SPECIFIC NOTES: BATTERY CHARGE PRO
SPECIFIC NOTES: BATTERY CHARGE PRO
10.7. WARNING/FIRE SUPPRESSION SYSTEM
• The warning/fire suppression system offers the option of connection to a constantly manned building ma-
nagement system or fire alarm centre.
• Make use of this option so that trained rescue personnel can be quickly alerted and be on-site in a very short
time and, following an initial assessment of the situation, immediately initiate further measures (for example,
transporting the cabinet out of the building).
• In this way consequential damage to the building and personal injuries can be avoided.
• The extinguishing agent, based on calcium carbonates, is harmless in the necessary extinguishing agent con-
centration and has no harmful effects on the human organism
• In case of triggering, the aerosol is ejected at a high temperature and temperatures of over 300 °C are briefly
generated in front of and on the housing of the fire suppression cartridge (according to the manufacturer‘s
data, a minimum distance to combustible materials need not be maintained; however, a distance of at least
150 mm to the fire suppression cartridge should generally be maintained)
• After triggering of the fire suppression cartridge, ventilate the room and the cabinet well, observing the instruc-
tions in point 8.
ATTENTION:
The complete warning/fire suppression system is active only with mains operation.
The integrated smoke detector is part of the entire fire suppression system (direct power supply)
10.8. WARNING MESSAGE
>50 °C
1
2
3
sofern
aufgeschaltet
4
Actions
• immediate visual inspection of the system
by the company‘s own qualified personnel
• initiation of necessary actions
• if the interior temperature falls below 50 °C, the system returns to normal operation and the visual and
acoustic signals are switched off
.
10.9. ALARM STAGE 1
!
1
2
3
sofern
aufgeschaltet
4
Actions
• immediate visual inspection of the system
by technical personnel (e.g. fire brigade)
• subsequently, initiation of necessary actions
• if the smoke detector does not detect any further smoke development in the cabinet, the system can be reset
to normal operation by briefly disconnecting the mains voltage.
10.10. ALARM STAGE 2
>70 °C
1
2
3
sofern
aufgeschaltet
4
5
6
7
Actions
• immediate visual inspection of the system
by technical personnel (e.g. fire brigade)
• subsequently, initiation of necessary actions
• See 8.1
for the transport of the cabinets out of the building
ATTENTION:
Afterwards the complete system can only be assessed and if possible reset to normal operation
by authorised asecos service technicians. At least the fire suppression unit and the smoke
detector need to be replaced for this.
10.11. FALSE ALARM OF THE SMOKE DETECTOR
• By interrupting the power supply for a few seconds, the smoke detector is reset and the system returns to
normal operation