background image

Ascon Tecnologic Srl - X33H

 

– OPERATING INSTRUCTIONS – MX33HENG00 - PAGE 8

 

=  2

  -  Activation  by  front  key  (U,  UP/F1,  DOWN/F2)  or  by  digital 

input:  the  output  is  activated  through  the  action  of  a  front  key 
suitably  configured  for  the  function  (=  2),  or  by  means  of  the 
activation  of  a  digital  input,  always  on  condition  it  is  correctly 
configured (=12). These commands have bistable operation, which 
means,  for  example,  that  upon  the  first  action  of  the  key  or  the 
digital  input,  the  output  is  activated,  while  upon  the  second,  it  is 
deactivated. In this mode, the AUS output can also be switched off 
automatically  after  a  certain  time,  which  can  be  set  in  the  "tuA" 
parameter.  With  "tuA"  =  OFF,  the  output  is  activated  and 
deactivated only manually; inversely, once it has been activated, the 
output is switched off automatically after the time set. This function 
can be used, for example, as a command for lights, for anti-fogging 
resistances, or for other utilities. 

 
4.13 - ALARM FUNCTIONS 

 

All  the  parameters  regarding  the  alarm  functions  are  contained  in 
the 

]

AL”

 group

.

 

Le alarm functions of the appliance act on the internal buzzer, if one 
is  present  and  configured  by  means  of  the  “buF”  par.,  and  on  the 
desired  output,  if  it  is  configured  by  means  of  the  “Out1”,  “Out2”, 
“Out3” or “Out4” parameters, in accordance with that which is set in 
the aforementioned parameters. 
The  possible  selections  of  these  parameters  for  the  functioning  of 
signalling alarms are: 

= ALt

 - when it is wished that the buzzer or the output be activated 

under an alarm condition and that they can be manually deactivated 
(alarm  silencing)  by  pressing  any  key  on  the  appliance  (typical 
application for an acoustic signal). 

= AL

 - when it is wished that the buzzer or the output be activated 

under  an  alarm  condition  but  that  they  cannot  be  manually 
deactivated and are hence deactivated only at the cessation of the 
alarm condition (typical application for a luminous signal). 

= ALL

 - when it is wished that the buzzer or the output be activated 

under an  alarm  condition  and  that  they  remain  activated also  after 
the  cessation  of  the  alarm  condition  (see  alarm  memory).  The 
deactivation  (recognition  of  the  alarm  memorized)  may  then  occur 
manually  by  pressing  any  key  only  after  the  alarm  has  terminated 
(typical application for a luminous signal). 

=  -ALt

  -  when  it  is  wished  to have  the  operation  described as  ALt 

but  with  inverse  operating  logic  (buzzer  or  output  activated  under 
normal condition and deactivated under an alarm condition). 

= -AL

 - when it is wished to have the operation described as AL but 

with  inverse  operating  logic  (buzzer  or  output  activated  under 
normal condition and deactivated under an alarm condition). 

= -ALL

 - when it is wished to have the operation described as ALL 

but  with  inverse  operating  logic  (buzzer  or  output  activated  under 
normal condition and deactivated under an alarm condition). 
Any  active  alarm  condition  is  signalled  on  the  display  of  the 
appliance by switching on the ALARM LED. 
Any  silenced  or  memorized  alarm  condition  is  signalled  by  the 
ALARM LED flashing. 
 
The alarm conditions of the appliance are: 
- Errors in Sensors 

“E1”, “-E1”, “E2, “-E2”, “E3”, “-E3”, “E4”, “-

E4” 

- Temperature alarms 

“HI 1”, “LO 1”, “HI 2”, “LO 2”, “HI 3”, “LO 

3”, “HI 4”, “LO 4” 

- External alarm 

“AL” 

- Door open alarm 

“AdoP”

 

 

4.13.1 - TEMPERATURE AND HUMIDITY ALARMS

 

The  temperature  and  humidity  alarms  act  on  the  basis  of  the 
measurement  of  the  Pr1,  Pr3  (temperature)  and  Pr4  (humidity) 
sensors, of the type of alarm set in the 

“Aty1”

“Aty2”,

 and 

“Aty4” 

parameters

,

  of  the  alarm  thresholds  set  in  the 

“HAL1”

“HAL3”,

 

and 

“HAL4”

 parameters (maximum alarms), 

“LAL1”, “LAL3”, 

and

 

“LAL4”

  parameters  (minimum  alarms),  and  of  the  related 

intervention differentials 

“dAL1”, “dAL3”, 

and 

“dAL4”.

 

Using the “Aty ” parameters, it is possible to establish whether the 
“HAL” and “LAL” alarm thresholds should be considered as absolute 
(“Aty”=Ab) or relative to the active Set Point (“Aty”=dE). 

In  the  event  of  relative  alarms  referring  to  the  Pr1  and  Pr3  inputs, 
the relative Set point will be the active temperature Set point “SPt”, 
while for the Pr4 input, it will be the active humidity Set point “SPh”. 
Some parameters may also be used to delay the enabling and the 
intervention of these alarms. 
These parameters are: 

“PAL1”,  “PAL3”, 

and 

“PAL4

  -  are  the  exclusion  times  for  the 

temperature (1,3) and humidity (4) alarms from the switching on of 
the  appliance  whenever  the  appliance  is  under  alarm  conditions 
when switching on. 

“ALd1”,  “ALd3”, 

and 

“ALd4”

  -  are  the  times  of  the  delays  in 

actuating the temperature (1,3) and humidity (4) alarms 

“dAd1”,  “dAd3”, 

and 

“dAd4”

  -  are  the  exclusion  times  of  the 

temperature  (1,3)  and  humidity  (4)  alarms  from  the  opening  of  the 
door. 

