3.3 

Electrical Connections

General notes on electrical connections

•  The probe cables must be kept separated from high 

power voltage wiring.

3.3.1 

Electrical wiring

VDC

Out-RH

Control

i

Power supply voltage:

 9 ÷ 30 VDC;

Current consumption:

 20 mA;

Reverse polarity protection:

 Diode;

Cable length:

 2 meters.

4.  PROBLEMS AND MAINTENANCE

4.1 

Cleaning

We recommend to clean the instrument with a slightly wet 
cloth using water and not abrasive cleaners or solvents only.
Should it be necessary to remove the sensor, avoid to me-
chanical stress it and in particular avoid touching the humid-
ity sensor.

4.2 

Disposal

The appliance (or the product) must be 
disposed of separately in compliance 
with the local standards in force on 
waste disposal.

5.  WARRANTY AND REPAIRS

The instrument is under warranty against manufacturing 
flaws or faulty material, that are found within 18 months from 
delivery date.  The warranty is limited to repairs or to the 
replacement of the instrument.
The eventual opening of the housing, the violation of the instru-
ment or the improper use and installation of the product will 
bring about the immediate withdrawal of the warranty effects.
In the event of a faulty instrument, either within the period of 
warranty, or further to its expiry, please contact our sales de-
partment to obtain authorisation for sending the instrument 
to our company.
The faulty product must be shipped to Ascon Tecnologic with 
a detailed description of the faults found, without any fees or 
charge for Ascon Tecnologic, except in the event of alterna-
tive agreements.

6.  TEHNICAL DATA

6.1 

Sensor characteristics

Sensor type: 

CMOS-C.

6.1.1 

Relative humidity

Parameter

Condition Min. Typical Max.

Units

Resolution

12bit

0.04

%RH

8 bit

0.7

%RH

Accuracy/ 
Tolerance

Typical

±3.0

%RH

Max.

See figure

%RH

Repeatability

±0.1

%RH

Hysteresis

±1

%RH

Non-linearity

<0.1

%RH

Response time

t

63%

8

s

Operative range Extended

0

100 %RH

Long-term drift

Normal

<0.5

%RH/year

DRH (%RH)

Relative humidity (%RH)

0

10

20 30

40 50

60

70 80

90 100

±0

±2

±4

±6

±8

±10

Maximum tolerance
Typical tolerance