= 11

 - Selecting the active set point (SP/SP2) and heating/cooling

control mode with contact normally open: on  closing the digital
input (and after the “i.ti” time) the temperature set point “SP2” with
cooling action is activated. When instead the input is open the set
point “SP” with heating action is active.

= -1, -2, -3, -4, -5, -6, -7, -8, -9, -10 

- Like “i.Fi” with positive values

but with function logic reversed (contact normally closed)

4.4 - OUTPUTS AND BUZZER CONFIGURATION

The instrument outputs can be configured by the relative
parameters 

“o.o1” , “o.o2”.

The outputs can be configured for the following functions:

= ot

 - to control the compressor or however, the temperature

control device 

= dF

 - to control the defrosting device

= Fn

 - to control the fans

= Au

 - to control the auxiliary device

= At

 - to control a silenceable alarm device through a contact that

is normally open, and then closed when the alarm sounds

= AL

 - to control an alarm that cannot be silenced through a

contact that is normally open and closed when the alarm sounds.

= An

 - to control an alarm with a memory function through a

contact that is normally open and closed when the alarm sounds.

= -At

 - to control a silenceable alarm device through a contact that

is normally closed, and then open when the alarm sounds.

= -AL

 - control an alarm that cannot be silenced through a contact

that is normally closed and open when the alarm sounds.

= -An

 - to control an alarm with a memory function through a

contact that is normally closed and open when the alarm sounds
(see alarm memory).

= on

 - Output on when the instrument is in on state. This mode can

be used to control lights, non-misting resistance on room door or
other utilities

= oF

 - Disabled output

The function carried out for auxiliary output (par. desired output =
Au) is defined by the parameter 

“o.Fo”

 and the function is

conditioned by the time set in parameter 

“o.tu”.

The parameter “o.Fo” can be configured for the following functions:

= oF

  - Auxiliary output not active

= 1

 - Temperature control output delayed with contact normally

open: the auxiliary output is activated with delay that can be set on
the parameter "o.tu" compared to the output configured as ot. The
output is then turned off at the same time as the ot output is
disabled. This function mode can be used as a command for a
second compressor or for all other working utilities according to the
same ot output conditions, but which must be delayed after the
start up of the compressor to avoid excess electricity absorption.

= 2

 - Activation by front key (U or DOWN/AUX) or by digital input

with contact normally open: the output is activated by pressing the
keys U or DOWN/AUX suitably configured (“t.UF” or “t.Fb” = 1) or
via activation of the digital input if suitably configured (“i.Fi”=7).
These commands have a bi-stable function, Which means that
when first pressed, the output key is activated while the second is
disabled. In this mode, the AUX output can be turned off
automatically after a certain time that can be set on the parameter
"o.tu". With "o.tu" = oF the output is activated and deactivated only
manually, using the key (U or DOWN/AUX) or via the digital input.
Differently, the output, once activated, is turned off automatically
after the set time. This function can be used, for example, as a cell
light command, for non-misting resistance or other utilities.

= 3

 - Light output managed by Active set point ( "economy"

function). 
This output will be on in “normal” mode (Set Point "SP" active) and
off in economy mode operation (Set Point "SP2" active).

= 4

 - Internal Light output managed by digital input. This output will

be on when door is opened (“i.Fi”= 5, 6).
The internal buzzer (if present) can be configured by par. 

“o.bu”

for the following functions:

oF

 = Buzzer always disable

1

 = Buzzer signal active alarms only

2

 = Buzzer signal key pressed only (no alarm) 

3

 = Buzzer signal active alarms and key pressed

4.5 - ACTIVE SET POINT SELECTION

The instrument allows up to 2 different Set points to be pre-set
(

“SP”

 and 

“SP2”

) and then to choose which one to make active.

This function can be used if it is necessary to switch two different
function temperatures (e.g. day and night or positive and negative
etc). 
The active set point can be selected:
- Using the parameter 

“S.SA”

- using the key U if the parameter 

"t.UF"

 = 3.

- Using the key DOWN/AUX if the parameter 

"t.Fb"

 = 3.

- Using the digital input if the parameter. 

“i.Fi” 

= 8 or 11

The selection of the Set point active can  be also combined to the
function of switch off  Auxiliary output if used as light ("o.Fo" = 3)
and to Heating/Cooling change action by digital input ("i.Fi"=11).
The Set points  "SP" and "SP2" can be set with a value between
the programmed value in parameter.

 “S.LS”

  and the programmed

value in parameter 

“S.HS”.

Note:

 in the examples that follow, the Set point is generally

indicated as "SP", how when operating the instrument will work
according to the Set point selected as active.

4.6 - TEMPERATURE CONTROL

The regulation of the instrument is ON/OFF and acts on the output
configured as “ot” depending on the measuring of probe Pr1, of the
active Set Point

 “SP”

 

(or “SP2”)

, the intervention differential 

“r.d”

and the function mode 

“r.HC”

 .

Depending on the function mode programmed on the parameter
“r.HC” the differential is automatically considered by the regulator
with positive values for a Refrigeration control (“r.HC”=C) or with
negative values for a heating control   (“r.HC”=H).

SP

off

ON

r.HC=H

time

r.d

SP

Temp.

r.d

time

r.HC=C

ON

ON

ON

ON

ON

off

off

off

Pr1

Pr1

Temp.

Out

(ot)

(ot)

Out

In the event of probe error, it is possible to set the instrument so
that that the output continues to work in cycles according to the
times programmed in the parameter  

“r.t1”

 (activation time) and

“r.t2” 

(deactivation time).

If an error occurs on the probe the instrument activates the output
for the time “r.t1”, then deactivates it for the time “r.t2” and so on
whilst the error remains.
Programming “r.t1” = oF the output in probe error condition will
remain switched off.
Programming instead “r.t1” to any value and “r.t2” = oF the output
in probe error condition will remain switched on.
Remember that the temperature regulation function can be
conditioned by the “Continuous Cycle”, “Compressor Protection
and output delay at power-on”, “Defrost”, “Door open” and “external
alarm with outputs disable”  functions.

4.7 - COMPRESSOR PROTECTION FUNCTION AND DELAY AT
POWER-ON

The function “Compressor Protection” aims to avoid close start ups
of the compressor controlled by the instrument in cooling
applications.
This function foresees 3 time controls on the switching on of the
output configured as “ot” associated with the temperature
regulation request.
The protection consists of preventing the output being switched on
during the times set in the parameters

 

“P.P1”, “P.P2” and “P.P3”

and therefore that any activation occurs only after all the times has
finished.
First control (par. 

“P.P1”

 ) foresees a delay to the output activation

(switching-on delay).

ASCON TECNOLOGIC - Z31Y 

 

- OPERATING INSTRUCTIONS - Vr. 02 - 04/12 -  ISTR-MZ31YENG02 -  PAG. 5

Содержание Z31SY

Страница 1: ...4 10 1 ALARM FUNCTIONS 4 10 EVAPORATOR FANS CONTROL 4 9 DEFROST DISPLAY LOCK 4 8 4 END DEFROST 4 8 3 MANUAL DEFROST 4 8 2 AUTOMATIC DEFROST STARTS 4 8 1 DEFROST CONTROL 4 8 COMPRESSOR PROTECTION FUNCT...

Страница 2: ...status on off off and silenced or memorized flashing 11 Led AUX Indicates AUX output status on on off off or inhibited flashing 12 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 FAST PROG...

Страница 3: ...identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring the air and product temperature for the transport storage and distr...

Страница 4: ...nt is switched off peak values are always re set However it is also possible to reset these values if the instrument is switched on by using the DOWN key hold for 3 sec during peak visualization The d...

Страница 5: ...put will be on in normal mode Set Point SP active and off in economy mode operation Set Point SP2 active 4 Internal Light output managed by digital input This output will be on when door is opened i F...

Страница 6: ...lts that currently used in the refrigerators systems ct intervals with counts only the compressor function time output ot switched on Mode typically used in the positive temperature refrigerators syst...

Страница 7: ...1 differential Hysteresis The active defrost is shown on the instrument display with the lighting up of the DEFROST led At the end of defrosting it is possible to delay the new start up of the compre...

Страница 8: ...s the alarm signal when the alarm status ends To cancel the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory An or An it is necessary...

Страница 9: ...cessary that the device or instrument are being supplied USB SUPPLY AC SUPPLY SUPPLY ADAPTER 12 VDC USB For additional info please have a look at the A01 instruction manual 4 12 2 TVRY REMOTE DISPLAY...

Страница 10: ...obe Calibration i C2 10 oF oF 0 01 9 59 min sec Fan delay after defrost F Fd 37 oF oF on Fan status during defrost F FE 36 1 0 0 0 30 0 C F Differential fan control F dF 35 99 9 99 9 999 C F Low tempe...

Страница 11: ...rs relative to compressor protection and power on delay 99 5 min sec x10 1 0 255 MODBUS Station address for serial communication t AS 60 oF oF 999 Access Password to parameter functions t PP 59 oF oF...

Страница 12: ...21 990 25 C or NTC 103AT 2 10K 25 C 1 digital input for free voltage contacts alternative to Pr2 input Output s up to 2 relay outputs 5 A Res 6 4 A 8 3 A Out2 SPDT 8A 1 2HP 250V 1 3HP 125 VAC 12 A Res...

Страница 13: ...1000 4 4 2KV supply and relay outputs 1KV inputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V Directive 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C...

Отзывы: