left Blank...
Страница 53: ...Page intentionally Left Blank...
Страница 69: ...Page intentionally Left Blank...
Страница 73: ...Page intentionally Left Blank...
Страница 74: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM SS Rev No 02 Page No 74 of 150 Section 6 Setting Sheet...
Страница 80: ...Page intentionally Left Blank...
Страница 92: ...Page intentionally Left Blank...
Страница 93: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM UG Rev No 02 Page No 93 of 150 Section 8 User Guide...
Страница 122: ...Page intentionally Left Blank...
Страница 123: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM FC Rev No 02 Page No 123 of 150 Section 9 Flow Chart...
Страница 136: ...Page intentionally Left Blank...
Страница 140: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM DR Rev No 02 Page No 140 of 150...
Страница 141: ...Page intentionally Left Blank...
Страница 151: ......