GENERAL NOTES
GENERAL NOTES
3. INSTALLATION
3.1. ALIGNMENT OF THE CABINETS
ATTENTION:
Door elements must not scrape against the fire prevention seals in the fold of the door when opening and
closing! Doors with an automatic closing mechanism must close automatically from every position and the
lock must be able to lock!
4×
2
max. 2× (!)
3
3.2. COMMISSIONING
• Before the first commissioning, the user must carry out an examination of the safety storage cabinet for pos-
sible damage, such as defective or loose sealing elements, correct alignment and perfect functioning of the
door elements (hinges, locking system and, if applicable, door closer).
• Use the cabinet and accessories only if they are in an orderly condition.
4. CLOSING
The doors are permanently self-closing.
The cabinets feature a cylinder lock with closing status indicator.
They can be integrated into a master key system.
ATTENTION:
The owner/user must ensure that all doors are kept closed whenever the contents of the cabinet are not
being accessed. In general, it must be noted that the cabinets do not possess an emergency unlocking
facility. This means that persons trapped inside the cabinet cannot free themselves!
5. INTERIOR EQUIPMENT
5.1. BOTTOM COLLECTING SUMP
1
2
According to EN 14470-1:
A bottom collecting sump must be
installed below the lowest storage level. The bottom collecting sump
must be able to hold a minimum volume of 10 % of all the containers
stored in the cabinet
1
or at least 110 % of the volume of the largest
single container
2
, whichever of these volumes is larger.
Leaks:
• Liquid in the sump is to be collected using suitable means.
• The choice of means is your own responsibility.
1
2
3
5.2. GRIDS / SHELVES WITH POWER SOCKET STRIPS
Load capacities
IO90.195.060.K9.WDC
IO90.195.120.K3.WDC
max.
25 kg
max.
75 kg
max.
50 kg
max.
180 kg
Standard interior
equipment
Standard interior
equipment
Only special
interior equipment:
Order No. 38520
Order No. 38521
Order No. 38522
Order No. 38523
Only interior
equipment with grids:
Order No. 38776 / 38772
Order No. 38777 / 38773
Order No. 38778 / 38774
Order No. 38779 / 38775
ATTENTION:
The positions of the shelves / grids and power socket strips are fixed and cannot be changed.
5.3. TOTAL POWER RATING OF THE POWER SOCKET STRIPS
Standard: single-phase, 230 V
Version
EU
CH
UK
FR
fusing
16 A
10 A
13 A
16 A
max. total power
3,68 kW
2,3 kW
2,99 kW
3,68 kW
Optional: 3-phase, 400 V, (accessory item HF.E.32822)
Note on model with a width of 600 mm IO90.195.060.K9.WDC: Only 2 of the 3 connected phases are
required by the cabinet electronics. The third phase remains unused
Version
EU
CH
UK
FR
fusing
3 x 16 A
3 x 10 A
3 x 13 A
3 x 16 A
max. total power
11,04 kW
6,9 kW
8,97 kW
11,04 kW
ATTENTION:
The load on the system is to be distributed as evenly as possible over the power socket strips! The
individual power strip must not be loaded with more than the specified power max. (see table)!
The necessary fuse protection is to be provided by the customer!