In alarm conditions with “i.Fi”= 9 all the control outputs will be off.

4.10.3 - OPEN DOOR ALARM

The instrument can signal an open door alarm by activating the
digital input with the function programmed as  “i.Fi” = 5 or 6.
When the digital input is activated the instrument show 

oP

 and

after the delay programmed in parameter 

“A.oA”,

 the instrument

signals the alarm via the activation of the configured alarm output
(buzzer/ouput).
At the intervention of the open door alarm the inhibited output will
reactivated  (fans or fans + compressor).

4.11 - FUNCTIONING OF KEYS “U” AND “DOWN/AUX”

Two of the instrument keys, in addition to their normal functions,
can be configured to operate other commands.
The U key function can be defined by the parameter 

“t.UF”

 while

the DOWN/AUX key function can be defined by the parameter

“t.Fb”

Both the parameters have the same possibilities and can be
configured for the following functions:

=oF

 - The key carries out no function.

= 1

 - Pressing the key for at least 1 second, it is possible to

enable/disable the auxiliary output if configured  (“o.Fo”=2).

= 2

 - Pressing the key for at least 1 second, it is possible to

enable/disable a continuous cycle.

= 3

 - Pressing the key for at least 1 second, it is possible to select

one of the 2 memorised set point in rotation. Once selection has
been made, the display will flash the active set point code for about
1 sec. (SP, SP2).

= 4

 - Pressing the key for at least 1 second, it is possible to switch

the instrument from the ON status to Stand-by status and vice
versa.

4.12 - ACCESSORIES

The instrument is equipped with a connector that allows the
connection of some accessories described as follow.

4.12.1 - PARAMETERS CONFIGURATION BY “A01”

It is possible the transfer from and toward the instrument of the
functioning parameters through the device

 A01

 with 5 poles

connector.
This device A01 it’s mainly useable for the serial programming of
the instruments which need to have the same parameters
configuration or to keep a copy of the programming of an
instrument and allow its rapid retransmission.
The same device can connect the instrument via USB to a PC and
through the proper configuration software tools "TECNOLOGIC
UniversalConf”, it’s possible to configure the operating parameters.
To use the device A01 it’s necessary that the device or instrument
are being supplied.

USB

SUPPLY

AC SUPPLY 

SUPPLY ADAPTER

12 VDC

USB

For additional info, please have a look at the A01 instruction
manual.

4.12.2 - “TVRY” REMOTE DISPLAY

To the instrument it is possible to connect the remote display 

TVR

Y

 through the special cable that can have a maximum length of 10

m.  The device TVR Y, directly supplied by the instrument, it allows

to visualize the temperature measured by the probe Pr1 through a
2 ½ digit display.

SUPPLY

TVR Y

cable 10 m MAX.

For additional info, please have a look at the TVR Y instruction
manual.

4.12.3 - RS 485 SERIAL INTERFACE BY “TLCNV”

The instrument can be connected by a special cable to the

 TLCNV

device  (mod. C - TTL/RS485 interface), by means of which it is
possible to connect the regulator with a net to which other
instruments (regulators of PLC) are connected, all depending
typically on a personal computer used as plant supervisor. 
Using a personal computer it is possible to acquire all the function
information and to program all the instrument’s configuration
parameters. 
The software protocol adopted for the instrument is a MODBUS
RTU type, widely used in several PLC and supervision programs
available on the market (Y and Z series protocol manual is
available on request).
If the instrument is used with TLCNV program by the parameter

"t.Ad"

 the station Address.

Set a different number for each station, from 1 to 255.

Note: 

The baud-rate are fixed at 9600 baud.

TLCNV interface is directly supplied by the instrument.

SUPPLY

TLCNV

cable

6

5

4

8

7

9

ON

3

2

1

TX/RX

TTL

TLCNV

B

GND

A

RS 485

For additional info, please have a look at the TLCNV instruction
manual.