“dALd”

 - is the exclusion time of the temperature alarms referring 

to  the  Pr1  input  after  the  end  of  a  defrosting  cycle  (and,  if 
programmed, also of the dripping cycle). 
The alarms are enabled upon the expiry of the exclusion times and 
activate  after  the  “ALd”  time  when  the  temperature  or  humidity 
measured  by  the  related  sensor  rises  above  or  falls  below  the 
respective maximum and minimum alarm thresholds. 
The alarm thresholds will be the same as those set in the “HAL” and 
LAL” parameters if the alarms are absolute (“Aty”=Ab),

 

dAL1

dAL1

tim e

AL

off

O N

LAL1

HI 1

HAL1

Tem p.

Pr1

LO  1

off

off

O N

 

Example with absolute alarms of Pr1

 

or  they  will  be  the  [”SP”+”HAL”]  and  [”SP”+”LAL”]  values  if  the 
alarms are relative (“Aty”=dE). 

time

dAL1

dAL1

AL

off

ON

HI 1

LAL1

SPt

HAL1

Temp.

Pr1

LO 1

off

off

ON

 

Example with relative alarms of Pr1

 

The maximum and minimum alarms can be disabled by setting the 
related "HAL" and "LAL" parameters = OFF.  
 
At  the  same  time  as  the  alarm  signal  configured  (buzzer  and/or 
output), the appliance signals the alarm by switching on the ALARM 
LED, and showing on the display: 

HI 1

 in the case of maximum Pr1 temperature alarm  

LO 1

 in the case of minimum Pr1 temperature alarm  

HI 3

 in the case of maximum Pr3 temperature alarm  

LO 3

 in the case of minimum Pr3 temperature alarm  

HI 4

 in the case of maximum Pr4 humidity alarm  

LO 4

 in the case of minimum Pr4 humidity alarm  

The  error  message  will  be  displayed  alternatively  on  the  display 
which normally shows the variable that the alarm refers to. 
If  the  display  does  not  normally  show  the  variable  that  the  alarm 
refers  to,  the  alarm  message  will  be  shown  on  the  upper  display 
alternating with the variable established in the “diSU” par.. 
 

Содержание X33H

Страница 1: ...PARAMETER PROGRAMMING 2 5 CONFIGURATION OF THE PARAMETERS WITH A01 2 6 KEYPAD LOCK 3 WARNINGS FOR INSTALLATION AND USE 3 1 PERMITTED USE 3 2 MECHANICAL INSTALLATION 3 3 ELECTRICAL CONNECTIONS 3 4 ELE...

Страница 2: ...n the value set will be memorized and the display will then move on to read SP h humidity Set point and the value set for it To modify this value use the UP and DOWN keys The SP h Set point can be set...

Страница 3: ...ted with a 5 pole connector The A01 device can be used for the serial programming of appliances that must have the same configuration of the parameters or for keeping a copy of the programming of one...

Страница 4: ...upply the appliance can be in one of 2 different states ON means that the controller actuates the control functions STAND BY means that the controller does not actuate any function and the display is...

Страница 5: ...sabled The buF par allows the buzzer to be enabled YES or disabled no 4 4 TEMPERATURE REGULATOR All the parameters regarding the regulation of the temperature are contained in the rEG group The regula...

Страница 6: ...he appliance is switched on for the time set in the od par During the phase of delay upon switching on the display will show the indication od alternating with the normal programmed messages The delay...

Страница 7: ...hether the recycling fans must be switched on FdF On or whether they should switch off during defrosting FdF OFF In this last case it is possible to delay the re starting of the fans even after the en...

Страница 8: ...he alarm conditions of the appliance are Errors in Sensors E1 E1 E2 E2 E3 E3 E4 E4 Temperature alarms HI 1 LO 1 HI 2 LO 2 HI 3 LO 3 HI 4 LO 4 External alarm AL Door open alarm AdoP 4 13 1 TEMPERATURE...

Страница 9: ...upon the closure of the input and after the did time the alarm is activated and the appliance alternately shows on the upper display AL and the variable established in the diSU par 2 Signalling of an...

Страница 10: ...cle the cycle is interrupted and the appliance returns to the normal regulation state STOP 7 START PAUSE STOP mode When the command is given by key the cycle is started START If the key is pressed for...

Страница 11: ...the event that it is envisaged that the operator cannot be present at the end of this phase and thus cannot extract the product it is possible to program a third maintenance phase For this third phase...

Страница 12: ...temp Pr3 Measurement of OFF Pr1 Pr2 Pr3 Pr4 SPt SPh Pr4 Pr3 sensor auxiliary temp Pr4 Measurement of Pr4 sensor humidity SPt Active temperature Set Point SPh Active humidity Set Point rEG group param...

Страница 13: ...shold for high Pr3 temperature OFF 58 0 302 0 C F OFF 62 LAL3 Alarm threshold for low Pr3 temperature OFF 58 0 302 0 C F OFF 63 dAL3 Differential of Pr3 temperature alarms 0 0 30 0 C F 2 0 64 ALd3 Del...

Страница 14: ...t AL ALL On End HEAt 86 Out3 Configuration of operation of OUT3 output see Out1 OFF CooL HEAt rh drh dEF FAnr FAnE drhE LIGH AuS ALt rH 87 Out4 Configuration of operation of OUT4 output see Out1 OFF C...

Страница 15: ...encountered within 12 months of delivery The guarantee is limited to the repair or replacement of the product Any opening of the housing tampering with the appliance or non compliant use and installa...

Страница 16: ...measurement sampling 130 ms Display 4 digit 1 Red and 1 Amber yellow h 7 mm Class and structure of the software Class A Conformity Directives 2004 108 CE EN55022 class B EN61000 4 2 8KV air 4KV cont E...

Отзывы: