Ascon tecnologic TLY26 Скачать руководство пользователя страница 4

 

4 - FUNCTIONS

 

 

4.1 - MEASURING AND VISUALIZATION

 

All the parameters concerning measuring are contained in the group 

]

InP”. 

Via the parameter 

“SEnS”

 it is possible to select the type of probes 

that one wishes to use and which can be: thermistores PTC KTY81-
121 (Ptc) or NTC 103AT-2 (ntc). 
Once the type of probe used has been selected, through the 
parameter 

“Unit”, 

 it is possible to select the temperature unit of 

measurement (°C or°F) and, through the  parameter 

“dP”

, the 

resolution of the desired measurement (OFF=1°; On =0,1°). 
The instrument allows the measuring to be calibrated, that can be 
used for re-calibrating the instrument according to application 
needs, through the parameters 

“OFS1”

 (for the probe Pr1) and 

“OFS2” 

(for the probe Pr2). 

If probe Pr2 (evaporator) is not used, set the parameter 

“Pr 2”

 = OFF. 

Using the parameter

 “FiL”, 

it is possible to set the time constant for the 

software filter for measuring the input values to be able to reduce the 
sensitivity to measurement disturbances (increasing the time). 
Through the paragraph 

“diSP”,

 it is possible to fix the normal 

visualisation on the display that can be the measurement of the cell 
probe (Pr 1), the measurement of the evaporator probe (Pr 2), the set 
point of active regulation (SP), the current hour if the instrument has a 
clock (CLo) or it can have the numerical display switched off (OFF).  
Regardless of what is set in the parameter “diSP”, it is possible to 
visualise all the variables in rotation by pressing the key 

U

, the 

display will alternately show the code that identifies the variable (

Pr 

1

Pr 2

 and, if present the clock, 

CLo

) and its value. 

The exit of this visualisation mode occurs automatically 15 seconds 
after the last pressing on the key U. 
Please remember that visualisation of the probe Pr1 can be 
changed by the display block in defrosting  function too, by using the 
parameter “dLo” (see par. 4.6). 

 
4.2 - OUTPUTS CONFIGURATION 

The instrument outputs can be configured in the parameters group 

]

Out” 

where the relative parameters 

“Out1” , “Out2” “Out3” 

and

 

“Out4” 

are found. 

The outputs can be configured for the following functions 

= Out

 - to control the compressor or however, the temperature 

control device  

= dEF

 - to control the defrosting device 

= FAn

 - to control the fans 

= AuS

 - to control the auxiliary device (see par. 4.11) 

= ALt

 - to control a silenceable alarm device through a contact that 

is normally open, and then closed when the alarm sounds 

= AL

 - to control an alarm that cannot be silenced through a contact 

that is normally open and closed when the alarm sounds. 

= ALL

 - to control an alarm with a memory function through a 

contact that is normally open and closed when the alarm sounds. 

= -ALt

 - to control a silenceable alarm device through a contact that 

is normally closed, and then open when the alarm sounds. 

= -AL

 - control an alarm that cannot be silenced through a contact 

that is normally closed and open when the alarm sounds. 

= -ALL

 - to control an alarm with a memory function through a 

contact that is normally closed and open when the alarm sounds 
(see alarm memory). 

= OFF

 - Disabled output 

 
4.3 - TEMPERATURE CONTROL 

All the parameters concerning temperature regulation are contained 
in the group 

]

rEG”. 

The regulation of the instrument is ON/OFF and acts on the output 
configured as “Out” depending on the measuring of probe Pr1, of 
the active Set Point

 “SP”

 (1 or 2), the intervention differential 

“HSEt”

 and the function mode 

“Func”

Depending on the function mode programmed on the parameter 
“Func” the differential is automatically considered by the regulator 
with positive values for a Refrigeration control (“Func”=CooL) or with 
negative values for a heating control  (“Func”=HEAt). 

Out

SP

off

ON

HEAt

Out

time

HSEt

SP

Temp.

HSEt

time

CooL

ON

ON

ON

ON

ON

off

off

off

Pr1

Pr1

Temp.

 

In the event of cell probe error (Pr1), it is possible to set the 
instrument so that that the output “Out” continues to work in cycles 
according to the times programmed in the parameter  

“tonE”

 

(activation time) and 

“toFE” 

(deactivation time). 

If an error occurs on the probe Pr1 the instrument activates the 
output for the time “tonE”, then deactivates it for the time “toFE” and 
so on whilst the error remains. 
Programming “tonE” = OFF lthe output in probe error condition will 
remain switched off. 
Programming instead “tonE” to any value and “toFE” = OFF the 
output in probe error condition will remain switched on. 
Remember that the temperature regulation function can be 
conditioned by the “Continuous Cycle”, “Compressor Protection”, 
“Minimum compressor function time”, “Delay compressor start up 
after defrosting” and “inhibition of compressor close to defrosting” 
functions described below. 
 

4.4 - CONTINUOUS CYCLE FUNCTION

 

The instrument has a continuous cycle function  by which it is 
possible to maintain the configured output configured as “out” 
always active for the time set in parameter 

“tCC”

 (in the group 

]

rEG”)

  regardless of the temperature control command. 

The function can be used for example, when rapid lowering of the 
product temperature is required after the refrigerator loading phase. 
During the continuous cycle, the defrosting is inhibited and the 
temperature alarms are disabled during the entire cycle and also 
later for the time set in parameter 

“dALc”

 (see par. 4.9). 

Starting up a continuous cycle can only be done by a manual 
command using the U or DOWN/AUX (“UrSb” or “Fbd” = 2) keys or 
via the digital input (“diF”=3) if suitably programmed (see par. 4.10 
and 4.12). 
The continuous cycle in progress is shown on the display with the 
indication 

CC 

and can be stopped by a further action on the key or 

digital input (as for activation).  
The continuous cycle function cannot be activated during defrosting 
and with "tCC" = OFF. 

 
4.5 - COMPRESSOR PROTECTION FUNCTION AND DELAY AT 
POWER-ON 

All the parameters concerning the compressor protection functions 
and the delay at power on are contained in the group 

]

PrC”. 

The function “Compressor Protection” carried out by the machine 
aims to avoid close start ups of the compressor controlled by the 
instrument in cooling applications. 
This function foresees a time control on the switching on of the 
“Out” output associated with the temperature regulation request. 
The protection consists of preventing the output being switched on 
during the time set in the parameter 

“PtC”

 and counted depending 

on what has been programmed in the parameter 

“PSC”

, and 

therefore that any activation occurs only after the “PtC” time has 
finished. 
If during the power on delay phase, the regulator request should 
disappear, due to an inhibition caused by the compressor protection 
function, the foreseen start up of the output is naturally cancelled

Using the parameter

 

"PSC", it is possible to set the type of 

compressor protection and therefore from when the inhibition time 
“PtC” must start. 
The parameter “PSC”  can be set as: 

= 1

: Power on delay 

Ascon Tecnologic - TLY26

 

- OPERATING INSTRUCTIONS - Vr. 02 - 04/14 - ISTR MTLY26ENG02 - PAG. 4

 

Содержание TLY26

Страница 1: ... 2 OUTPUTS CONFIGURATION 4 3 TEMPERATURE CONTROL 4 4 CONTINUOUS CYCLE FUNCTION 4 5 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 6 DEFROST CONTROL 4 7 MANUAL DEFROST 4 8 EVAPORATOR FANS CONTROL 4 9 ALARM FUNCTIONS 4 9 1 TEMPERATURE ALARMS 4 9 2 EXTERNAL ALARM 4 9 3 OPEN DOOR ALARM 4 9 4 ALARM MEMORY 4 10 DIGITAL INPUT 4 11 AUXILIARY OUTPUT 4 12 FUNCTION OF KEYS U AND DOWN AUX 4 13 RS 485 ...

