SPECIFIC NOTES: BATTERY CHARGE PRO
SPECIFIC NOTES: BATTERY CHARGE PRO
CAUTION:
Subsequent retrofitting is possible using the plug connection, so that no intervention in the electrical
components is required.
10.3. SELF TEST
Starts 5 seconds after
connection to the
mains supply
1
2
3
4
5
6a
6b
10.4. ERROR DURING SELF-TEST
1
2
5
3
5
sec
4
5
ATTENTION:
After pressing the reset button, the self-test begins again. If the error persists, please contact the asecos
Service Dept.
10.5. ERROR AND ALARM OVERVIEW
EVENT
LED GREEN
LED RED
ACOUSTIC ALARM
ACTIONS
Error during self-test off
on
5 signal tones
1.) Restart with RESET button
If error persists:
2.) Contact Service
Service interval
reached
flashing
off
off
Contact Service
Power failure
Flashes every
20 seconds
off
3 short signal tones
every 60 seconds
Check power supply
Warning message:
Temperature in the
cabinet >50 °C
off
on
long tone interval
(every 2 seconds for
250 ms)
see 10.8
Alarm stage 1:
Smoke detector
detects smoke in the
cabinet
off
on
medium tone interval
(every 0.5 seconds for
250 ms)
see 10.9
Alarm stage 2:
Smoke detector
detects smoke in the
cabinet, Tempera-
ture in the cabinet
>70 °C
off
flashing
short tone interval
(every 0.25 seconds for
125 ms)
see 10.10
10.6. POTENTIAL-FREE ALARM CONTACT
NOTE:
The potential-free alarm contact is for connecting a signal to a control room/control centre. A direct
connection to a fire alarm system is not recommended or may only be done in consultation with those
responsible for the system.
In general, however, the connection of the signal to a manned control room/control centre is
always recommended!
The connection of the potential-free switch contact must always be done by the customer (not a service
item).
(AC) / (DC)
(AC) / (DC)
Connector
Internal
alarm contact
Connection instructions
• Use only the supplied mating part (colour-coded black) to the plug for the connection
• The connection must be done by a qualified electrician
• The contact is designed for a max. DC voltage of 30 V or a max. AC voltage of 230 V
• The maximum current load is 10 A
• The switch contact is normally closed!
• The switch contact opens as soon as mains voltage is present and no error is pending (device is „ready to
operate“)