AC90SVHE-3 / AC100SVHE-3 Operations Manual....
21
5.2
ELECTRICAL INSTALLATION, cont.
FIGURE 6 INPUT AND OUTPUT CONNECTIONS
Prepare the power cables by removing approximately 6” of the outer cable insulation (in the case
of SO type portable cables). Install on each cable the appropriate 3/8” ring terminal required for
the size of cable chosen. Install the terminated cables onto the appropriate terminal block stud
using the supplied hardware, and tighten.
Replace the power cable access cover and front panel using the removed hardware.
Multi-cabinet systems connect outputs at the switchgear panel. It is recommended that
connection be made to the distribution bus through a manually operated disconnect device such as
a molded case switch or circuit breaker (rated for the total system amperage) for ease and safety of
service in the event of converter failure. The internal power contactors manage power control to
the distribution bus applying power through keypad, Auto-Restart, and remote control based
commands.