SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS

5--1

These timers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without
load transfer, or they can be completely disabled. The engine-generator should be exercised under load once a week for a
minimum time period of 20 minutes, or follow the recommendations of the engine-generator set manufacturer. Refer to
page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.

BUILT–IN ENGINE EXERCISER

The engine exerciser included in ASCO Series 300
Automatic Transfer Switches provides a once a week
20–minute exercise period. It occurs immediately when
the SET ENGINE EXERCISER push button is pressed
(and held for at least 5 seconds), and then at the same time
weekly thereafter. A 9 volt alkaline battery (

Duracell

R

MN1604,

Everready

R

522, or

Panasonic

R

6AM6) is

furnished and installed in the controller to maintain the
setting. The battery jumper block must be shifted to the
ON position. See Figure 4–2 on page 4–2.
Fill in day and time set. Week Day ______ Time _______.

DIP Switch Settings

FUNCTION

S1 DIP

SWITCH

S2 DIP

SWITCH

Std. Timer

Enabled

Actuator

7 on

7

Actuator

5 on

5

Std. Timer

Disabled

Actuator

7 off

7

Actuator

5 on

5

Exercise

without

Load

Actuator

8 off

8

Exercise

with Load

Actuator

8 on

8

Shaded DIP switches are standard factory settings.

status light

If

Exerciser with Load

is set,

transfers load to Emergency.

Press until light

FLASHES

If

Exercise with Load

is set,

retransfers load to Normal,

then stops generator after

5 min. cooldown.

Press to cancel an

active exercise period

(stops generator).

Press and hold for 5 sec. or until status

light blinks rapidly to set exercise period

immediately and every week hereafter

(generator starts).

Figure 5-1. Operator panel pushbuttons and light.

Select below either

Exercise without Load

or

Exercise with Load

according to the setting of DIP switch S1, actuator 8. The

load transfers from the Normal source to Emergency source (generator) and back again if

Exercise with Load

is selected.

Exercise without Load

, DIP Switch S1, Actuator 8 off

8

How to Set Built–In Timer

Step

Function

Explanation

Push Button

Status Light

1

SET ENGINE

EXERCISER

hold 5 sec.

blinks rapidly

FfFfFf

set exercise period

Exercise the generator now and

every week at this time hereafter.

2

release

blinks slowly

FffFff

exercise period now active

Generator starts and runs.

3

press

BYPASS

TIME DELAY

F

stays on

cancel active exercise period

Generator stops.

4

F

stays on

generator off

Exerciser enabled; repeats every 7 days.

Exercise with Load

, DIP Switch S1, Actuator 8 on

8

How to Set Built–In Timer

Step

Function

Explanation

Push Button

Status Light

1

SET ENGINE

EXERCISER

hold 5 sec.

blinks rapidly

FfFfFf

set exercise period

Exercise the generator now and

every week at this time hereafter.

2

release

blinks slowly

FffFff

exercise period now active

Generator starts and runs;

the load transfers to Emergency.

3

press

BYPASS

TIME DELAY

blinks slowly

FffFff

cancel active exercise period

The load retransfers to Normal; then

generator runs for 5 minute cooldown

( light blinks slowly during cooldown ).

4

F

stays on

generator off

Exerciser enabled; repeats every 7 days.

NOTE

: Every time

SET ENGINE EXERCISER

push button is pressed (held 5 seconds) the exercise period is changed.

Содержание Series 300

Страница 1: ...ble of causing shock burns or death WARNING is used in this manual to warn of possible personal injury CAUTION is used in this manual to warn of possible equipment damage Refer to the outline and wiring drawings provided with ASCO Series 300 ATS for all installation details 2000 amp size An experienced licensed electrician must install the ATS TABLE OF CONTENTS section INSTALLATION 1 SEQUENCE OF O...

Страница 2: ...ing Amperes Voltage Controller Enclosure B switched 1 standard G type 4 C type 1 F type 3R L type 12 3 three Ø 2 single Ø D 220 C 208 E 230 K 415 M 460 J 400 L 440 N 480 F 240 H 380 Q 575 P 550 R 600 2000 1600 1000 1200 blank solid blank open type type 4 12 enclosures are available only for 1000 1200 1600 amp sizes 1X if accessories ordered 3000 2600 terminal block TB for engine start and switch p...

Страница 3: ... nished with this switch and mount the Series 300 according to details and instructions shown on diagram Auxiliary Cable Box for 1000 2000 amp Anauxiliarycablebox isrequired ifthe powercables donot enter the enclosure directly adjacent to the terminal lugs for example if all power cables enter the top or bottom Order ASCO part no 609027 if needed Do not route the power cables along the sides of th...

Страница 4: ...n on the wiring diagram provided with this Series 300 Automatic Transfer Switch Make the necessary auxiliary connections by referring to Section 5 Control Features Harnesses The transfer switch is connected to the left side of the controller by a plug in harness two plugs TB Terminal Block field connections accepts wire range 22 12 AWG Engine Starting Signals 5 amps 32 V DC 5 amps resistive 28 V D...

