AC90SVHE-3 / AC100SVHE-3 Operations Manual....
20
5.2
ELECTRICAL INSTALLATION, cont.
INPUT WIRING MUST BE PERFORMED BY A QUALIFIED ELECTRICIAN
FAMILIAR WITH STANDARD SAFEGUARDS AND PROCEDURES REQUIRED BY
THE INSTALLATION OF THIS TYPE OF EQUIPMENT. POWER MUST BE
REMOVED FROM THE INPUT DISTRIBUTION SYSTEMS SUPPLYING POWER TO
THE AC90SVHE-3 / AC100SVHE-3 PRIOR TO THE START OF THE FOLLOWING
STEPS. INPUT POWER MUST BE SECURED (LOCKED) IN THE OFF
(DE-ENERGIZED)
STATE
UNTIL
INSTRUCTED
OTHERWISE
BY
THIS
DOCUMENT. ALSO SECURE IN THE OFF STATE ANY CIRCUIT BREAKER(S) IN
THE SWITCHGEAR PANEL THAT MAY BE SUPPLYING SHIP’S BUS POWER TO
THE CONVERTER OUTPUT TERMINAL BLOCK. FAILURE TO FOLLOW THESE
PROCEDURES CAN RESULT IN DAMAGE TO THE EQUIPMENT, AND CAN
PRESENT THE RISK OF INJURY OR DEATH TO THE INSTALLER OR THE
OPERATOR.
5.2.1 Input Power Connections
The converter is supplied with compression type terminal blocks for input power connections.
These terminal blocks accept wires in the range of 350MCM to 6AWG. Refer to the applicable
standards for selection of required wire gauge and type.
In two or more cabinet systems, one shore cord is connected to each converter shore power
terminal block.
5.2.2 Output Power Connections
The converter is supplied with compression type terminal blocks for output power connections.
These terminal blocks accept wires in the range of 350MCM to 6AWG. Refer to the applicable
standards for selection of required wire gauge and type.
The output ground wire is to be connected to a 3/8-16 UNC stud. Please refer to the Figure 6 on
page 21 for additional detail.