Troubleshooting

The fixtures are flashing 
randomly when connected to 
the Data-Lynx O/P.

1.  The common cause of this is that they are responding 

to RDM data being transmitted by the Data-Lynx. If 
they are DMX512 compliant they should ignore this 
data. To overcome this, refer to the ‘Jumper - Advanced 
Configuration’ section and link the jumper to disable 
RDM. Alternatively this can be done via the web-
server.

When using a Data-Lynx 
O/P the fixture seems to lose 
DMX when set to high start 
addresses.

1.  Some older equipment cannot handle full rate DMX 

refresh rates. This results in it working on lower start 
addresses, but seeming ‘steppy’ on higher start 
addresses. To overcome this, use the web-server DMX 
settings page to slow down the refresh rate.

Data-Lynx O/P powers up 
but all the LED indicators are 
flashing continuously.

1.  This means that the unit has gone into boot loader 

mode. Uploading the latest firmware will allow the unit 
to function normally.

I changed my IP address and 
have lost all communication 
with the Data-Lynx O/P.

1.  If the IP address of a device is changed such that it is 

out of the range the PC is on, you must then change 
the PC IP address to match. If you still cannot discover 
the device, you will need to reset all custom settings to 
put it back into the default IP range (2.x.x.x). 

All the LED indicators flash 
three times when I change 
the Sub-Net wheel selector.

1.  If the Sub-Net value has been set remotely the front 

panel wheel is ignored. The LEDs flash to indicate this.

I have connected a Data-
Lynx O/P directly to a 
computer and there is no 
communication.

1.  Computer has incorrect IP address (IP address should 

be in the range 2.x.x.x).

2.  Incorrect network cable (should be a ‘cross-over’).

3.  A firewall is blocking transmitted/received data packets 

I have a Data-Lynx O/P but I 
want some to be inputs. Can 
I use some gender changers 
to make it an input?

1.  No, port configuration is a factory process.

An output port DMX LED is 
flashing continuously.

1.  When the port LED is flashing it means that the output 

is merging two universes.

I have connected 3 or more 
Data-Lynx units in series and 
the data seems to be delayed 
from the first to the last. 

1.  If several Data-Lynx units are connected in series 

then the data from the control source has to be re-
transmitted to each one. The more in series, the longer 
the delay. To overcome the delay use an ethernet 
switch and connect all Data-Lynx units and control 
sources to it.

Содержание Data-Lynx O/P

Страница 1: ...Data Lynx O P User Guide Artistic Licence Version 1 8 Data Lynx O P User Guide ...

Страница 2: ... inside the outer case of this product Always disconnect from the power supply when not in use Any specific IP rating where appropriate is given in the instructions Unless otherwise stated this product is designed for indoor use only If used outdoors it MUST be installed in an appropriate IP rated cabinet Do not allow this product to be exposed to rain or moisture Do not allow liquid to penetrate ...

Страница 3: ... Net Select 9 Data Connection Ethernet 10 11 Data Connection DMX O P 1 2 12 13 Data Connection DMX O P 3 4 14 15 Data Connection DMX O P 5 6 16 17 Data Connection DMX O P 7 8 18 19 Data Connection DMX O P 9 10 20 21 Data Connection DMX O P 11 12 22 Data Connection Ethernet 23 Replaceable Fuse Mains I P Fuse 24 Power Connection Universal Mains I P Connection ...

Страница 4: ...5 Ethercon connections one front one back The product accepts Art Net the public domain protocol invented by Artistic Licence and sACN the standard managed under ESTA PLASA E1 31 Data Lynx O P requires Cat 5 cable or better and supports 10BaseT and 100BaseT Power Supply Earthing The internal power supply requires an input in the range 90 250 VAC with an Earth connection The mains fuse should only ...

Страница 5: ...icators pictured opposite have the following meanings STAT ON when unit is powered flashing if hardware fault see Error Messages NET ON when network data is active DMX 1 2 ON when data is transmitted flashing if merging two universes see DMX Workshop Power up During power up the LEDs will step sequentially Boot loader When in boot loader mode see page 8 all the LEDs will flash continuously If all ...

Страница 6: ... output information as shown in the screen shot opposite Right clicking on any entry brings up a menu that offers various functionality y y The Configure Node option enables configuration of the Universe Sub Net and Net values It also allows the user to give the device a short and long name y y Copy to clipboard enables all the node information to be pasted into a support request email y y Merge C...

Страница 7: ...lled by a DHCP server check the Enable DHCP box to activate this feature Note that the default IP and static addressing all ports can be forced manually by the following procedure 1 Set the Sub Net wheel to 9 2 Power cycle turn off then on again 3 Power off 4 Set the Sub Net wheel to F 5 Power on IP Address Configuration Web Server To configure Data Lynx O P via the internal web server either type...

Страница 8: ...y JP4 10 x x x IP addressing active ignored when DHCP is active JP5 RDM disabled on all outputs JP6 Inverts the low byte of the IP address JP7 For future use ROM Boot Switch to boot loader mode on power cycle ROM Boot Jumper Data Lynx O P has boot loader firmware programmed into its ROM This forces the product into a factory ROM mode ready for firmware upload The boot loader firmware allows the op...

Страница 9: ...M Fault Net All alternately flashing E2Prom Fault Port 1 All alternately flashing System ROM Fault Contact Artistic Licence for advice Application Diagram PSU DMX RDM interface e g Multichrome D1 Art Net Controller e g Colour Tramp RGB Pixels Data Lynx O P Art Net DMX RDM DMX RDM In this example Data Lynx O P converts Art Net from a Colour Tramp controller into DMX RDM data This is fed into intell...

Страница 10: ... range the PC is on you must then change the PC IP address to match If you still cannot discover the device you will need to reset all custom settings to put it back into the default IP range 2 x x x All the LED indicators flash three times when I change the Sub Net wheel selector 1 If the Sub Net value has been set remotely the front panel wheel is ignored The LEDs flash to indicate this I have c...

Страница 11: ...low blow y y DC fuse internal resettable fuse for control electronics Ethernet y y Type 10 100BaseT y y Isolation 1 kV y y PoE n a DMX512 Outputs y y Output mode ground referenced y y Output isolation n a y y Output ESD protection 12 kV y y Output voltage protection 80 V y y Output conditioning slew rate limited Control y y Input Protocols Art Net sACN y y Output Protocols DMX512 DMX512 1990 DMX51...

Страница 12: ...he appropriate CE FCC and RoHS regulations Product specific information is available on request Waste Electrical Electronic Equipment WEEE Artistic Licence is a member of a WEEE compliance scheme and will happily recycle any of our products that you at your expense return to us Due to our policy of continuing product improvement specifications are subject to change without notice Artistic Licence ...

Отзывы: