Installation and Maintenance

EHU-600 Series Humidifiers

8

7.

Control Humidistat

The Series EHU-600 is compatible with any humidistat with the follow-
ing characteristics:
NOTE: Use of shielded wire or wiring in conduit is recommended for
control wiring.
a.

4-20 Milliamps, See Fig. 8-2 for wiring instructions. Note: Printed
Circuit Board has 500 ohm impedance for this type input signal.
Some  4-20 inputs may require a floating ground. Change stat
grounding selector on PC Board. See Figure 9-1.

b. 2-10 Volts, See Fig. 8-2 for wiring instructions. Note: Printed Circuit

Board has 500 ohm impedance for this type input signal. The load
resistor may be removed to increase input impedance, consult factory.

c.

0-135 Ohms, See Fig. 8-3 for wiring instructions.

d. On/Off, See Fig. 8-4 for wiring instructions.
e.

Armstrong Humidistat. See Fig. 8-5 for wiring instructions.

d. Connect the dispersion tube to the steam generator using

minimum 1 1/4" nom. (EHU-600) or 1 1/2" (EHU-601/602) size
hard copper tube (customer supplied) and the two short hoses
supplied with the humidifier. See Figures 7-1 and 8-1. Insulate
the copper tube to minimize condensation. Long runs of pipe
and/or high duct static pressure may require 1 1/2" or 2" copper
pipe. See Figure 8-6.

If the optional 10 ft. flexible steam hose is used, cut the steam
hose to length as required. Wipe out the inside of each hose end
before installing. Connect the cut end of the hose to the dispersion
tube. Tighten all hose clamps.

e. If duct static pressure and piping back pressure exceeds 4" W.C.

please consult factory for special mounting procedures.

Steam hose or pipe must be free of loops, kinks, and sags to
allow for gravity drainage of condensate. (Provide pitch of 1"
per foot.) Hose supports may be required to accomplish this.

Figure 8-1: Connection at Unit

Figure 8-2: 4-20 Milliamps Humidistat

2-10 Volts Humidistat

Please consult factory for additional information on wiring
A18609, A18610, or A17888 Armstrong Humidistats.

Figure 8-4: On/Off Humidistat

Figure 8-3: 0-135 Ohms Humidistat

Figure 8-5: Armstrong Humidistat

Lb. / Hr. Steam

Figure 8-6:

Pressure Loss in Copper Pipe

(40 Feet Equivalent Run)

GND

+Input

500 OHM Input
Impedence ON
4-20 mA/2-10V
Stat. Selection

4-20 mA Stat.

OR

2-10 V Stat.

+5VDC

+Input

Brown

Orange

Opens with Increase
in Humidity

ON/OFF Stat.

AMW Part No.
A-8581 or
A-8581-A

0 – 135 OHM
STAT.

AMW PART NO.
A-8821

HUMIDITY
INCREASE

+5VDC

G N D

+INPUT

B L A C K

WHITE

R E D

Common

1.9-3.9 Vdc. Input

12 Vac Power

White

Green

Black

25

Armstrong

26

Solid State

27

Humidistat

AMW Part No.

C-1471 or

C-1472

1-3/8" O.D. (1-1/4" Nom.)
Copper Tube

Insulation

EHU

Cabinet

Top

Hose Clamps

Rubber Hose Cuff

Steam Generator Tank

Содержание EHF-2

Страница 1: ...midifier to function to its full capability be certain to install in accordance with Armstrong recommendations These installation and maintenance guidelines should be used by experienced person nel as...

Страница 2: ...Control humidistat 8 High limit duct humidistat 9 Fan interlock switch 10 Wiring diagrams 11 Capacity chart 12 Physical data 13 Submittal drawings C Principle of Operation Page 15 1 Operation 2 Sugge...

Страница 3: ...applicable building plumbing and electrical codes 3 Site Selection See Fig 3 1 Electronic steam humidifiers should be installed in locations that allow routine inspection and accessibility for mainte...

Страница 4: ...a wall by means of 3 8 diameter lag screws or other suitable fasteners capable of supporting the maximum operating weight of the humidifier Model EHU 600 Making sure the humidifier is level hold it ag...

Страница 5: ...se only wire with copper conductors rated 90o C or higher for high voltage and grounding g Avoid running high voltage wire next to PC board Use bottom knockout for high voltage wire inlet 3 Water Fill...

Страница 6: ...and type of steam dispersion tube has been selected See Chart 6 1 for proper dispersion tube lengths The standard dispersion tube has a built in slope to allow for gravity drainage of condensate back...

Страница 7: ...city per Tube Figure 7 4 Disperson Tube Below Steam Outlet on Humidifier c Insert the dispersion tube into the duct so the holes face upward Never install the tube with the holes facing downward Faste...

Страница 8: ...e 8 6 If the optional 10 ft flexible steam hose is used cut the steam hose to length as required Wipe out the inside of each hose end before installing Connect the cut end of the hose to the dispersio...

Страница 9: ...mounted control humidistats Armstrong Part C1472 are also available for installation where sensing and control from return air or exhaust air ducts is preferable Mounting The Armstrong Control Humidis...

Страница 10: ...e humidifier steam output at the proper modulated rate to maintain 40 RH The humidstat will send a 1 9 to 3 9 Vdc signal to the humidifier as the space humidity drops from 42 5 to 37 5 RH 2 5 RH throt...

Страница 11: ...trong Part A9023 All Pressure and electrical connections and set point adjustments are on side for each installation Temperature limit 32 F to 180 F Maximum surge pressure 10 psig Rated pressure 45 H2...

Страница 12: ...Installation and Maintenance EHU 600 Series Humidifiers 12 10 Wiring Diagram Figure 12 1 EHU 600 Wiring Diagram...

Страница 13: ...7 4 8 45 17 7 7 20 9 1 23 10 5 30 13 7 35 16 50 22 8 55 25 60 27 3 69 31 4 86 39 2 36 3 5 8 50 19 8 7 22 10 26 11 8 33 15 38 17 3 55 25 61 27 8 66 30 77 35 96 43 7 42 0 8 6 60 22 10 26 11 8 30 13 7 38...

Страница 14: ...ply Front 151 2 394 35 16 84 35 16 84 L Electrical Supply Side 31 8 80 2 51 2 51 M Electrical Supply Front 41 2 114 21 2 64 21 2 64 N Fan Height EHF 2 13 330 N A N A N A N A N Fan Height EHF 3 16 406...

Страница 15: ...uce steam Fig 15 1 When the water level rises as shown in Fig 15 2 increased electrical current flows through the water producing more steam This increase will continue until the required output of st...

Страница 16: ...HU 600 Series has a patented self regulating maximum output feature that eliminates manual adjustment and improves humidity control In low demand situations units with greater capacity can quickly ove...

Страница 17: ...circuit shall provide automatic protection from excessive current and high water overflow k The humidifier fill water line s shall have an air gap to prevent backflow syphoning of contami nated water...

Страница 18: ...the tank water After extended use repeated lighting of the Tank Full light indicates that in spite of periodic draining of mineral laden water the steam generator should be inspected and either clean...

Страница 19: ...k See Figure 19 1 7 Disconnect the control wiring to terminals 3 and 23 High Limit Humidistat and terminals 2 and 24 Air Proving Switch then jumper them out with the tabs provided or a short piece of...

Страница 20: ...y increasing the water s conductivity b If Tank Full light illuminates with water level below midway point in the tank the back pressure due to duct static or steam dispersion piping is too high Consu...

Страница 21: ...verify that it is working Look at the tube mounting plate there is anArmstrong A Logo or UP sticker which should be pointing up If not the tube will not drain properly See Figure 21 1 22 When using EH...

Страница 22: ...so this maintenance is required when you can least afford to perform it Hopefully understanding the problem and possible solutions will help avoid problems in the first place How water affects the EH...

Страница 23: ...mineral accumulations from the water This is a bottom blowdown so if minerals stick to the sides of the steam generator they will accumulate The standard drain interval is every 30 minutes for the EHU...

Страница 24: ...proper operation The water is too pure when the Tank Full light comes on excessively e Magnetic Treatment Magnetic coils designed to allow water to be magnetized have been found useful in some instanc...

Страница 25: ...ution Muriatic acid can cause severe chemical burns if not handled properly Wear rubber gloves and eye protection when using Read and follow carefully the safety procedures on the package a Obtain sev...

Страница 26: ...or tank Make sure all electrical connections are tight see Page 6 Check unit for proper operation 4 Electrode Installation Models EHU 601 and EHU 602 Three Phase a Clean the inside of the steam genera...

Страница 27: ...crew as shown Tighten the nuts and screw A 7 16 socket on an extension makes this step and the next much easier and safer c Set the two flat washers in place as shown Then set the inner electrode in p...

Страница 28: ...Figure 28 1 Model EHU 600 3 Phase Figure 28 2 Model EHU 600 1 Phase Model EHU 600 is shown above Models EHU 601 and EHU 602 are similar but some part numbers are different Parts Description 1 Hose Cla...

Страница 29: ...nk This signals that the diagnostics routine has begun For the purpose of the diagnostic function the lights on the front panel of the humidifier correspond to assigned input and output circuits Note...

Страница 30: ...dified or stat is mis wired or malfunctioning If All the lights are on then all controls are allowing the humidifier to fill In case of component malfunction consult your Armstrong Represen tative or...

Страница 31: ...cker with Contactor cycles or B W G or without sensor or pigtail chatters Unit fills continuously G B W 5 demand lights flicker with Contactor chatters or without sensor or pigtail Unit will not fill...

Страница 32: ...remedy with respect to the above limited warranty or with respect to any other claim relating to the products or to defects or any condition or use of the products supplied by Armstrong however cause...

Отзывы: