CONTROL FEATURES

(continued)

5--3

How to Set Optional Programmable Engine Exerciser (Accessory 11CD)

Proceed with care!

The automatic transfer switch is energized.

!

Setting the Clock (Time and Day)

Step

Press Button

Display

Meaning

1

reset

1234567 (blink)

00 00

¬

f

after self-test,

clears memory

2

hold

h

, then

press

±

1h

1 2 3 4 5 6 7

AM 12 00

¬

f

military 24 hr

or AM/PM

12 hr time

Note

Repeat step 2 to toggle between

military (blank display) and AM/PM time.

3

hold

¬

(clock symbol)

1234567 (blink)

00 00

¬

f

hold

¬

while

setting thru

step 7

4

±

1h

once

(if Daylight

Saving Time)

±

1h

do nothing if it

is Standard

Time.

5

h

(hold for

fast count)

[00] 00

hour

6

m

(hold for

fast count)

00 [00]

minute

7

Day

Mo Tu We Th Fr

Sa Su

day

8

release

¬

: blinking

time & date

set, clock starts

Programming Engine On-Off Period(s)

Step

Press Button

Display

Meaning

1

Prog.

(do not hold)

1 2 3 4 5 6 7

–– : ––

begin

2

hand

¬

on

3

h

start hour

4

m

start minute

start engine

5

Day

start day

Note

Successive pressing displays blocks of days:

Mon–Sat, Mon–Fri, Sat & Sun (1 is Monday)

6

Prog.

1 2 3 4 5 6 7

–– : ––

begin

7

Press

hand

(2 times)

f

off

8

h

stop hour

9

m

stop minute

stop engine

10

Day

stop day

11

¬

: blinking

program set

display

clock

button

Figure 5-2. Exerciser display and push buttons

program

button

1h

button
hour

button

minute

button

day

button

reset

button

on/off button

Changing or Checking Time Programs

By operating the

Prog.

button, the individual commands

as programmed can, at any time, be brought consecutively

into the display for revision or checking. Revisions are

accomplished by programming over the existing programs

using the steps at the left.

Canceling Time Programs

After the selecting the desired program, use the

h

and

m

buttons to set hours and minutes to zero; the

––:––

will

be displayed. This program has been made ineffective

and will no longer be carried out. To cancel all programs,

press the

Res. (reset)

button. This clears all memory

including the time base and program storage.

Manual Override

Do not manually override the exerciser unless

you are sure that the controller has been set for

exercise without load (see page 5–2). Failure to

do so could result in possible injury if the transfer

switch operates while the enclosure door is open.

!

Step

Press Button

Display

Meaning

1

hand

¬

hand

on

2

hand

[

¬

]

permanent on

3

hand

[

f

]

permanent off

4

hand

¬

f

back to automatic

Daylight Savings / Standard Time Change

To change to Daylight Savings time, press the

¦

1h

button

once. Clock advances by one hour and

+1h

appears in display.

To change to Standard Time, press the

¦

1h

button again; the

clock sets back one hour and

+1h

disappears.

Содержание Series 300

Страница 1: ...ble of causing shock burns or death WARNING is used in this manual to warn of possible personal injury CAUTION is used in this manual to warn of possible equipment damage Refer to the outline and wiring drawings provided with ASCO Series 300 ATS for all installation details 2000 amp size An experienced licensed electrician must install the ATS TABLE OF CONTENTS section INSTALLATION 1 SEQUENCE OF O...

Страница 2: ...ing Amperes Voltage Controller Enclosure B switched 1 standard G type 4 C type 1 F type 3R L type 12 3 three Ø 2 single Ø D 220 C 208 E 230 K 415 M 460 J 400 L 440 N 480 F 240 H 380 Q 575 P 550 R 600 2000 1600 1000 1200 blank solid blank open type type 4 12 enclosures are available only for 1000 1200 1600 amp sizes 1X if accessories ordered 3000 2600 terminal block TB for engine start and switch p...

Страница 3: ... nished with this switch and mount the Series 300 according to details and instructions shown on diagram Auxiliary Cable Box for 1000 2000 amp Anauxiliarycablebox isrequired ifthe powercables donot enter the enclosure directly adjacent to the terminal lugs for example if all power cables enter the top or bottom Order ASCO part no 609027 if needed Do not route the power cables along the sides of th...

Страница 4: ...n on the wiring diagram provided with this Series 300 Automatic Transfer Switch Make the necessary auxiliary connections by referring to Section 5 Control Features Harnesses The transfer switch is connected to the left side of the controller by a plug in harness two plugs TB Terminal Block field connections accepts wire range 22 12 AWG Engine Starting Signals 5 amps 32 V DC 5 amps resistive 28 V D...

Страница 5: ...closure door Locate and remove the maintenance handle and hub stored on the transfer switch frame Theninstall thehub ontothe centeroperator shaft and insert the handle firmly into the hole in the side of the hub spring fully compressed See Figure 1 3 and 1 4 and Table B 2 If the transfer switch is closed on Normal window shows CLOSED grasp handle firmly and turn it counterclock wise The transfer s...