Страница 5: ...closure door Locate and remove the maintenance handle and hub stored on the transfer switch frame Theninstall thehub ontothe centeroperator shaft and insert the handle firmly into the hole in the side of the hub spring fully compressed See Figure 1 3 and 1 4 and Table B 2 If the transfer switch is closed on Normal window shows CLOSED grasp handle firmly and turn it counterclock wise The transfer s...

Страница 6: ...pond only to the rated voltage specified on the Transfer Switch nameplate 1 Close the normal source circuit breaker The Transfer Switch Connected To Normal and the Normal Source Available lights should come on 2 Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres ent at the transfer switch normal source terminals 3 Close the emergency source circuit breaker Start g...

Страница 7: ...rting control in the automatic position 1 The normal source must be available and the generator must be ready to start Check that the Normal Source Available light is on 2 Press and hold the Transfer Switch Test button until the engine starts and runs This should happen within 15 sec TRANSFER SWITCH TEST 3 The Emergency Source Available light should come on 4 The transfer switch should transfer to...

Страница 8: ...immediately the sensor may accept it as soon as NR relay drops out When the emergency source is accepted by the sensor relay ER begins its timing cycle transfer to emergency delay ER relay is provided with an adjustable 0 to 5 minutes time delay on pickup to delay transfer of the load to the emergency source For immediate transfer press Bypass Time Delay button ER relay energizes the TS coil is en...

Страница 9: ...e harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged If the controller must be isolated follow these steps carefully Disconnecting the Plugs Do not unplug the controller until step 1a or 1b below is completed 1 Observe the position of the transfer switch a If the transfer switch is in the Normal position place standby engine starting control in the ...

Страница 10: ...inals EA and EC or EL1 and EL2 for 2 pole switches These are factory settings Transfer switch does not transfer the load to normal source when normal returns or when TRANSFER SWITCH TEST button is released Wait for Retransfer to Normal Delay 1 sec to 30 min to time out For immediate re transfer press BYPASS TIME DELAY button If Motor Load Transfer is active wait for in phase condition see below Vo...

Страница 11: ...ding DIP switch actuators Any change in these settings may affect the normal operation of the automatic transfer switch This change could allow the load circuits to remain connected to a low voltage source Table 4 2 Voltage and Frequency Settings Shaded DIP switches are standard factory settings DESCRIPTION LABELS SETTING of nominal S1 DIP DESCRIPTION LABELS SETTING FACT SET ADJ RANGE S1 DIP SWITC...

Страница 12: ...ar pointed tool to slide the switch actuators left or right so they match the il lustration next to the setting left off right on Recheck the setting See Figure 4 4 7 Install the cover on the controller by hooking it on the left side and latching the right side 8 Reconnect both harness plugs to the controller by aligning and pressing straight in until latches click Close the enclosure door 9 Close...

Страница 13: ...oldown Press to cancel an active exercise period stops generator Press and hold for 5 sec or until status light blinks rapidly to set exercise period immediately and every week hereafter generator starts Figure 5 1 Operator panel pushbuttons and light Select below either Exercise without Load or Exercise with Load according to the setting of DIP switch S1 actuator 8 The load transfers from the Nor...

Страница 14: ...uator 5 on 5 Exercise without Load Actuator 8 off 8 Exercise with Load Actuator 8 on 8 Shaded DIP switches are standard factory settings The Accessory 11CD Programmable Engine Exerciser incorporates a 7 day time base and therefore each day of the week can be uniquely programmed to test the engine generator set either with or without load The proper controller settings must be made to determine whe...

Страница 15: ... Exerciser display and push buttons program button 1h button hour button minute button day button reset button on off button Changing or Checking Time Programs By operating the Prog button the individual commands as programmed can at any time be brought consecutively into the display for revision or checking Revisions are accomplished by programming over the existing programs using the steps at th...

Страница 16: ...er Time delay between the load disconnect control signal and initiation of transfer is set on the controller with DIP switch S2 actuators 6 7 8 as shown below Delay Before Transfer LD TDBT S2 DIP SWITCH 0 disable Actuator 7 on Actuator 8 on 8 7 3 seconds Actuator 7 on Actuator 8 off 8 7 10 seconds Actuator 7 off Actuator 8 on 8 7 20 seconds Actuator 7 off Actuator 8 off 8 7 Shaded DIP switches are...

Страница 17: ...This optional accessory is available factory installed or in kit form Turn the thermostat s dial to required setting as shown dial turn counterclockwise to lower temperature turn clockwise to raise temperature thermostat AVAILABLE KITS FROM ASCO Controls Description Accessory Kit Programmable Engine Exerciser 11CD K601111 Serial Communication Module 72A K601110 Strip Heater Accessory 44 Descriptio...

Страница 18: ...ration of 1 1 warning 1 1 L labels engine starting contacts 1 2 inputs outputs 1 2 rating cover lights 1 4 5 1 load disconnect feature 5 4 lubrication 3 1 M maintenance preventive 3 1 manual load transfer 3 2 warning 3 2 manual operation 1 3 illustration of 1 3 warning 1 3 motor load transfer feature 5 3 N nameplate cover O operation electrical 1 4 manual 1 3 illustration of 1 3 warning 1 3 sequen...

Отзывы: