Ascon tecnologic TLY26 Скачать руководство пользователя страница 10

Group 

]

din 

(parameters relative to digital input) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

55 

diF

  Function and function 

logic  of digital input: 
0 = No function 
1= Start defrost 
2= End defrost 
3= Continuous cycle 
4= External alarm 
5= Door open with fan 
block  
6= Door open with fan 
and compressor block 
7= Auxiliary output 
command 
8= Selection of active 
Set Point  
9= External alarm with 
deactivation of control 
outputs 
10= Switch on/Switch 
off (Stand-by) 

-10 / -9 / -8 / -

7 / -6 / -5 / -4 / 
-3 / -2 / -1 / 0 / 

1 / 2 / 3 / 4 / 5 

/ 6 / 7 / 8 / 9 / 

10 

0  

56 

did

  Delay in acquiring 

digital input 

OFF ÷ 99.59 

min.sec 

OFF  

Group 

]

AuS 

(parameters relative to auxiliary output) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

57 

FOA

  Function mode auxiliary 

output: 
0= No Function 
1= regulation output 
delayed 
2= manual activation by 
key or digital input. 

0 / 1 / 2 

 

58 

tuA

  Time relative to 

auxiliary output 

OFF ÷ 99.59 

min.sec 

OFF  

Group 

]

Out  

(parameters relative to configuration of outputs) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

59 

Out1

  Configuration of output 

function OUT1: 
OFF= No function 
Out= Temperature 
control (compressor) 
dEF= defrosting 
FAn= fans 
AuS= Auxiliary 
ALt= Silenceable alarm 
AL= Alarm not 
silenceable 
ALL= memorised alarm 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ 

-AL/ -ALL 

Out  

60 

Out2

  Configuration of output 

function OUT2: 
see “Out1” 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ 

-AL/ -ALL 

dEF  

61 

Out3

  Configuration of output 

function OUT3:  
see “Out1” 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ 

-AL/ -ALL 

FAn  

62 

Out4

  Configuration of output 

function OUT4/Buzzer:  
see “Out1” 

OFF/Out/dEF/ 

FAn/AuS/ALt/ 

AL/ALL/ -ALt/ 

-AL/ -ALL 

ALt  

Group 

]

PAn 

(parameters relative to configuration of the keyboard) 

Par.

 

Description

 

Range

 

Def.

 

Note

63

Fbd

  Function mode key 

DOWN/AUX: 
OFF= No function 
1= Auxiliary output 
command 
2= Continuous cycle 
command 
3= Selection of active 
Set Point 
4= Switch on/Switch off 
(Stand-by) 

OFF / 1 / 2 / 3 

/ 4 

OFF  

64

USrb

Function mode key U: 
see “Fbd” 

OFF / 1 / 2 / 3 

/ 4 

OFF  

65

PASS

Access Password to 
parameter functions  

OFF ÷ 9999 

OFF   

Group “

 ]

 SEr”

 (parameters relative to the serial communication) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

66

Add

  Station address in case 

of serial communication 

0 … 255 

 

Group 

]

CLO 

(parameters relative to the internal clock) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

67

StCL

Current time 

0.00 ÷ 23.59  

hrs.min 

0.00  

68

CLOF

Daily calibration of clock 

-20 ÷ 20 

sec 

0  

 

6 - PROBLEMS, MAINTENANCE AND WARRANTY

 

 
6.1 - SIGNALLING 
Error Signalling:

 

Error

 

Reason

 

Action 

 

E1 

-E1

 

The probe Pr1 may be 
interrupted or in short circuit, 
or may measure a value 
outside the range allowed 

Check the correct 
connection of the 
probe with the 
instrument and check 
the probe works 
correctly 

E2 

-E2

 

The probe Pr2 may be 
interrupted or in short circuit, 
or may measure a value 
outside the range allowed 

EEPr

 

Internal memory error 

Check 

and 

if 

necessary re-
programme the 
parameters function. 

In Cell probe error status, the output OUT behaves as set by the 
parameters “tonE” and “toFE”. 

 
Other Signalling:

 

Message

 

Reason

 

od

 

Delay in switching on in progress 

dEF

 

Defrosting in progress with  “dLo”=Lb 

PdEF

 

Post-defrosting in progress with “dLo”=Lb 

CC

 

Continuous cycle in progress 

HI

 

Maximum temperature alarm in progress 

LO

 

Minimum temperature alarm in progress 

AL

 

Digital input alarm in progress 

AP

 

Door open  

 

6.2 - CLEANING 

We recommend  cleaning of the instrument with a slightly wet cloth 
using water and not abrasive cleaners or solvents which may 
damage the instrument. 

