AC15QTP And AC20QTP Operations Manual....
39
SHORE CORD SETUP CONV.CAPACITY:20.0kVA
MASTER CORD CAPACITY: 100 Amps
VOLTAGE: 208 Vac, FORM: 3
Ø
, Freq.: 60Hz
More Less Exit
ALARM AT % and ALARM enable settings, and Exit (
F5
) to save the settings and exit the
screen. When the cursor is on the ALARM AT % or ALARM enable settings, the Cord/Droop
buttons will change to More/Less and Enable/Disable respectively to allow for setting
adjustment.
Default
Range
Units
ALARM AT %
100%
50 - 100%
% of cord capacity
ALARM enable
DISABLED Disabled, Enabled
SHORE CORD RATING is displayed for reference and adjusted in the Shore Cord Setup screen.
7.3.2 Shore Cord Setup, Single, Master, or Slave Converters
The Shore Cord Setup screen is used to set the actual shore cord ampacity based on the marina’s
dock or pedestal circuit breaker. The converter’s new, programmed CONV. CAPACITY is then
displayed for reference. The converter’s Load Level and Power indicators for Shore Power and
Converter Power will then display the actual converter capacity usage based on the programmed
CONV. CAPACITY.
It is important to understand that this is an indication device, and affects reporting and alarming
only. The peak and average overload capabilities are not affected by this setting. Dynamic
response to loading and equipment startup surges is unaffected. The intent here is to prevent
tripping of dockside circuit breakers by average loading when a smaller than desired shore
supply is used.
From the front panel, press the
SHORE POWER
+
F2
buttons, and then Cord (
F1
) to access the