Ascon Tecnologic - KX6 - ENGINEERING MANUAL - Vr. 0.0
PAG. 22
]
Al1 group
no. param.
description
dec.
point
values
default
19
AL1t
Alarm 1 type
0
nonE = Alarm not used;
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Windows alarm in alarm outside the windows;
LHAi = Windows alarm in alarm inside the windows;
SE.br = Sensor Break;
LodE = Deviation low alarm (relative);
HidE = Deviation high alarm (relative);
LHdo = Relative band alarm in alarm out of the band;
LHdi = Relative band alarm in alarm inside the band.
HiAb
20
Ab1
Alarm 1 function
0
0... 15:
+1 = Not active at power up;
+2 = Latched alarm (manual reset);
+4 = Acknowledgeable alarm;
+8 = Relative alarm not active at set point change.
0
21
AL1L
-
For High and low alarms, it is the low limit
of the AL1 threshold;
- For band alarm, it is low alarm threshold
dp
From -1999 to AL1H (E.U.)
-1999
22
AL1H
-
For High and low alarms, it is the high
limit of the AL1 threshold;
- For band alarm, it is high alarm threshold
dp
From AL1L to 9999 (E.U.)
9999
23
AL1
AL1 threshold
dp
From AL1L to AL1H (E.U.)
0
24
HAL1
AL1 hysteresis
dp
1... 9999 (E.U.)
1
25
AL1d
AL1 delay
0
From 0 (oFF) to 9999 (s)
oFF
26
AL1o
Alarm 1 enabling during Stand-by mode and
out of range conditions
0
0 = Alarm 1 disabled during Stand by and out of range;
1 = Alarm 1 enabled in stand by mode;
2 = Alarm 1 enabled in out of range condition;
3 = Alarm 1 enabled in stand by mode and in out of
range condition.
0
]
Al2 group
no. param.
description
dec.
point
values
default
27
AL2t
Alarm 2 type
0
nonE = Alarm not used;
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Windows alarm in alarm outside the windows;
LHAi = Windows alarm in alarm inside the windows;
SE.br = Sensor Break;
LodE = Deviation low alarm (relative);
HidE = Deviation high alarm (relative);
LHdo = Relative band alarm in alarm out of the band;
LHdi = Relative band alarm in alarm inside the band.
Loab
28
Ab2
Alarm 2 function
0
0... 15:
+1 = Not active at power up;
+2 = Latched alarm (manual reset);
+4 = Acknowledgeable alarm;
+8 = Relative alarm not active at set point change
0
29
AL2L
-
For High and low alarms, it is the low limit
of the AL2 threshold;
- For band alarm, it is low alarm threshold
dp
From -1999 to AL2H (E.U.)
-1999
30
AL2H
-
For High and low alarms, it is the high
limit of the AL2 threshold;
- For band alarm, it is high alarm threshold
dp
From AL2L to 9999 (E.U.)
9999
31
AL2
AL2 threshold
dp
From AL2L to AL2H (E.U.)
0
32
HAL2
AL2 hysteresis
dp
1... 9999 (E.U.)
1
33
AL2d
AL2 delay
0
From 0 (oFF) to 9999 (s)
oFF
34
AL2o
Alarm 2 enabling during Stand-by mode and
out of range conditions
0
0 = Alarm 2 disabled during Stand by and out of range;
1 = Alarm 2 enabled in stand by mode;
2 = Alarm 2 enabled in out of range condition;
3 = Alarm 2 enabled in stand by mode and in out of
range condition.
0