Страница 2: ...d rapidly Exiting the Set mode is achieved by pressing the P key or automatically if no key is pressed for 15 seconds After that time the display returns to the normal function mode 2 2 PARAMETERS PROGRAMMING To access the instrument s function parameters press the key P and keep it pressed for about 5 seconds after which the SET led will light up the display will visualised the code that identifi...

Страница 3: ...nstallation if necessary using proper filters Whenever a failure or a malfunction of the device may cause dangerous situations for persons thing or animals please remember that the plant has to be equipped with additional devices which will guarantee safety 3 2 MECHANICAL MOUNTING The instrument in case 33 x 75 mm is designed for flush in panel mounting Make a hole 29 x 71 mm and insert the instru...

Страница 4: ...on differential HSEt and the function mode Func Depending on the function mode programmed on the parameter Func the differential is automatically considered by the regulator with positive values for a Refrigeration control Func CooL or with negative values for a heating control Func HEAt Out SP off ON HEAt Out time HSEt SP Temp HSEt time CooL ON ON ON ON ON off off off Pr1 Pr1 Temp In the event of...

Страница 5: ... is not reached in the time set in the parameter dEFE defrosting is interrupted In order to avoid pointless defrosting the parameter tSdF is foreseen that sets the enablement temperature for defrosting If the temperature measured by the probe is higher than the one set in the parameter tSdF and in the parameter tEdF the defrosting is inhibited NO def defrost tEdF dEF off ON tSdF dint 1 Pr2 Temp de...

Страница 6: ...d in normal conditions and disabled in alarm status ALL when one wants the function described as ALL but with inverse working logic output activated in normal conditions and disabled in alarm status When no alarms are present the green LED OK is lit Any active alarm switch on the buzzer and is shown on the instrument display with the lighting up of the AL led and the switching off of the led OK Wh...

Страница 7: ...abled the alarm is activated and the instrument visualises AL and the variable set in parameter diSP alternately on the display 10 Switching on switching off Stand by of instrument with contact normally open on closing the input and after the did time the instrument is switched on while it is placed in Stand by when opened 1 defrosting commencement command with contact normally closed similar to d...

Страница 8: ... is made to enter the programming from the keyboard whilst a communication through the serial port is in progress the instrument will visualise buSy to indicate the busy state 4 14 ACCESSORIES 4 14 1 PARAMETERS CONFIGURATION BY KEY A01 The instrument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ASCON TECNOLOGI...

Страница 9: ...y Lock OFF display free On Lock on tempera ture Pr1 before defrost Lb Lock on label dEF during defrosting and PdEF during post defrosting On OFF Lb OFF 34 Etdu Differential display unlock after defrost 0 30 C F 2 0 Group FAn parameters relative to evaporator fan control Par Description Range Def Note 35 FCOF Fan status with compressor off On OFF On 36 FEdF Fan status during defrost On OFF OFF 37 F...

Страница 10: ...active Set Point 4 Switch on Switch off Stand by OFF 1 2 3 4 OFF 64 USrb Function mode key U see Fbd OFF 1 2 3 4 OFF 65 PASS Access Password to parameter functions OFF 9999 OFF Group SEr parameters relative to the serial communication Par Description Range Def Note 66 Add Station address in case of serial communication 0 255 1 Group CLO parameters relative to the internal clock Par Description Ran...

Страница 11: ...VDE Sampling rate 130 ms Installation category II Serial Interface RS485 insulated Measurement category I Communication protocol MODBUS RTU JBUS Protection class against electric shock Class II for Front panel Baud rate 9600 baud Insulation Reinforced insulation between the low voltage part relay outputs and front panel Reinforced insulation between the low voltage section relay outputs and the ex...

Отзывы: