Asetek InRackCDU Installation, Operation & Maintenance Guide 14
5.8
Configure Monitoring System on Network
Default static IP address & subnet mask
IP address:
192.168.0.199
Gateway:
192.168.0.1
Subnet mask:
255.255.255.0
Configure the laptop to use the same subnet mask and gateway and an address in the subnet besides 199
and point a web browser at the IP address above. You will be asked for a user name and password. Two
levels of user name and password are provided: Standard Users and Administrators. Only Administrators
may change the network settings on the monitoring system. To log onto the monitoring system as an
administrator:
Username:
Admin
Password:
admin
Under the “Settings” heading on the left you will see a “Network” button. Select the Network button and
then de-select the DHCP: check box and enter the desired IP address, default gateway and subnet masks.
Additional information on the monitoring system is provided in the monitoring manual.
Recommended Setting of Monitoring System
Refering the leaflet of the InRackCDU system ”Recoomended Setting of Monitoring System”, please define
to setting values of Monitoring System.
Additional information on the monitoring system is provided in the monitoring manual.
Status LED
The CDU Cabinet has a colored status LED on the front bezel that lights up in Green, Yellow and Red.
Green Light
:
OK: System is operating without any warnings or alarms,
Yellow Brink:
Warning: One or more of the sensors, could be temperature, pressure or flow
sensors has reached its warning level
Red Brink:
Alarm: One or more of the sensors, could be temperature, liquid level,
pressure or flow sensors has reached its alarm level
Status LED