36
-
0MNPVESA52LUA
S
TRING
B
OX
Measures
Register
Bit
Name
Description
Units
20
I_String_1
String current, input 1
0.1 A
21
I_String_2
String current, input 2
0.1 A
22
I_String_3
String current, input 3
0.1 A
23
I_String_4
String current, input 4
0.1 A
24
I_String_5
String current, input 5
0.1 A
25
I_String_6
String current, input 6
0.1 A
26
I_String_7
String current, input 7
0.1 A
27
I_String_8
String current, input 8
0.1 A
28
29
30
31
32
33
34
35
36
V_REF
Reference voltage
0.001 V
37
V_IN
Input voltage
0.1 V
38
Analog1
Generic analog
39
Analog2
Generic analog
40
HwConfig
(Internal use)
41
Temp1
Probe 1 temperature
0.1 K
42
Temp2
Probe 2 temperature
0.1 K
43
4_20MA low
16
0.001 mA
44
4_20MA high
45
0_10V low
0.001 V
46
0_10V high
47
48
49
50
Dip-switch
dip-switch reading
Lower 8 bits
51
Generic I/O
I/O generic reading
Lower 8 bits
52
NumAlarms
Number of alarms
N in [0:65535]
53
54
55
56
57
58
59
16
The values of the two probes are transmitted on two words.