© 2020 ASCO Power Technologies. All Rights Reserved
3
IO-75024
01/2020
For access to self-service tools and chat support visit se.com/us/en/work/support or call 1-888-778-2733 for technical assistance
Model 159 (Edco HVCP-48)
Surge Protective Device (SPD)
Introduction
The
ASCO Model 159
is a hybrid surge protective device product featuring
DC power, data and video protection in one package. Each separate circuit
is capable of handling high-current impulses while tightly clamping transients
and allowing critical power and data to be transmitted.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462.
•
This equipment must only be installed and serviced by qualified electri
-
cal personnel.
•
Turn off all power supplying this equipment before working on or inside
equipment.
•
Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this
equipment.
•
This equipment must be effectively grounded per all applicable codes.
Use an equipment-grounding conductor to connect this equipment to the
power system ground.
•
Confirm that the Surge Protective Device voltage rating on the module
or nameplate label is not less than the operating voltage.
• Do not exceed the following current levels:
– DC Power Circuit - 1 Amp
– High Speed Data Circuit - 150mA
Failure to follow these instructions will result in death or serious injury.
WARNING:
This product can expose you to chemicals including
DINP, which is known to the State of California to cause cancer, and
DIDP which is known to the State of California to cause birth defects
or other reproductive harm. For more information go to: www.
P65Warnings.ca.gov.
NOTICE
LOSS OF SURGE SUPPRESSION
• Make certain that Surge Protective Device is disconnected from the
circuit it is protecting before conducting high potential insulation testing.
Failure to follow these instructions can result in equipment damage.
DANGER