Ascon Tecnologic - TRH200 - USER MANUAL - PAG. 1

TRH200

RELATIVE HUMIDITY 

MEASUREMENT SENSOR

User manual 

22/10 - Code: ISTR_M_TRH200_E_01_--

ASCON TECNOLOGIC S.r.l.

Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY

TEL.: +39 0381 69871 - FAX: +39 0381 698730

sito: 

http:\\www.ascontecnologic.com

e-mail: 

[email protected]

PREFACE

 

D

This manual contains the information necessary for the 
product to be installed correctly and also instructions for 
its maintenance and use; we therefore recommend that 
the utmost attention is paid to the following instructions 
and to save it.

This document is the exclusive property of Ascon Tecnologic 
S.r.l. which forbids any reproduction and divulgation, even par-
tially, of the document, unless expressly authorized.
Ascon Tecnologic S.r.l. reserves the right to make any formal or 
functional changes at any moment and without any notice.
Ascon Tecnologic S.r.l. and its legal representatives do not 
assume any responsibility for any damage to people, things or 
animals deriving from violation, wrong or improper use or in 
any case not in compliance with the instrument features.

 

D

Whenever a failure or a malfunction of the device may 
cause dangerous situations for persons, thing or animals, 
please remember that the plant has to be equipped with 
additional devices which will guarantee safety.

1.  INSTRUMENT DESCRIPTION

1.1 

General description

The probes of the 

TRH200

 series are devices with 4 ÷ 20 mA 

current output for monitoring relative humidity characterized 
by a very low energy consumption. 
The 

TRH200

 uses a high-precision sensor and its conver-

sion / retransmission devices are of quality to ensure high 
reliability and excellent long-term stability.

2.  USAGE WARNINGS

2.1 

Admitted usage

 

D

The instrument has been projected and manufactured 
as a measuring and control device to be used accord-
ing to EN60730-1 at altitudes operation below 2000 m.

Using the instrument for applications not expressly permitted 
by the above mentioned rule must adopt all the necessary 
protective measures.
The instrument 

must not be used

 in dangerous environ-

ments (flammable or explosive) without adequate protections.

 

D

The installer must ensure that the EMC rules are 
respected, also after the instrument installation, if 
necessary using proper filters.

3.  INSTALLATION WARNINGS

3.1 

Mounting requirements

Select a mounting location having the following characteristics:

•  It should be easily accessible;
•  It must not be subjected to vibrations or impacts;
•  Must be free from corrosive gases;
•  Must be free from water or other fluids (condensation).

3.2 

Installation position

Wall fixing is done by clips.  Particular attention must be paid 
to the sensor positioning, it must be kept away from heat 
sources that can influence the humidity measurement.
It is a good idea to mount the probe with the sensor facing 
downwards (output cable upwards) and 

NEVER

 with the 

sensor facing upwards and also horizontally to avoid possi-
ble measurement errors due to self-heating.

NO

OK

NO

BEST

Cable

Any error in humidity measurement may be due to the settling 
time of the probe, in this case it will be necessary to wait for 
the time necessary to achieve a stable measurement.
Steam jets, water sprays, drafts, direct sun exposure, conden-
sation on the sensor or mounting on a wall made cold by the 
outside temperature can also cause important measurement 
errors; due to these conditions, during the installation, the 
probe must be protected from any possible external influence.