5 - PROGRAMMABLE PARAMETERS TABLE

Here below is a description of all the parameters available on the
instrument. Some of them may not   be present because depend
on the model/type of instrument.

0.0

-30.0 ÷ 30.0

°C/°F

Pr1 Probe  Calibration

i.C1

9

2.0

oF ÷ 20.0

sec

Measurement filter

i.Ft

8

C1

C0 / F0 / C1 /

F1

Unit of measurement
and resolution
(decimal point)
C0 = °C with 1° res.
F0 = °F with 1° res.
C1 =°C with 0,1° res.
F1 = °F with 0,1° res.

i.uP

7

nt

Pt / nt

Probes Type

i.SE

6

i. -parameters relative to inputs

0.0

S.LS ÷ S.HS

Set Point 2

SP2

5

0.0

S.LS ÷ S.HS

Set Point (1)

SP

4

1

1 ÷ 2

Active Set Point

S.SA

3

99.9

LS ÷ 999

Maximum Set Point 

S.HS

2

-50.0

-99.9 ÷ HS

Minimum Set Point 

S.LS

1

S. - parameters relative to Set Point

Note

Def.

Range

Description

Par.

ASCON TECNOLOGIC - Z31Y 

 

- OPERATING INSTRUCTIONS - Vr. 02 - 04/12 -  ISTR-MZ31YENG02 -  PAG. 9

Содержание Z31SY

Страница 1: ...4 10 1 ALARM FUNCTIONS 4 10 EVAPORATOR FANS CONTROL 4 9 DEFROST DISPLAY LOCK 4 8 4 END DEFROST 4 8 3 MANUAL DEFROST 4 8 2 AUTOMATIC DEFROST STARTS 4 8 1 DEFROST CONTROL 4 8 COMPRESSOR PROTECTION FUNCT...

Страница 2: ...status on off off and silenced or memorized flashing 11 Led AUX Indicates AUX output status on on off off or inhibited flashing 12 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 FAST PROG...

Страница 3: ...identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring the air and product temperature for the transport storage and distr...

Страница 4: ...nt is switched off peak values are always re set However it is also possible to reset these values if the instrument is switched on by using the DOWN key hold for 3 sec during peak visualization The d...

Страница 5: ...put will be on in normal mode Set Point SP active and off in economy mode operation Set Point SP2 active 4 Internal Light output managed by digital input This output will be on when door is opened i F...

Страница 6: ...lts that currently used in the refrigerators systems ct intervals with counts only the compressor function time output ot switched on Mode typically used in the positive temperature refrigerators syst...

Страница 7: ...1 differential Hysteresis The active defrost is shown on the instrument display with the lighting up of the DEFROST led At the end of defrosting it is possible to delay the new start up of the compre...

Страница 8: ...s the alarm signal when the alarm status ends To cancel the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory An or An it is necessary...

Страница 9: ...cessary that the device or instrument are being supplied USB SUPPLY AC SUPPLY SUPPLY ADAPTER 12 VDC USB For additional info please have a look at the A01 instruction manual 4 12 2 TVRY REMOTE DISPLAY...

Страница 10: ...obe Calibration i C2 10 oF oF 0 01 9 59 min sec Fan delay after defrost F Fd 37 oF oF on Fan status during defrost F FE 36 1 0 0 0 30 0 C F Differential fan control F dF 35 99 9 99 9 999 C F Low tempe...

Страница 11: ...rs relative to compressor protection and power on delay 99 5 min sec x10 1 0 255 MODBUS Station address for serial communication t AS 60 oF oF 999 Access Password to parameter functions t PP 59 oF oF...

Страница 12: ...21 990 25 C or NTC 103AT 2 10K 25 C 1 digital input for free voltage contacts alternative to Pr2 input Output s up to 2 relay outputs 5 A Res 6 4 A 8 3 A Out2 SPDT 8A 1 2HP 250V 1 3HP 125 VAC 12 A Res...

Страница 13: ...1000 4 4 2KV supply and relay outputs 1KV inputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V Directive 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C...

Отзывы: