AC25/30Q-1 and -3 Operations Manual....
47
AGC CONTROL SCREEN
Automatic Gain Control is: ENABLED
Enable Disable Exit
7.6 AGC
CONTROL
Press the
SHORE POWER + F4
buttons to access the Automatic Gain Control (AGC)
CONTROL display.
This function enables or disables AGC. Press the Enable
(F1)
button to enable the feature, the
Disable
(F2)
button to disable the feature, and the Exit
(F5)
button to save the settings and exit.
Default Range
Automatic Gain Control
Enabled
Enabled, Disabled
Application: this function will compensate for changes in output voltage not already corrected by
hardware and software calibration such as load-dependent output voltage variances. This
function should be disabled before calibrating the hardware oscillator and current compensation
pots on the Modulator Interface PCB (usually only done when initially setting the output voltage
configuration at the factory). It must be disabled when using Converter Output Impedance
Control (see page 48).