 
6.3 - WARRANTY AND REPAIRS

 

The instrument is under warranty against manufacturing flaws or 
faulty material, that are found within 12 months from delivery date. 
The guarantee is limited to repairs or to the replacement of the 
instrument. 

Ascon Tecnologic - TLY26

 

- OPERATING INSTRUCTIONS - Vr. 02 - 04/14 - ISTR MTLY26ENG02 - PAG. 10

 

Содержание TLY26

Страница 1: ... 2 OUTPUTS CONFIGURATION 4 3 TEMPERATURE CONTROL 4 4 CONTINUOUS CYCLE FUNCTION 4 5 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 6 DEFROST CONTROL 4 7 MANUAL DEFROST 4 8 EVAPORATOR FANS CONTROL 4 9 ALARM FUNCTIONS 4 9 1 TEMPERATURE ALARMS 4 9 2 EXTERNAL ALARM 4 9 3 OPEN DOOR ALARM 4 9 4 ALARM MEMORY 4 10 DIGITAL INPUT 4 11 AUXILIARY OUTPUT 4 12 FUNCTION OF KEYS U AND DOWN AUX 4 13 RS 485 ...

Страница 2: ...d rapidly Exiting the Set mode is achieved by pressing the P key or automatically if no key is pressed for 15 seconds After that time the display returns to the normal function mode 2 2 PARAMETERS PROGRAMMING To access the instrument s function parameters press the key P and keep it pressed for about 5 seconds after which the SET led will light up the display will visualised the code that identifi...

Страница 3: ...nstallation if necessary using proper filters Whenever a failure or a malfunction of the device may cause dangerous situations for persons thing or animals please remember that the plant has to be equipped with additional devices which will guarantee safety 3 2 MECHANICAL MOUNTING The instrument in case 33 x 75 mm is designed for flush in panel mounting Make a hole 29 x 71 mm and insert the instru...

Страница 4: ...on differential HSEt and the function mode Func Depending on the function mode programmed on the parameter Func the differential is automatically considered by the regulator with positive values for a Refrigeration control Func CooL or with negative values for a heating control Func HEAt Out SP off ON HEAt Out time HSEt SP Temp HSEt time CooL ON ON ON ON ON off off off Pr1 Pr1 Temp In the event of...

Страница 5: ... is not reached in the time set in the parameter dEFE defrosting is interrupted In order to avoid pointless defrosting the parameter tSdF is foreseen that sets the enablement temperature for defrosting If the temperature measured by the probe is higher than the one set in the parameter tSdF and in the parameter tEdF the defrosting is inhibited NO def defrost tEdF dEF off ON tSdF dint 1 Pr2 Temp de...

Страница 6: ...d in normal conditions and disabled in alarm status ALL when one wants the function described as ALL but with inverse working logic output activated in normal conditions and disabled in alarm status When no alarms are present the green LED OK is lit Any active alarm switch on the buzzer and is shown on the instrument display with the lighting up of the AL led and the switching off of the led OK Wh...

Страница 7: ...abled the alarm is activated and the instrument visualises AL and the variable set in parameter diSP alternately on the display 10 Switching on switching off Stand by of instrument with contact normally open on closing the input and after the did time the instrument is switched on while it is placed in Stand by when opened 1 defrosting commencement command with contact normally closed similar to d...

Страница 8: ... is made to enter the programming from the keyboard whilst a communication through the serial port is in progress the instrument will visualise buSy to indicate the busy state 4 14 ACCESSORIES 4 14 1 PARAMETERS CONFIGURATION BY KEY A01 The instrument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ASCON TECNOLOGI...

Страница 9: ...y Lock OFF display free On Lock on tempera ture Pr1 before defrost Lb Lock on label dEF during defrosting and PdEF during post defrosting On OFF Lb OFF 34 Etdu Differential display unlock after defrost 0 30 C F 2 0 Group FAn parameters relative to evaporator fan control Par Description Range Def Note 35 FCOF Fan status with compressor off On OFF On 36 FEdF Fan status during defrost On OFF OFF 37 F...

Страница 10: ...active Set Point 4 Switch on Switch off Stand by OFF 1 2 3 4 OFF 64 USrb Function mode key U see Fbd OFF 1 2 3 4 OFF 65 PASS Access Password to parameter functions OFF 9999 OFF Group SEr parameters relative to the serial communication Par Description Range Def Note 66 Add Station address in case of serial communication 0 255 1 Group CLO parameters relative to the internal clock Par Description Ran...

Страница 11: ...VDE Sampling rate 130 ms Installation category II Serial Interface RS485 insulated Measurement category I Communication protocol MODBUS RTU JBUS Protection class against electric shock Class II for Front panel Baud rate 9600 baud Insulation Reinforced insulation between the low voltage part relay outputs and front panel Reinforced insulation between the low voltage section relay outputs and the ex...