35
-
0MNPVESA52LUA
Characterization register map
Register
Name
Vers.
Centr.
EVO
EASY
Description
801
INVTYPE
1.2.5
1.0.0
Lower nibble: HHV/HV/Standard Standard=1, HV=2, HHV=3
bit 15 (0x8000) = 1 -> Transformer.
bit 14 (0x4000) = 1 -> Easy/Evo Model
bit 13 (0x2000) = 1-> Battery charger
802
AC_PRO
1.2.5
No
Active probes, lower nibble, bit = 1, active probe
803-818
P1_UNIT
1.2.5
No
Probe #1 identification string
819-834
P2_UNIT
1.2.5
No
Probe #2 identification string
835-850
P3_UNIT
1.2.5
No
Probe #3 identification string
851-866
P4_UNIT
1.2.5
No
Probe #4 identification string
867
P1_MAX
1.2.5
No
Maximum value of probe #1
868
P2_MAX
1.2.5
No
Maximum value of probe #2
869
P3_MAX
1.2.5
No
Maximum value of probe #3
870
P4_MAX
1.2.5
No
Maximum value of probe #4
871
KPV_AC
1.2.5
No
Value of Kpv/Ac (%)
DC-box register map
Register
Name
Vers.
Centr.
EVO
EASY
Description
901
NUM_DC
1.2.5
No
Number of Dc-box configured.
13
902
DC_A1M1
1.2.5
No
First current of first module
14
(0.1A units)
903
DC_A2M1
1.2.5
No
Second current of first module (0.1A units)
…
…
1.2.5
No
…
909
DC_A8M1
1.2.5
No
Eight current of first module (0.1A units)
910
DC_A1M2
1.2.5
No
First current of second module (0.1A units)
…
…
1.2.5
No
…
917
DC_A8M2
1.2.5
No
Eight current of second module (0.1A units)
918
DC_A1M3
1.2.5
No
First current of third module (0.1A units)
…
…
1.2.5
No
…
925
DC_A8M3
1.2.5
No
Eight current of third module (0.1A units)
926
DC_A1M4
1.2.5
No
First current of fourth module (0.1A units)
…
…
…
…
933
DC_A8M4
1.2.5
No
Eight current of fourth module (0.1A units)
934
DC_ALM1
1.2.5
No
Alarms of first module
15
935
DC_ALM2
1.2.5
No
Alarms of second module
936
DC_ALM3
1.2.5
No
Alarms of third module
937
DC_ALM4
1.2.5
No
Alarms of fourth module
938
DC_W1M1
1.2.5
No
First weight of first module (%)
939
DC_W2M1
1.2.5
No
Second weight of first module (%)
…
945
DC_W8M1
1.2.5
No
Eight weight of first module (%)
946
DC_W1M2
1.2.5
No
First weight of second module (%)
…
953
DC_W8M2
1.2.5
No
Eight weight of second module (%)
954
DC_W1M3
1.2.5
No
First weight of third module (%)
…
961
DC_W8M3
1.2.5
No
Eight weight of third module (%)
962
DC_W1M4
1.2.5
No
First weight of fourth module (%)
…
969
DC_W8M4
1.2.5
No
Eight weight of fourth module
13
The number of modules ranges from 1 to 4. The maximum number of measures is 32, 8 for each module.
14
If the value is positive, it’s a valid measure. If the value is 0xFFFF, the measure belongs to a non-configured
module; if the measure belongs to a configured module, but it’s in timeout, the value is 0xFEFE.
15
If the value is zero, there are no alarms on the corresponding module. If the value is different from zero,