Страница 6: ...pond only to the rated voltage specified on the Transfer Switch nameplate 1 Close the normal source circuit breaker The Transfer Switch Connected To Normal and the Normal Source Available lights should come on 2 Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres ent at the transfer switch normal source terminals 3 Close the emergency source circuit breaker Start g...

Страница 7: ...rting control in the automatic position 1 The normal source must be available and the generator must be ready to start Check that the Normal Source Available light is on 2 Press and hold the Transfer Switch Test button until the engine starts and runs This should happen within 15 sec TRANSFER SWITCH TEST 3 The Emergency Source Available light should come on 4 The transfer switch should transfer to...

Страница 8: ...immediately the sensor may accept it as soon as NR relay drops out When the emergency source is accepted by the sensor relay ER begins its timing cycle transfer to emergency delay ER relay is provided with an adjustable 0 to 5 minutes time delay on pickup to delay transfer of the load to the emergency source For immediate transfer press Bypass Time Delay button ER relay energizes the TS coil is en...

Страница 9: ...e harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged If the controller must be isolated follow these steps carefully Disconnecting the Plugs Do not unplug the controller until step 1a or 1b below is completed 1 Observe the position of the transfer switch a If the transfer switch is in the Normal position place standby engine starting control in the ...

Страница 10: ...inals EA and EC or EL1 and EL2 for 2 pole switches These are factory settings Transfer switch does not transfer the load to normal source when normal returns or when TRANSFER SWITCH TEST button is released Wait for Retransfer to Normal Delay 1 sec to 30 min to time out For immediate re transfer press BYPASS TIME DELAY button If Motor Load Transfer is active wait for in phase condition see below Vo...

Страница 11: ...ding DIP switch actuators Any change in these settings may affect the normal operation of the automatic transfer switch This change could allow the load circuits to remain connected to a low voltage source Table 4 2 Voltage and Frequency Settings Shaded DIP switches are standard factory settings DESCRIPTION LABELS SETTING of nominal S1 DIP DESCRIPTION LABELS SETTING FACT SET ADJ RANGE S1 DIP SWITC...

Страница 12: ...ar pointed tool to slide the switch actuators left or right so they match the il lustration next to the setting left off right on Recheck the setting See Figure 4 4 7 Install the cover on the controller by hooking it on the left side and latching the right side 8 Reconnect both harness plugs to the controller by aligning and pressing straight in until latches click Close the enclosure door 9 Close...

Страница 13: ...oldown Press to cancel an active exercise period stops generator Press and hold for 5 sec or until status light blinks rapidly to set exercise period immediately and every week hereafter generator starts Figure 5 1 Operator panel pushbuttons and light Select below either Exercise without Load or Exercise with Load according to the setting of DIP switch S1 actuator 8 The load transfers from the Nor...

Страница 14: ...uator 5 on 5 Exercise without Load Actuator 8 off 8 Exercise with Load Actuator 8 on 8 Shaded DIP switches are standard factory settings The Accessory 11CD Programmable Engine Exerciser incorporates a 7 day time base and therefore each day of the week can be uniquely programmed to test the engine generator set either with or without load The proper controller settings must be made to determine whe...

Страница 15: ... Exerciser display and push buttons program button 1h button hour button minute button day button reset button on off button Changing or Checking Time Programs By operating the Prog button the individual commands as programmed can at any time be brought consecutively into the display for revision or checking Revisions are accomplished by programming over the existing programs using the steps at th...

Страница 16: ...er Time delay between the load disconnect control signal and initiation of transfer is set on the controller with DIP switch S2 actuators 6 7 8 as shown below Delay Before Transfer LD TDBT S2 DIP SWITCH 0 disable Actuator 7 on Actuator 8 on 8 7 3 seconds Actuator 7 on Actuator 8 off 8 7 10 seconds Actuator 7 off Actuator 8 on 8 7 20 seconds Actuator 7 off Actuator 8 off 8 7 Shaded DIP switches are...

Страница 17: ...This optional accessory is available factory installed or in kit form Turn the thermostat s dial to required setting as shown dial turn counterclockwise to lower temperature turn clockwise to raise temperature thermostat AVAILABLE KITS FROM ASCO Controls Description Accessory Kit Programmable Engine Exerciser 11CD K601111 Serial Communication Module 72A K601110 Strip Heater Accessory 44 Descriptio...

Страница 18: ...ration of 1 1 warning 1 1 L labels engine starting contacts 1 2 inputs outputs 1 2 rating cover lights 1 4 5 1 load disconnect feature 5 4 lubrication 3 1 M maintenance preventive 3 1 manual load transfer 3 2 warning 3 2 manual operation 1 3 illustration of 1 3 warning 1 3 motor load transfer feature 5 3 N nameplate cover O operation electrical 1 4 manual 1 3 illustration of 1 3 warning 1 3 sequen...

Отзывы: