Ascon Tecnologic - KX6 - ENGINEERING MANUAL - Vr. 0.0
PAG. 24
]
sp group - set point parameters
no. param.
description
dec.
point
values
default
60
nSP
Number of used set points
0
1... 4
1
61
SPLL
Minimum set point value
dP
From -1999 to SPHL
-1999
62
SPHL
Maximum set point value
dP
From SPLL to 9999
9999
63
SP
Set point 1
dP
From SPLL to SPLH
0
64
SP 2
Set point 2
dP
From SPLL to SPLH
0
65
SP 3
Set point 3
dP
From SPLL to SPLH
0
66
SP 4
Set point 4
dP
From SPLL to SPLH
0
67
A.SP
Selection of the active set point
0
From 1 (SP 1) to nSP
1
68
SP.rt
Remote set point type
0
rSP = The value coming from serial link is used as remote SP;
trin =
The value will be added to the local set point selected
by A.SP and the sum becomes the operative set point;
PErc = The value will be scaled on the input range and this
value will be used as remote SP.
trin
69
SPLr
Local/remote set point selection
0
Loc =
Local;
rEn = Remote.
Loc
70
SP.u
Rate of rise for
positive
set point
change (ramp UP)
2
0.01... 99.99 (inF) engineering units per minute
inF
71
SP.d
Rate of rise for
negAtive
set point
change (ramp DOWN)
2
0.01... 99.99 (inF) engineering units per minute
inF
]
pAn group - operator hmi parameters
no. param.
description
dec.
point
values
default
72
PAS2
Level 2 password (limited
access level)
0
- oFF (Level 2 not protected by password);
- 1... 200.
20
73
PAS3
Level 3 password (com-
plete configuration level)
0
3... 200
30
74
uSrb
button function during
RUN TIME
nonE = No function;
tunE = Auto-tune/self-tune enabling. A single press (longer than 1 se-
cond) starts the auto-tune;
oPLo = Manual mode. The first pressure puts the instrument in manual mode
(oPLo) while a second one puts the instrument in Auto mode;
AAc = Alarm reset;
ASi =
Alarm acknowledge;
St.by = Stand by mode. The first press puts the instrument in stand by
mode while a second one puts the instrument in Auto modet;
SP1.2 = SP/SP2 selection.
tunE
75
diSP
Middle display management
nonE = Standard display;
SPF = Final set point;
Spo =
Operative set point;
AL1 =
Alarm 1 threshold;
AL2 =
Alarm 2 threshold;
Po =
Power Output
0
76
di.cL
Colour of the upper display
0 = The display colour is used to show the actual deviation (PV - SP);
1 = Display red;
2 = Display green;
3 = Display orange.
0
77
AdE
Deviation for display colour
management
1... 9999 (E.U.)
5
78
diS.t
Display Timeout
2
- oFF (display always ON);
- 0.1... 99.59 (mm.ss).
oFF
79
fiLd
Filter on the displayed
value
1
- oFF (filter disabled);
- 1... 100 (E.U.).
oFF
80
dSPu
Instrument status at power
ON
AS.Pr = Starts in the same way it was prior to the power down;
Auto = Starts in Auto mode;
oP.0 = Starts in manual mode with a power output equal to zero;
St.bY = Starts in stand-by mode.
AS.Pr
81
oPr.E
Operative modes enabling
ALL =
All modes will be selectable by the next parameter;
Au.oP = Auto and manual (oPLo) mode only will be selectable by the next
parameter;
Au.Sb = Auto and Stand-by modes only will be selectable by the next parameter
ALL
82
oPEr
Operative mode selection
If oPr.E = ALL:
- Auto = Auto mode;
-
oPLo = Manual mode;
-
St.bY = Stand by mode;
If oPr.E = Au.oP: -
Auto = Auto mode;
- oPLo = Manual mode;
If oPr.E = Au.Sb: - Auto = Auto mode;
-
St.bY = Stand by mode.
Auto